Manage Trend Memory; Send Trend Data By E-Mail - Siemens OZW672.01 Commissioning Instructions

Web server
Hide thumbs Also See for OZW672.01:
Table of Contents

Advertisement

Note
Sort data points
Delete data points from
the list
Siemens
Building Technologies
The data points within a Trend are all queried at the same interval.
The entire path for a data point is always displayed simply identifying the source of
the data point.
Data points can be moved within the list.
Simply left-click the sort symbol
data point is moved to the new position.
A single left-click of the waste can symbol
point list without additional confirmation.
8.2.5

Manage Trend memory

A fixed memory (flash) size is assigned to each Trend channel. Trend channel 1
has more memory and is particularly well suited for long-term Trending with a
number of data points, or a high query interval.
· Trend channel 1: 14 MB
· Trend channel 2...5: 2 MB
The read data is written first to RAM while Trending. It is transmitted to flash
memory every 60 minutes. A maximum of one hour of Trend data is lost in the
event of a power outage.
8.3

Send Trend data by e-mail

Trend data can be sent as an appendix by email.
Settings to send Trend data by e-mail are entered in the following area:
1. In primary navigation, click Home.
2. In secondary navigation, click 0.x.y OZW... .
3. Click Settings.
4. Click Trend.
In secondary navigation, the menus Trend channel 1...5 and E-mail receiver
are now available.
Web Server OZW672... V6.0
Trend functions
for the data point and keep it pressed until the
deletes the data point from the data
115 / 143
CE1C5712en
2015-10-13