12
PointBus Status Indicator
Refer to the table for a description of the PointBus Status indicator.
PointBus Status Indicator
State
Status
Off
Off or
Process in
Progress
Green
Operating
Normally
Flashing
Incorrect or
Red
Missing
I/O Module
Red
Critical
Failure
Publication
1738-IN015C-EN-E - February 2010
Description
• No power supplied.
• Hardware check in
progress.
• Initialization in
progress.
The adapter is operating
normally.
• Incorrect ArmorPoint
I/O module is
installed.
• ArmorPoint I/O
module was
removed from
backplane.
Critical link failure
(BUS_OFF).
Recommended Action
Turn the adapter on or wait until the
hardware check or initialization has
finished.
None.
Install the correct ArmorPoint I/O
module.
Check your physical network and
cycle power.