Outputs Menu – OUTPUTS
Point name
Status
off/on
1
CP_A1
off/on
2
CP_A2
off/on
3
CP_A3
off/on
4
FAN_A1LS
off/on
5
FAN_A1HS
off/on
6
FAN_A2LS
off/on
7
FAN_A2HS
8
HD_POS_A
-
9
EXVPosA
-
10
EXVNPosA
-
off/on
11
RV_A
off/on
12
CP_B1
off/on
13
CP_B2
off/on
14
FAN_B1LS
off/on
15
FAN_B1HS
16
HD_POS_B
-
17
EXVPosB
-
18
EXVNPosB
-
off/on
19
RV_B
off/on
20
C_HEATER
off/on
21
BOILER
22
EHS_STEP
-
off/on
23
ALARM_R
off/on
24
RUN_R
off/on
25
OIL_VALV
*Depends on the selected language (English by default).
Pump Status Menu – PUMPSTAT
Point name
Status
off/on
1
CPUMP_1
off/on
2
CPUMP_2
3
ROT_PUMP
no/yes
4
W_P_IN
-
5
W_P_OUT
-
6
WP_CALIB
no/yes
7
WP_OFFST
-
8
DP_FILTR
-
9
WP_MIN
-
10
WAT_FLOW
-
11
CAPPOWER
-
12
p_dt_spt
-
13
p_dp_spt
-
14
drvp_pct
-
15
drvp_pwr
-
16
drvp_i
-
17
drvp_ver
xxx
*Depends on the selected language (English by default).
18
Unit
Displayed text*
-
Compressor A1 Output
-
Compressor A2 Output
-
Compressor A3 Output
-
Fan A1LS Output
-
Fan A1HS Output
-
Fan A2LS Output
-
Fan A2HS Output
%
Head Pressure Position A
%
EXV Position Circuit A
%
EXV Next Pos Circuit A
-
4 Way Refrigerant ValveA
-
Compressor B1 Output
-
Compressor B2 Output
-
Fan B1LS Output
-
Fan B1HS Output
%
Head Pressure Position B
%
EXV Position Circuit B
%
EXV Next Pos Circuit B
-
4 Way Refrigerant ValveB
-
Cooler & Drain Pan Heatr
-
Boiler Command
-
Electrical Heat Stage
-
Alarm Relay Status
-
Running Status
-
Oil Valve Status
Unit
Displayed text*
-
Water Pump #1 Command
-
Water Pump #2 Command
-
Rotate Pumps Now?
kPa / PSI
Inlet Water Pressure
kPa / PSI
Outlet Water Pressure
-
Water Pressure Calibrat
Water Pressure Offset
kPa / PSI
kPa / PSI
Delta Water Press. Filt
kPa / PSI
Mini Water Pressure
l/s / GPS
Water Flow
kW
Actual Power Capacity
^C / ^F
Water DT Setpoint
kPa / PSI
Water DP Setpoint
%
Pump Drive Percent
kW
Pump Drive Power
A
Pump Drive Amps
-
Pump Drive Version
Description
Compressor A1 status
Compressor A2 status
Compressor A3 status
Fan A1 low speed status
Fan A1 high speed status
Fan A2 low speed status
Fan A2 high speed status
Head pressure, circuit A
EXV position, circuit A
EXV next position, circuit A
4-way refrigerant valve, circuit A: Used to manage cooling / heating
/ defrost operation (heat pumps)
Compressor B1 status
Compressor B2 status
Fan B1 low speed status
Fan B1 high speed status
Head pressure, circuit B
EXV position, circuit B
EXV next position, circuit B
4-way refrigerant valve, circuit B: Used to manage cooling/heating/
defrost operation (heat pumps)
Water exchanger / Drain pan heater
Boiler status
Electric heating stages
Alarm relay status
Unit ON relay
Oil valve status
Description
Water pump 1 command
Water pump 2 command
Water exchanger pumps rotation
Inlet water pressure
Outlet water pressure
Water pressure calibration
Water pressure offset
Delta water pressure filtration
Minimum water pressure
Water flow status
Actual power capacity
Water discharge temperature setpoint
Water discharge pressure setpoint
Pump drive percent
Pump drive power
Pump drive (A)
Pump drive version