Object Name
ALM_SP_A_F
ALM_SP_B_F
ALM_SP_C_F
ALM_PD_P_A_F
ALM_PD_P_B_F
ALM_OIL_P_A_F
ALM_OIL_P_B_F
ALM_OIL_P_C_F
ALM_ECO_P_A_F
ALM_ECO_P_B_F
ALM_ECO_P_C_F
ALM_FC_IN_P_A_F
ALM_FC_IN_P_B_F
ALM_FC_OUT_P_A_F
ALM_FC_OUT_P_B_F
ALM_HP_APPROACH_P_A_F
ALM_HP_APPROACH_P_B_F
ALM_WATER_P_1_F
ALM_WATER_P_2_F
ALM_WATER_P_3_F
ALM_WATER_P_4_F
ALM_WATER_P_TOO_HIGH
ALM_WATER_P_TOO_LOW
ALM_WATER_FILTER_DIRTY
ALM_CPA_COM_F
ALM_CPB_COM_F
ALM_CPC_COM_F
ALM_SIOB_CIR_A_COM_F
ALM_SIOB_CIR_B_COM_F
Back to Beginning of Chapter – Table of Contents
ECG–UG–14-002
30XAXW
BACnet Option
BV
201
IR
BV
202
IR
BV
203
IR
BV
204
IR
BV
205
IR
BV
206
IR
BV
207
IR
BV
208
IR
BV
209
IR
BV
210
IR
BV
211
IR
BV
212
IR
BV
213
IR
BV
214
IR
BV
215
IR
BV
216
IR
BV
217
IR
BV
218
IR
BV
219
IR
BV
220
IR
BV
221
IR
BV
222
IR
BV
223
IR
BV
224
IR
BV
225
IR
BV
226
IR
BV
227
IR
BV
228
IR
BV
229
IR
REVISION
Rev G
March 2017
Description
0
RO
Circuit A Suction Transducer
0
RO
Circuit B Suction Transducer
0
RO
Circuit C Suction Transducer
Circuit A Reclaim Pumpdown
0
RO
Pressure Transducer
Circuit B Reclaim Pumpdown
0
RO
Pressure Transducer
0
RO
Circuit A Oil Pressure Transducer
0
RO
Circuit B Oil Pressure Transducer
0
RO
Circuit C Oil Pressure Transducer
Circuit A Economizer Pressure
0
RO
Transducer
Circuit B Economizer Pressure
0
RO
Transducer
Circuit C Economizer Pressure
0
RO
Transducer
Circuit A Free Cooling Pump Inlet
0
RO
Pressure Transducer
Circuit B Free Cooling Pump Inlet
0
RO
Pressure Transducer
Circuit A Free Cooling Pump Outlet
0
RO
Pressure Transducer
Circuit B Free Cooling Pump Outlet
0
RO
Pressure Transducer
Circuit A Heatpump Approach
0
RO
Pressure Transducer
Circuit B Heatpump Approach
0
RO
Pressure Transducer
Water Pressure before cooler
0
RO
Transducer
Water Pressure after cooler
0
RO
Transducer
Water Pressure before filter
0
RO
Transducer
Water Pressure after filter
0
RO
Transducer
0
RO
Water Pressure too high
Water Pressure too low - pump
0
RO
cavitaion risks
0
RO
Water filter dirty
Loss of communication with
0
RO
Compressor Board A
Loss of communication with
0
RO
Compressor Board B
Loss of communication with
0
RO
Compressor Board C
Loss of communication with SIOB
0
RO
Board Number A
0
RO
Loss of communication with SIOB
DATE
PAGE
28 OF 56

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

30xa

Table of Contents