Configuration Menu (Config) - Carrier Touch Pilot Junior Manual

For carrier 30rbs; carrier 30rqs
Table of Contents

Advertisement

Setpoint Menu – SETPOINT
Point name
Status
1
csp1
-28.9 to 20.0
-20.0 to 68.0
2
csp2
-28.9 to 20.0
-20.0 to 68.0
3
hsp1
25.0 to 55.0
77.0 to 131.0
4
hsp2
25.0 to 55.0
77.0 to 131.0
5
ramp_sp
0.1 to 1.1
0.2 to 2.0
6
cauto_sp
3.9 to 50.0
39.0 to 122.0
7
hauto_sp
0 to 46.1
32.0 to 115.0
8
lim_sp1
0 to 100
9
lim_sp2
0 to 100
10
lim_sp3
0 to 100
11
min_sct
26.7 to 60.0
80.0 to 140.0
*Depends on the selected language (English by default).

7.2 - Configuration menu (CONFIG)

Icon
Displayed text*
General Config
Pump Configuration
Heat/Cool Config
Reset Config
User Configuration
Schedule
Holiday
Broadcast
Date/Time
Control Identification
*Depends on the selected language (English by default).
Since specific units may not include additional features,
some tables may contain parameters that cannot be
configured for a given unit.
20
Default
Unit
7.0
°C
44.6
°F
7.0
°C
44.6
°F
38.0
°C
100.4
°F
38.0
°C
100.4
°F
0.6
^C
1.0
^F
23.9
°C
75.0
°F
17.8
°C
64.0
°F
100
%
100
%
100
%
40.0
°C
104.0
°F
Description
Name
General configuration
GENCONF
Pump configuration
PUMPCONF
Heat/Cool configuration
HCCONFIG
Reset configuration
RESETCFG
User configuration
USERCONF
Schedule menu
SCHEDULE
Holiday menu
HOLIDAY
Broadcast menu
BROADCAST
Date/time configuration
DATETIME
Control identification
CTRL_ID
CAUTION
Displayed text*
Cooling Setpoint 1
Cooling Setpoint 2
Heating Setpoint 1
Heating Setpoint 2
Ramp Loading
Cool Changeover Setpt
Heat Changeover Setpt
Switch Limit Setpoint 1
Switch Limit Setpoint 2
Switch Limit Setpoint 3
Desuperheater Min Sct
Description
Cooling setpoint 1
Cooling setpoint 2
Heating setpoint 1
Heating setpoint 2
Ramp loading
Cool changeover setpoint
Heat changeover setpoint
Switch limit setpoint 1
Switch limit setpoint 2
Switch limit setpoint 3
Desuperheater minimum saturated condensing
temperature

Hide quick links: