Panasonic SF4C Series Instruction Manual page 68

Ultraslim light curtain/type4
Hide thumbs Also See for SF4C Series:
Table of Contents

Advertisement

Functions
● Large multi-purpose indicator setting changing function
One mode can be selected from the following eigiht modes with the handy controller SFC-HC (optional).
Factory setting is mode 0.
Mode
Large multi-purpose indicatoe input 1 / 2
PNP output: High NPN output: Low PNP output: Low NPN output: High
0
Lights up in red
1
Blinks in red
2
Lights up in red
3
Blinks in red
4
Lights up in red
(Note 1)
5
Blinks in green
(Note 1)
6
(Note 1)
7
Lights up in red
(Note 1)
Notes: 1) Blinking takes precedence in case of same color brinks or light up in the large multi-purpose indicator.
2) The large multi-purpose indicator (red) and the large multi-purpose indicator (green) can be lit up and blinked in same
time.
Furthermore, large multi-purpose indicator (red) can be blinked in lockout status.
Lockout blinking display function
Valid
Invalid
● Interlock setting changing function
It is selectable one interlock state among the following three interlock settings with handy controller
SFC-HC (optional).
• Start / Restart interlock
The device goes into the interlock state after the power is turned ON, or when the light is blocked.
The factory setting is start / restart interlock.
• Start interlock
The device goes into the interlock state when the power supply is turned ON. Once this interlock is re-
set, the device does not go into the interlock state.
• Restart interlock
The device does not go into the interlock state when turning ON the power supply. Only when the con-
trol output (OSSD 1 / 2) becomes ON and the light is blocked after the power is turned ON and this de-
vice receives the light, the device goes into the interlock state.
● External device monitor setting changing function
The setting of the external device monitor is changeable with the handy controller SFC-HC (optional).
1. Allowable time for response time: 100 to 600ms (Unit: 10ms)
Factory setting is 300ms.
2. The external device monitor function can be selected to valid or invalid.
The factory setting is set to valid for the external device monitor function.
● Protective function
The functional setting is not allowed to change without input of password.
The factory setting is set to be invalid for the protective function.
68
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Operation of Large multi-purpose indicator
Lights up in green
Blinks in green
Blinks up- in green
Lights up in green
Blinks in red
Lights up in green
-
Blinks in red
Lockout ON
Blinks in red
-
Control output 1 / 2 (OSSD 1 / 2) Muting function Override function
ON
-
-
-
-
-
-
Lights up in
-
green
-
© Panasonic Industrial Devices SUNX Co., Ltd. 2016
OFF
Valid
-
-
-
-
-
-
-
-
-
-
-
-
Lights up in
Blinks in
red
green
Lights up in
-
green
Valid
-
-
-
-
-
-
-
Blinks in
green