E-Mail With "Energy Indicator" For The Plant; E-Mail Receiver Configuration - Siemens OZW672.01 Commissioning Instructions

Web server
Hide thumbs Also See for OZW672.01:
Table of Contents

Advertisement

E-mail receiver
configuration
Notes
Test receiver
Siemens
Building Technologies
6.5

E-mail with "Energy indicator" for the plant

6.5.1

E-mail receiver configuration

Either no E-mail (no transmit time = Default) or one or two e-mails (Transmit time 1
and/or Transmit time 2) can be sent with the plant's "Energy indicator".
E-mail receivers 1 and 2 can be configured with "Administrator" and "Service"
access rights on the Web Server.
Path: OZW672... > Settings > Energy indicator
E-mail receivers 1 and 2 are configured individually (separate settings).
If Transmit time 1 and/or 2 are configured, the "Energy indicator" of the plant is sent
as an e-mail only if at least one monitored data point exceeds its "Green limit".
Configuration of e-mail receivers 1 and 2 for the "Energy indicator" of the plant is
not related to the e-mail receivers of fault messages (device failure etc.).
One e-mail each can be sent for test purposes to E-mail receiver 1 and 2.
· The test is triggered manually via data point "Test receiver = Trigger".
· Reception is confirmed in data point "Energy indicator transmitted = Yes".
· Data point "Reason" contains feedback on whether the e-mail was sent or
which setting must be checked in the event of an error.
Web Server OZW672... V6.0
"Energy indicator" function
91 / 143
CE1C5712en
2015-10-13