"Plant" level
Note
"Partial plants" level
"Data points" level
Confirmation message
for "Monitoring off"
Green limits
to default values!
Note
Siemens
Building Technologies
Selecting the checkbox deactivates the data points for the selected device (can be
reactivated).
Selecting the summary checkbox (green/red, bottom row) deactivates the data
points for the plant (can be reactivated)).
A confirmation message is displayed when data point monitoring for a device
or plant is deactivated; see below.
Selecting the checkbox deactivates the data points for the selected partial plant
(can be reactivated)).
No confirmation message is displayed when data point monitoring for a partial
plant is deactivated.
Selecting the checkbox deactivates the selected data point (can be reactivated)).
No confirmation message is displayed when data point monitoring is deactivated.
A confirmation message is displayed when data point monitoring for a device or
plant is deactivated:
Clicking [ Yes ] for message "Really to be continued?" to deactivate monitoring also
resets "Green limits" (changed by the user) to their default values. Therefore:
"Monitoring off" deactivates monitoring while, at the same time, setting the "Green
limits" to the default values of device list creation.
Contrary to the "Green limits", deactivation does not reset changed data point
values to default values. Therefore:
Following "Monitoring off" and reactivation, "Energy indicator" data points may no
longer be within the green limits, as the "Green limits" reset to default values have
different dependencies.
Web Server OZW672... V6.0
"Energy indicator" function
85 / 143
CE1C5712en
2015-10-13