Parameter Descriptions - ABB LST100 Operating Instructions Manual

Ultrasonic level transmitter for upstream oil and gas
Table of Contents

Advertisement

5 Configuration

5.2 Parameter descriptions

Menu summary
Menu name
No. Configure name
Easy Setup
1
Operate Mode
2
Length Unit
3
Empty Distance
4
Span
5
Blanking
6
Max Rate of Change
Calibration
1
Enable User Calibration
2
Measured Value of P1
3
Actual Value of P1
4
Measured Value of P2
5
Actual Value of P2
6
Enable Simulation
7
Simulated Voltage
8
Offset of 1000mV
9
Offset of 5000mV
Monitor
1
Level
Console
2
Instant
3
Percentage
4
Voltage Output
5
Refresh Automatically
Advanced
1
Measure Interval
Setup
2
Temp. Compensation
3
Temp. Unit
4
Temp. Offset
5
Min Power Level
6
Max Power Level
7
Invert Voltage
8
Failsafe
9
Factory Reset
10
User Password
16 OI/LST100-EN | LST100 – Ultrasonic level transmitter
Setting range
1: Level
2: Distance
1: Feet
2: Meters
0.213 to 15.24 m (0.700 to 50.00 ft)
0.213 to 15.24 m (0.700 to 50.00 ft)
0.001 to 15.24 m (0.003 to 50.00 ft)
0.001 to 15.24 m/minute
(0.003 to 50.00 ft/minute)
1. No
Yes
0.001 to 15.24 m (0.003 to 50.00 ft)
0.001 to 15.24 m (0.003 to 50.00 ft)
0.001 to 15.24 m (0.003 to 50.00 ft)
0.001 to 15.24 m (0.003 to 50.00 ft)
1. No
Yes
1 to 5800 mV
500 to 1500 mV
4000 to 6000 mV
Read Only
Read Only
Read Only
Read Only
1. No
Yes
2 to 3600 s
1. No
Yes
1. Fahrenheit
Celsius
-200 to 200
1. Level_1
2. Level_2
3. Level_3
4. Level_4
5. Level_5
1. Level_1
2. Level_2
3. Level_3
4. Level_4
5. Level_5
1. No
Yes
1. LOW ALARM
2. HIGH ALARM
3. HOLD MODE
1. No
Yes
Read Only
Description
Measurement mode
Measurement length units
Distance from sensor to bottom of tank
Measurement span
Distance from sensor where no measurement is possible
Maximum rate the level can change in the process
Enable user calibration function
LST100 measured value of calibration point 1 (short range)
Actual distance to target for calibration point 1 (short range)
LST100 measured value of calibration point 2 (short range)
Actual distance to target for calibration point 2 (short range)
Enable Simulation
Simulated Voltage used for output calibration
Offset for 1000 mV
Offset for 5000 mV
Output level value
Instant distance from target surface to bottom of tank
Percentage of Span
The voltage to output
Refresh automatically
Interval between measurements
Compensate for the speed of sound
Temperature unit
Offset for temperature sensor
Minimum power used
Maximum power used
Invert voltage
Failsafe
Factory reset