7 - SETTING UP TOUCH PILOT JUNIOR - PARAMETERS

7.1 - Main menu

Icon
Displayed text*
General Parameters
Temperature
Pressure
Inputs
Outputs
Pump Status
Runtime
DC Free Cooling
Status
Modes
Setpoint
Configuration
*Depends on the selected language (English by default).
Since specific units may not include additional features,
some tables may contain parameters that cannot be
configured for a given unit.
General Parameters Menu – GENUNIT
Point name
1
CTRL_TYP
2
STATUS
3
ALM
4
min_left
5
HEATCOOL
6
HC_SEL
7
SP_SEL
8
SP_OCC
9
CHIL_S_S
10
CHIL_OCC
11
CAP_T
12
CAPA_T
13
CAPB_T
14
DEM_LIM
15
SP
16
CTRL_PNT
17
EMSTOP
*Depends on the selected language (English by default).
16
Description
Name
General parameters
GENUNIT
Temperatures
TEMP
Pressures
PRESSURE
Inputs status
INPUTS
Outputs status
OUTPUTS
Pump status
PUMPSTAT
Run times
RUNTIME
Dry Cooler - Free
FCOOL_ST
Cooling
Modes status
MODES
Setpoints
SETPOINT
Configuration menu
CONFIG
CAUTION
Status
Unit
0 to 2
-
xxx
-
xxx
-
0 to 0
min
0 to 2
-
0 to 2
-
no/yes
-
dsable/enable
-
no/yes
-
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
-
°C / °F
-20.0 to 67.0
°C
-4.0 to 153.0
°F
dsable/enable
-
Displayed text*
Local=0 Net.=1 Remote=2
Running Status
Alarm State
Minutes Left for Start
Heat/Cool status
Heat/Cool Select
0=Cool 1=Heat 2=Auto
Setpoint Select
0=Auto. 1=Spt1. 2=Spt2
Setpoint Occupied?
Net.: Cmd Start/Stop
Net.: Cmd Occupied
Percent Total Capacity
Circuit A Total Capacity
Circuit B Total Capacity
Active Demand Limit Val
Current Setpoint
Control Point
Emergency Stop
Description
Operating mode: 0 = Local, 1 = Network,
2 = Remote
Unit running status: 0 = Off, 1 = Running, 2 = Stopping,
3 = Delay, 4 = Trip out, 5 = Ready, 6 = Override, 7 =
Defrost, 8 = Run Test, 9 = Test
Alarm status
Minutes left before the unit start-up
Heating/Cooling status
Heating/Cooling selection
0 = Cool, 1 = Heat, 2 = Auto
Setpoint select
0 = Auto, 1 = Setpoint 1, 2 = Setpoint 2
Setpoint occupied?
Unit start/stop via Network: When the unit is in Network
mode, start/stop command can be forced
Unit time schedule via Network: When the unit is in
Network mode, the forced value can be used instead
of the real occupancy state
Total unit capacity
Total capacity, circuit A
Total capacity, circuit B
Active demand limit value: When the unit is Network
mode, the minimum value will be used compared to
the status of the external limit switch contact and the
demand limit switch setpoint
Current setpoint
Control point: Water temperature that the unit must
produce
Emergency stop