Carrier 30XW User Manual page 26

Touch pilot control bacnet option
Table of Contents

Advertisement

Object Name
SERVICE1_ewt_cirA
SERVICE1_leak_thr
SERVICE1_leak_tmr
SERVICE1_metric
SERVICE1_cur_offA
SERVICE1_cur_offB
SERVICE1_cur_offC
CP_UNABL_un_cp_a
CP_UNABL_un_cp_b
CP_UNABL_un_cp_c
MST_SLV_ms_sel
MST_SLV_ms_ctrl
MST_SLV_slv_addr
MST_SLV_lead_sel
MST_SLV_ll_bal_d
MST_SLV_lstr_tim
MST_SLV_lead_pul
MST_SLV_start_dt
MST_SLV_lag_mini
MST_SLV_lag_pump
MST_SLV_ll_serie
BACNET_bacena
BACNET_bacunit
BACNET_network
BACNET_ident
BACNET_bbmd
SETPOINT_csp1
SETPOINT_csp2
SETPOINT_ice_sp
SETPOINT_cramp_sp
SETPOINT_hsp1
SETPOINT_hsp2
SETPOINT_hramp_sp
SETPOINT_cauto_sp
SETPOINT_hauto_sp
SETPOINT_w_sct_sp
SETPOINT_lim_sp1
SETPOINT_lim_sp2
SETPOINT_lim_sp3
SETPOINT_rsp
SETPOINT_hr_deadb
GENUNIT_CHIL_S_S_wr
PUMPSTAT_HPUMP_1_wr
PUMPSTAT_HPUMP_2_wr
PUMPSTAT_CPUMP_1_wr
Back to Beginning of Chapter – Table of Contents
ECG–UG–14-002
30XAXW
BACnet Option
BV
155
AV
329
AV
330
BV
156
AV
331
AV
332
AV
333
BV
157
BV
158
BV
159
AV
334
AV
335
AV
336
AV
337
AV
338
AV
339
AV
340
AV
341
AV
342
AV
343
BV
160
BV
161
BV
162
AV
344
AV
345
AV
346
AV
347
AV
348
AV
349
AV
350
AV
351
AV
352
AV
353
AV
354
AV
355
AV
356
AV
357
AV
358
AV
359
AV
360
AV
361
BV
163
CMD
BV
164
CMD
BV
165
CMD
BV
166
CMD
REVISION
Rev G
March 2017
Description
0
RO
EWT Probe on cir A side
0
RO
Leakage charge Threshold
0
RO
Leakage charge Timer
0
RO
metric
0
RO
Current offset cir A
0
RO
Current offset cir B
0
RO
Current offset cir C
0
RO
Compressor A Disable
0
RO
Compressor B Disable
0
RO
Compressor C Disable
0
RO
Master/Slave Select
0
RO
Master Control Type
0
RO
Slave Address
0
RO
Lead Lag Select
0
RO
Lead/Lag Balance Delta
0
RO
Lead/Lag Start Timer
0
RO
Lead Pulldown Time
0
RO
Lag Unit Pump Control
0
RO
Lag Minimum Running Time
0
RO
Lag Unit Pump Control
0
RO
Chiller In Series
0
RO
BACnet Enable
0
RO
Metric Unit
0
RO
Network
0
RO
Identifier
0
RO
BACnet Management Device
0
RW
Cooling Setpoint 1
0
RW
Cooling Setpoint 2
0
RW
Cooling Ice Setpoint
0
RW
Cooling Ramp Loading
0
RW
Heating Setpoint 1
0
RW
Heating Setpoint 2
0
RW
Heating Ramp Loading
0
RW
Cool Changeover Setpt
0
RW
Heat Changeover Setpt
0
RW
Water Val Condensing Stp
0
RW
Switch Limit Setpoint 1
0
RW
Switch Limit Setpoint 2
0
RW
Switch Limit Setpoint 3
0
RW
Reclaim Setpoint
0
RW
Reclaim Deadband
0
RW
Chiller Start/Stop
0
RW
Condenser pump 1
0
RW
Condenser pump 2
0
RW
Evaporator pump 1
DATE
PAGE
26 OF 56