9.2 - Alarms description

9.2.1 - Alarms
Name
1
COOL_EWT_F
2
COOL_LWT_F
3
DEFROST_T_A_F
4
DEFROST_T_B_F
5
OAT_F
6
CHWSTEMP_F
7
SUCTION_T_A_F
8
SUCTION_T_B_F
9
SGTC1_F
10
SGTC2_F
11
DP_A_F
12
DP_B_F
13
SP_A_F
14
SP_B_F
15
SIOB_CIR_A_
COM_F
16
SIOB_CIR_B_
COM_F
17
AUX1_COM_F
18
COOLER_
FREEZE_F
19
LOW_SUCTION_A_F 10005
20
LOW_SUCTION_B_F 10006
21
HIGH_SH_A_F
22
HIGH_SH_B_F
23
LOW_SH_A_F
24
LOW_SH_B_F
25
COOLER_LOCK_F
26
CPA1_REVERSE_
ROT_F
27
CPA2_REVERSE_
ROT_F
28
CPA3_REVERSE_
ROT_F
29
CPB1_REVERSE_
ROT_F
30
CPB2_REVERSE_
ROT_F
31
LOSS_COM_SM_F
32
LOSS_COM_MS_F
Code
Description
15001
Water Exchanger Entering Fluid
Thermistor Failure
15002
Water Exchanger Leaving Fluid Thermistor
Failure
15003
Circuit A Defrost Thermistor Failure
15004
Circuit B Defrost Thermistor Failure
15010
OAT Thermistor Failure
15011
MASTER/Slave Common Fluid Thermistor
Failure
15012
Circuit A Suction Gas Thermistor Failure
15013
Circuit B Suction Gas Thermistor Failure
15044
Coil Suction Gas Thermistor Sensor 1
Failure
15045
Coil Suction Gas Thermistor Sensor 2
Failure
12001
Circuit A Discharge Pressure Transducer
Failure
12002
Circuit B Discharge Pressure Transducer
Failure
12004
Circuit A Suction Pressure Transducer
Failure
12005
Circuit B Suction Pressure Transducer
Failure
4901
Loss of communication with SIOB Board
Number A
4902
Loss of communication with SIOB Board
Number B
4601
Loss of communication with AUX1 Board
10001
Water Exchanger Freeze Protection
Circuit A Low Saturated Suction
Temperature
Circuit B Low Saturated Suction
Temperature
10008
Circuit A High Superheat
10009
Circuit B High Superheat
10011
Circuit A Low Superheat
10012
Circuit B Low Superheat
10014
Interlock Failure
10016
Compressor A1 Not Started Or Pressure
Increase not Established
10017
Compressor A2 Not Started Or Pressure
Increase not Established
10018
Compressor A3 Not Started Or Pressure
Increase not Established
10020
Compressor B1 Not Started Or Pressure
Increase not Established
10021
Compressor B2 Not Started Or Pressure
Increase not Established
10029
Loss of communication with System
Manager
10030
Master/Slave communication Failure
Reset
Action taken
Automatic, if thermistor
Unit shuts down
reading returns to normal
As above
As above
As above
Cooling mode: Unit
continues to operate
Heating mode: Circuit A
shuts down
As above
Cooling mode: Unit
continues to operate
Heating mode: Circuit B
shuts down
As above
Unit shuts down
As above
Master/Slave operation is
disabled, each unit
returns to the stand-
alone mode
As above
Circuit A shuts down
As above
Circuit B shuts down
As above
Circuit A shuts down (in
heating mode);
None (in cooling mode)
As above
Circuit B shuts down (in
heating mode);
None (in cooling mode)
Automatic, if sensor voltage
Circuit A shuts down
reading returns to normal
As above
Circuit B shuts down
As above
Circuit A shuts down
As above
Circuit B shuts down
Automatic, if
Circuit A shuts down
communication is
re-established
As above
Circuit B shuts down
As above
Unit shuts down
Automatic (the first alarm in
Unit shuts down, the
the last 24 h) or Manual
water exchanger pump is
running
Automatic (the first alarm in
Circuit A shuts down
the last 24 h) or Manual
As above
Circuit B shuts down
Manual
Circuit A shuts down
Manual
Circuit B shuts down
Manual
Circuit A shuts down
Manual
Circuit B shuts down
Automatic (if the unit was
Unit shuts down
stopped) or Manual
Manual
Compressor A1 shuts
down
Manual
Compressor A2 shuts
down
Manual
Compressor A3 shuts
down
Manual
Compressor B1 shuts
down
Manual
Compressor B2 shuts
down
Automatic, if
Unit returns to the
communication is
stand-alone mode
re-established
Automatic, if
Master/Slave operation is
communication is
disabled, the unit returns
re-established
to the stand-alone mode
Possible cause
Defective thermistor
As above
As above
As above
As above
As above
As above
As above
As above
As above
Defective transducer
As above
As above
As above
As above
Bus installation fault,
communication error
As above
No water flow,
defective thermistor
Pressure transducer
defective, EXV blocked or
lack of refrigerant
As above
Pressure transducer
defective, temperature
sensor defective, EXV
blocked or lack of
refrigerant
As above
As above
As above
Customer interlock input
set on
Compressor breaker or
fuse fault, compressor
switch open
As above
As above
As above
As above
CCN bus installation
defective
CCN bus installation
defective
33