Appendix A: Default Gateway Settings - Advantech Vlinx MESR9 Series User Manual

Modbus gateways
Hide thumbs Also See for Vlinx MESR9 Series:
Table of Contents

Advertisement

APPENDIX A: DEFAULT GATEWAY SETTINGS

Gateway Name User assigned
MAC Address Fixed - see bottom label
Firmware Version (Vx.x.x)
Hardware Version (Vx.x.x)
Serial Port Mode RS-232
Flow Control None
Serial Timeout 0 seconds
Inter-character Timer 0 ms
Maximum Connection 1
Setting Default Value
Password Password field is blank from factory
DHCP Enabled
DHCP will configure. If a DHCP server is not available,
IP Address
the unit will default to 169.254.102.39
Net Mask 255.255.0.0
Gateway 169.254.102.100
Port 1, 2
Baud Rate 9600
Data Bits 8
Parity None
Stop Bits 1
Protocol TCP
Port 1 = 4000
TCP Port
Port 2 = 4001
68
MESR9xx Modbus
Gateways:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mesr90Mesr921Mesr922tMesr902tMesr922t-scMesr921-mt

Table of Contents