Carrier Touch Pilot Junior Manual page 34

For carrier 30rbs; carrier 30rqs
Table of Contents

Advertisement

Name
33
M_S_CONFIG_F
34
INI_FACT_CONF_F
35
ILL_FACT_CONF_F
36
CCN_EMSTOP_F
37
COOL_PUMP1_F
38
COOL_PUMP2_F
39
REPEATED_HIGH_
DGT_A_F
40
REPEATED_HIGH_
DGT_B_F
41
REPEATED_LOW_
SST_A_F
42
REPEATED_LOW_
SST_B_F
43
HEAT_LOW_EWT_F 10043
44
SENSORS_SWAP_F 10097
45
SERVICE_
MAINTNANCE_
ALERT
46
DRV_FAN_A_F
47
DRV_FAN_B_F
48
DRV_WTR_PUMP_F 19001
49
SIOB_LOW_VOLT_
CIRA_F
50
SIOB_LOW_VOLT_
CIRB_F
51
WP_IN_F
52
WP_OUT_F
53
WL_PRESS_ZERO_
ERROR_F
54
WL_PRESS_TOO_
LOW_F
55
WL_PUMP_NOT_
STARTED_F
57
WL_PUMP_
OVERLOAD_F
58
WL_LOW_FLOW_F
59
WL_PRESS_
CROSS_F
60
WL_LOW_PRESS_
WARNING_F
61
HP_SWITCH_A_F
62
HP_SWITCH_B_F
63
FLUIDE_FAIL
64
FC_PROCESS_F
65
FC_WLOOP_F
66
FC_LWT_F
67
FC_OAT_F
68
FC_AUX1_COM_F
34
Code
Description
Master chiller configuration error
9001
Initial factory configuration required
8000
Illegal configuration
7001
10031
Unit is in CCN emergency stop
10032
Water Pump 1 fault
10033
Water Pump 2 fault
10037
Circuit A Repeated High Discharge Gas
Overrides
10038
Circuit B Repeated High Discharge Gas
Overrides
10040
Circuit A Repeated Low Suction Temp
Overrides
10041
Circuit B Repeated Low Suction Temp
Overrides
Low Entering Water Temperature In
Heating
Water Exchanger Temperature Sensors
Swapped
130-nn
Service maintenance alert
16001
Circuit A Variable Speed Fan Failure
17001
Circuit B Variable Speed Fan Failure
Water pump Variable Speed Fan Failure
57001
Circuit A SIOB Low Voltage Failure
57002
Circuit B SIOB Low Voltage Failure
12024
Water Exchanger Entering Fluid
Transducer Failure
12025
Water Exchanger Leaving Fluid
Transducer Failure
11202
Water Loop : Delta Pressure Error
11203
Water Loop : Pressure Too Low
11204
Water Loop : Pump Not Started
11206
Water Loop : Pump Overload
11207
Water Loop : Flow Too Low
11208
Water Loop : Pressure Sensors Crossed
11209
Water Loop : Low Pressure
Warning
10063
Circuit A High pressure switch Failure
10064
Circuit B High pressure switch Failure
10099
Possible Refrigerant Leakage Failure
10101
Free Cooling Process Failure
15046
Free Cooling Water Loop Thermistor
Failure
15047
Free Cooling Leaving Water Thermistor
Failure
15048
Free Cooling OAT Water Thermistor
Failure
4602
Loss of communication with Free Cooling
Board 1
Reset
Action taken
Automatic, if master/slave
Master/slave mode is
configuration returns to
stopped
normal
Automatic, if configuration
Unit shuts down
is entered
Manual
Unit shuts down
Automatic, if emergency
Unit shuts down
stop is deactivated
Manual
Unit is restarted with
another pump running; If
no pump is available, the
unit shuts down
Manual
As above
Automatic (no discharge
None
gas overrides within 30
min) or Manual
As above
None
Manual
Circuit A shuts down
Manual
Circuit B shuts down
Automatic
None
Manual
Unit shuts down
Manual
None: Contact Carrier
service
Automatic
Circuit A shuts down
Automatic
Circuit B shuts down
Automatic
Unit is restarted with
another pump running; If
no pump is available, the
unit shuts down
Automatic, if the alarm
Unit shuts down
occurred up to 6 times in
the last 24 h (otherwise
manual)
As above
Unit shuts down
Automatic, if sensor voltage
Unit shuts down
reading returns to normal
As above
Unit shuts down
Automatic, if water
Unit shuts down
pressure delta returns to
normal
Automatic, if water pressure
Unit shuts down
reading returns to normal
and the alarm occurred up to
6 times in the last 24 h
(otherwise manual)
Automatic
Pump is stopped
Automatic
None
Automatic, if water flow
Pump is stopped
reading returns to normal
Manual
Unit shuts down
Automatic, if water
None
pressure reading returns to
normal
Manual
Circuit A shuts down
Manual
Circuit B shuts down
Automatic
None
Automatic
Free Cooling is stopped
Automatic, if thermistor
Free cooling is stopped
reading returns to normal
Automatic, if thermistor
Free cooling is stopped
reading returns to normal
Automatic, if thermistor
OAT sensor reading
reading returns to normal
(instead of FC OAT
sensor) is used
Automatic, if
Free Cooling is stopped
communication is
re-established
Possible cause
Master/slave configuration
error
The unit size has not
been configured
The unit size has been
configured with the wrong
value
Network emergency stop
command
Flow switch or water pump
fault
As above
Repetitive capacity
decreases
As above
As above
As above
Low entering fluid
temperature in Heating
mode
Input and output
temperature reversed
Servicing required
Speed controller fault
As above
As above
Unstable electrical supply
or electrical issue
As above
Defective transducer
Defective transducer
Too low or high water
pressure reading
Pump inlet pressure is
below 60 kPa
Too low or high pump
pressure reading
Water pressure drop too
low
Water loop pressure drop
too high
Pressure sensors crossed
Water pressure is below 60
kPa
High pressure switch is
open, compressor fault
As above
Refrigerant leak detected
Installation fault
Defective thermistor
Defective thermistor
Defective thermistor
Bus installation fault,
communication error

Hide quick links:

Advertisement

Table of Contents
loading