Temperature Menu – TEMP
Status
Point name
1
EWT
-
2
LWT
-
3
OAT
-
4
CHWSTEMP
-
5
SCT_A
-
6
SST_A
-
7
SCT_B
-
8
SST_B
-
9
DEFRT_A
-
10
DEFRT_2
-
11
sgtc1
-
12
sgtc2
-
*Depends on the selected language (English by default).
Pressure Menu – PRESSURE
Point name
Status
1
DP_A
-
2
SP_A
-
3
DP_B
-
4
SP_B
-
*Depends on the selected language (English by default).
Inputs Menu – INPUTS
Point name
Status
1
ONOFF_SW
open/close
2
HC_SW
open/close
3
on_ctrl
xxx
4
SETP_SW
open/close
5
LIM_SW1
open/close
6
LIM_SW2
open/close
7
LIM_ANAL
-
8
FLOW_SW
open/close
9
leak_v
-
10
leak_2_v
-
11
DSHT_SW
open/close
12
PWRIN_ST
open/close
13
HP_SWA
open/close
14
HP_SWA3B
open/close
15
bacdongl
no/yes
*Depends on the selected language (English by default).
Unit
Displayed text*
°C / °F
Entering Water Temp
°C / °F
Leaving Water Temp
°C / °F
External Temperature
°C / °F
Common Master/Slave Temp
°C / °F
Saturated Cond Tmp A
°C / °F
Saturated Suction Tmp A
°C / °F
Saturated Cond Tmp B
°C / °F
Saturated Suction Tmp B
°C / °F
Defrost Temp Cir A
°C / °F
Defrost Temp Second Coil
°C / °F
Suction Gas Temp Coil 1
°C / °F
Suction Gas Temp Coil 2
Unit
Displayed text*
kPa / PSI
Discharge Pressure A
kPa / PSI
Suction Pressure A
kPa / PSI
Discharge Pressure B
kPa / PSI
Suction Pressure B
Unit
Displayed text*
Remote On/Off Switch
-
-
Remote Heat/Cool Switch
-
Current Control
-
Remote Setpoint Switch
-
Limit Switch 1
-
Limit Switch 2
mA
Limit Analog Input
-
Flow Switch
V
Leakage detector #1 val
V
Leakage detector #2 val
-
Desuperheater Switch
-
Power Input Stable
-
HP Switch Circuit A
-
HP Switch Circuit A3/B
-
BACnet Dongle
Description
Entering water temperature: Used for capacity control
Leaving water temperature: Used for capacity control
Outdoor air temperature: Used to determine a number of control
mechanisms such as heat/cool changeover, water exchanger
heater operation, defrost cycle
Common master/slave temperature
Saturated condensing temperature, circuit A
Saturated suction temperature, circuit A
Saturated condensing temperature, circuit B
Saturated suction temperature, circuit B
Defrost temperature, circuit A (heat pumps only)
Defrost temperature on the second coil on circuit A (heat pumps
only)
Suction gas temperature coil 1
Suction gas temperature coil 2
Description
Compressor discharge pressure, circuit A
Compressor suction pressure, circuit A
Compressor discharge pressure, circuit B
Compressor suction pressure, circuit B
Description
Remote On/Off switch
Remote Heat/Cool switch
Current control status: Off, On Cool, On Heat, On Auto
Remote setpoint switch
Demand limit switch 1
Demand limit switch 2
Limit Analog Input 4-20mA
Water exchanger flow switch
Leakage detector 1
Leakage detector 2
Desuperheater switch
Power input stable
High pressure switch, circuit A
High pressure switch, circuit B
BACnet dongle status (BACnet option)