Split System Interconnecting Line Sizing Chart - Wine Guardian PRO Series Installation, Operation And Maintenance Manual

Split systems, professional grade split cooling systems
Hide thumbs Also See for PRO Series:
Table of Contents

Advertisement

horizontal parallel to the compressor, crankshaft or in a vertical position 90 degrees to
compressor crankshaft.
NOTE: The suction line should be clamped near the inlet end of the vibration
eliminator. The vibration eliminator is located between the clamp and the
.
compressor

Split System Interconnecting Line Sizing Chart

Table 3
Model
SP25
SP50
SP88
SP200
*Interconnecting tube must be reduced down at evaporator connection
Notes:
Line lengths are expressed in equivalent feet = actual run length + fitting allowances (i.e.
~5' for each bend/elbow allowance).
Use only refrigeration grade dehydrated tubing.
Install refrigeration piping per local codes and ASHRAE guidelines.
Liquid
Liquid
Suction
Line(OD)
connection
line
at
(OD)
evaporator
(OD)
1/4"
1/4"
3/8"
1/4"
1/4"
1/2"
3/8"
*1/4"
1/2"
3/8"
3/8"
7/8"
Min.
Suction
Suction
connection
line
at
insulation
evaporator
thickness
(OD)
(in)
3/8"
3/8"
*3/8"
3/8"
5/8"
1/2"
*1/2"
5/8"
Maximum
Maximum
"total"
lift
line length
(height)
50'
15'
50'
15'
50'
15'
50'
15'
38