2.5.3

Operating page "Faults current"

Local faults and faults in system are displayed under "Faults current".
Path: Home > 0.5 OZW672... > Faults current
A description of faults is available in Section 4.3 "Faults
".
2.5.4

Operating page "Settings"

2.5.4.1
Web Server
Path: Home > 0.5 OZW672... > Settings > Web Server
Data point
Language
Default val:
English
Setting val:
See example
Code
Default val:
01
Setting val:
max. 20 char.
Reset admin password *
Default val:
No
Setting val:
Yes
* with PC software ACS790 only.
Web Server OZW672... V6.0
Commissioning
Explanation, example
Web Server language.
The language set is applied to Web Server
fault text messages, message history,
messages and system reports.
Access code for PC Software ACS790.
If you do not know the administrator password
for the Web Server, setting value "Yes" again
provides access to the Web Server via the
administrator password "Password"
("Password" = Factory setting for administrator
password).
"Password or Password.1" is possible again
(Administrator password for delivery of
devices to Version 5.2 = "Password", for
devices as of Version 6.0 = "Password.1").
Setting value "Yes" is a temporary state, i.e.
the setting value automatically goes to "No"
after ca. 2 seconds.
*
*
CE1C5712en
2015-10-13