General Config Menu – GENCONF
Point name
Status
1
lead_cir
0 to 2
2
seq_typ
no/yes
3
ramp_sel
no/yes
off_on_d
4
1 to 15
5
nh_limit
0 to 100
6
nh_start
00:00
7
nh_end
00:00
8
bas_menu
0 to 3
*Depends on the selected language (English by default).
Pump Configuration Menu – PUMPCONF
Point name
Status
1
pump_seq
0 to 4
2
pump_del
24 to 3000
3
pump_per
no/yes
4
pump_sby
no/yes
5
pump_loc
no/yes
*Depends on the selected language (English by default).
Heat/Cool Config Menu – HCCONFIG
Point name
Status
1
auto_sel
no/yes
2
cr_sel
0 to 3
3
hr_sel
0 to 3
4
heat_th
-20.0 to 0.0
-4.0 to 32.0
5
boil_th
-15.0 to 15.0
5.0 to 59.0
6
ehs_th
-5.0 to 21.1
23.0 to 70.0
7
both_sel
no/yes
8
ehs_back
no/yes
9
ehs_pull
0 to 60
10
ehs_defr
no/yes
*Depends on the selected language (English by default).
Reset Config Menu – RESETCFG
Point name Status
1
2
oatcr_no
-10.0 to 51.7
14.0 to 125.0
3
oatcr_fu
-10.0 to 51.7
14.0 to 125.0
4
dt_cr_no
0 to 13.9
0 to 25.0
5
dt_cr_fu
0 to 13.9
0 to 25.0
Default
Unit
Displayed text*
0
-
Cir Priority Sequence
0=Auto 1=A Lead 2=B Lead
no
-
Staged Loading Sequence
no
-
Ramp Loading Select
Unit Off to On Delay
1
min
100
%
Night Capacity Limit
00:00
-
Night Mode Start Hour
00:00
-
Night Mode End Hour
Basic Menu Config
0
-
0 = All Access
1 = no alarm menu
2 = no setpoint menu
3 = 1 + 2
Default
Unit
Displayed text*
0
-
Water Pumps Sequence
0 = No Pump
1 = One Pump Only
2 = Two Pumps Auto
3 = Pump#1 Manual
4 = Pump#2 Manual
48
hour
Pump Auto Rotation Delay
no
-
Pump Sticking Protection
no
-
Stop Pump During Standby
Flow Checked if Pump Off
yes
-
Default
Unit
Displayed text*
no
-
Auto Changeover Select
0
-
Cooling Reset Select
0
-
Heating Reset Select
1=OAT,
2=Delta T
3= Analog (4-20mA)
-15.0
°C
Heating OAT Threshold
5.0
°F
-9.9
°C
Boiler OAT Threshold
14.2
°F
5.0
°C
Elec Stage OAT Threshold
41.0
°F
no
-
HSM Both Command Select
no
-
1 Elec Stage For Backup
0
min
Electrical Pulldown Time
no
-
Quick EHS For Defrost
Default
Unit
Displayed text*
COOLING RESET
-10.0
°C
OAT No Reset Value
14.0
°F
-10.0
°C
OAT Full Reset Value
14.0
°F
0
^C
Delta T No Reset Value
0
^F
0
^C
Delta T Full Reset Value
0
^F
Description
Circuit priority sequence
0 = Automatic changeover
1 = Circuit A lead
2 = Circuit B lead
Staged loading sequence
Ramp loading sequence
Unit OFF to ON delay
Night capacity limitation
Night mode start hour
Night mode end hour
Basic menu configuration
0 = All access
1 = Alarm menu
2 = Setpoint menu unavailable
3 = Alarm and Setpoint menus are unavailable
Description
Water pumps sequence
0 = No pump
1 = One pump only (units with one pump)
2 = Two pumps automatic control
3 = Pump 1 selected (units with two pumps)
4 = Pump 2 selected (units with two pumps)
Pump automatic rotation delay
Pump sticking protection
Pump stopped when the unit is in standby
Water flow is checked when the pump is off
Description
Heating/Cooling automatic changeover
Cooling reset
Heating reset
0=None
0 = No reset
1 = Reset based on OAT
2 = Reset based on delta T
3 = Reset based on analog input (4-20 mA)
Heating OAT threshold
Boiler OAT threshold
Electric heating stage OAT threshold
HSM command
Electric heating stage for back-up
Electrical pull-down time: It defines the time
between starting the unit and determining whether
the electric heating stage should be started
Quick electric heating used for defrost
Description
Cooling reset parameters
OAT no reset value
OAT full reset value
Delta T no reset value
Delta T full reset value
21