s
LPB and BSB plants
Web server OZW672... V4.0
Commissioning instructions
CE1C5712en
28.08.2012
OZW672.01
OZW672.04
OZW672.16
Building Technologies

Advertisement

Table of Contents
loading

Summary of Contents for Siemens OZW672 Series

  • Page 1 LPB and BSB plants OZW672.01 Web server OZW672... V4.0 OZW672.04 Commissioning instructions OZW672.16 CE1C5712en Building Technologies 28.08.2012...
  • Page 2 Siemens Switzerland Ltd Infrastructure & Cities Sector Building Technologies Division Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 © 2010-2012 Siemens Switzerland Ltd www.siemens.com/sbt Subject to change 2 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies 28.08.2012...
  • Page 3: Table Of Contents

    3.2.2 Operate web server ................41 3.2.3 Web server diagnostics................44 Faults ......................47 3.3.1 Overview ....................47 3.3.2 Web server fault ..................47 File transfer .....................48 Operation with ACS790................51 3 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Table of contents 28.08.2012...
  • Page 4 Local area network (LAN) ...............85 6.1.2 Remote operation via the Internet............89 Messages via e-mail ................93 Appendix ....................99 General notes..................99 Diagnostics....................99 7.2.1 Web server fault codes ................99 7.2.2 Windows commander................100 4 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Table of contents 28.08.2012...
  • Page 5 Internet protocol ..................101 7.3.2 Free e-mail account providers ..............101 7.3.3 Install RNDIS driver................102 7.3.4 Alternative network configuration............103 7.3.5 Siemens routers ..................105 Glossary of Ethernet and Internet terms..........106 Index ......................113 5 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Table of contents 28.08.2012...
  • Page 6 6 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Table of contents 28.08.2012...
  • Page 7: Overview

    • Do not open the device. Failure to comply will invalidate any warranty claims. • The technical data are provided solely for use with Siemens bus devices. The user ensures the functionality of operation when using third-party devices not expressly mentioned here.
  • Page 8: Display And Operating Elements

    History data is not deleted. Switch • Position "On" Message inhibition Messages cannot be sent. • Position "Off" Message sending allowed. (DIP switches) No function. 8 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Overview 28.08.2012...
  • Page 9: Web Operation

    7 Plant name The display range displays content corresponding to the selected function via 8 Display primary and secondary navigation. 9 Logo area Shows Logo 1 and Logo 2. 9 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Overview 28.08.2012...
  • Page 10: User Levels

    • Operate service and end user data. Administrator • Fault overview • Documents, Message history, Logos and System definitions. • Administer all user accounts. • Create device websites. 10 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Overview 28.08.2012...
  • Page 11: Symbols, Notations, Abbreviations

    System definitions Logos. Switch over displays: Full view, partial view Fault indication: Green field = no fault; red field = fault (alarm) "Green leaf" "Orange leaf" "Grey leaf" 11 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Overview 28.08.2012...
  • Page 12: Notations

    OZW672.04 or OZW672.16 IP address, domains Entry in the web browser address line: • IP address: 192.168.2.10 • Domains: www.siemens.com Buttons Buttons are written as follows: [ Add ] 1.4.3 Abbreviations Abbreviations Auto MDI-X Auto Medium Dependent Interface - Crossed...
  • Page 13: Commissioning

    • To navigate, always start with primary navigation, then use the secondary navigation to select the desired menu item. • Return: Click "Upward" or navigate via the path or primary navigation. 13 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning...
  • Page 14: Getting Started

    RNDIS driver is installed. The installation wizard will guide you through installation. Note You can also manually set up the RNDIS driver (see Section 7.3.3). 14 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning...
  • Page 15: Log Into Web Server

    "Password") and the following note is displayed: • The following message is displayed if you fail to fill out all required fields: • Capitalization must be observed when entering the password. 15 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 16: Administer User Accounts

    Enter / select user data: - User name - Password - Repeat password - Description (optional) - E-mail address (optional) - Language: English - User group Close with [ OK ] 16 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 17 • A secure password is comprised of lowercase and uppercase letters, numbers and special characters, is at least 20 characters long, and does not include a name or words from dictionaries. 17 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 18: Create Device Web

    You can add just one BSB device to the device list. Click [ OK ] to confirm. The web server searches for a device with the entered bus address. It is displayed in the device list if found. 18 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning...
  • Page 19 The web server removes the device from the device list. Wait until Process finished is displayed. Click [ OK ] confirm. The device is removed from the device list. 19 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 20 Process takes a few minutes Wait until Process finished is displayed. Close with [ OK ] In the device list, the web server and the bus device display state "Generated". 20 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 21 The device web pages are updated. Process takes a few minutes Wait until Process finished is displayed. The device list for the web server display state "Generated". 21 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 22: Web Server Settings

    • Otherwise, both date and time must be newly set. Data point Explanation, example Time of day/date Set the current time and date. Weekday is calculated automatically. Default val: 00:00 1.1.2005 Setting val: Time of day/date 22 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 23: Operating Page Settings "Settings

    (daylight saving time), i.e. time is adjusted backward one hour. Note Disable the function by setting both start of daylight saving and standard time to the same date. 23 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 24 You Default val: 192.168.2.1 Setting val: IP address typically enter the IP address for the router here. Does not require setting if "DHCP client = On". 24 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 25 Internet connects a globally valid name to a Default val: 192.168.2.1 Setting val: IP address domain with an IP address (e.g. domain www.siemens.com with IP address 146.254.191.150). The setting corresponds to the IP address for the next router or DNS server that recognizes for its part a queried name (domain) or another DNS server.
  • Page 26 Web server registers its existence in the USB network, when • "UPnP localization" = "USB" is set and • The connection between PC/laptop and the web server is active via USB. 26 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 27 Not urgent exempts all message recipients subscribing to "Only urgent ones". Next report Waiting time to next system report. — Default val: 0 d (day) Setting val: 0...255 d (Resolution: 1 d) 27 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 28 The time the web server must wait until a fault becomes active Default val.: 00:05. Setting val: 00:00…59:55 is set here. (Resolution 00:05) 28 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 29 Default val: OZW672.01 OZW672.04 Update note on menu texts => Update or OZW672.16 regenerate web server device web page. Setting val: max. 20 characters 29 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 30: Operating Page Settings "Message Recipient

    • You can copy the switching times for a day of the week by clicking [ Copy ] one day to a selection of other days • Click [ Check ] to check the data before it is saved. 30 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 31 • Select checkbox to select active entries. • Select "Annually" to set annually recurring switching times. • Click [ Check ] to check the data before it is saved. 31 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 32: Commission Network Components

    PC with web browser on a local area network (LAN): • IP address • Subnet mask Note The addresses in the illustration are examples must be adapted to router addressing. See Section 6.1.1 for more details. 32 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 33: Router

    • DynDNS: The dynamic IP address for the connection must be published if no fixed public IP address is available. Settings depend on network type and application. The different variants are described in Section 6.1.2. 33 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning...
  • Page 34: Functional Check

    DNS server could not be Check Setting DNS ser- reached or no guaran- ver, Default gateway, or teed network connection. network connection. Table continued on next page 34 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 35 An invalid "E-mail ad- ferent errors. dress sender" can Encrypted mail server also result in this error. (i.e. with TLS = Transport Layer Security) may not be supported. 35 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 36: Additional Settings

    Delete history of all events and messages. — Note : Setting value Yes is a temporary state, i.e. Default val: Setting val: the value automatically returns to No after ca. 2 seconds. 36 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 37: Final Steps

    – The web server sends a system report to the defined message receivers. – Fault LED (4) displays (flashing) error in establishing communications. On LED must be green. Fault LED must be dark. 37 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning 28.08.2012...
  • Page 38: Supply State

    Procedures are communicated for any firmware update accordingly. Logo update The logos can be customized. See Section 3.4, part "Upload logos" for information on uploading. 38 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Commissioning...
  • Page 39: Operate Using A Web Browser

    Note You can automate the process by adding the login information to the web browser’s address line. Format: <IP address>/main.app?user=<User name>&pwd=<myPassword> Example: 10.169.9.121/main.app?user=Administrator&pwd=myPassword 39 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser 28.08.2012...
  • Page 40 The current, valid login information must be included for syntax "user=<user name>&pwd=<myPassword>". Note Deep links can be rendered invalid by generating an associated bus device. 40 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser...
  • Page 41: Operate The Plant

    Left-click in the menu to select web server operation. Web server displays the top web server level of the menu tree. From here, you can go to all operating pages and data points. 41 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser...
  • Page 42 Note In partial view, navigation to other plant web pages must be implemented using user-defined links. You can return to the full view at any time for navigation. 42 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser...
  • Page 43 • Click [ Copy ] to copy the switching times for any weekday to a number of other days • Click [ Check ] to check the data before it is saved. 43 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser 28.08.2012...
  • Page 44: Web Server Diagnostics

    Field bus module 1 type. Software version Field bus module 1 software version. Message inhibition Shows the setting of the message suppression switch (8). 44 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser 28.08.2012...
  • Page 45 Actual number of devices monitored by the web current server on the LPB/BSB bus. Last change Time of last change to device list. 45 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser 28.08.2012...
  • Page 46 An alternative DNS server is only defined for redundant systems and is typically empty. Physical address The physical address is a unique identification for the Ethernet interface. 46 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser 28.08.2012...
  • Page 47: Faults

    Device name, Fault information, Fault text, Device address, Device type. Note Faults for bus devices are listed in the documentation for the corresponding devices. 47 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser 28.08.2012...
  • Page 48: File Transfer

    • Message history export is available to administrator and service user levels. Notes • The message history remains intact when resetting the web server to default. 48 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser...
  • Page 49 Save logos: Click "Logo 1" or "Logo 2". The browser window opens with the logo. Right-click the log and save to the desired location via "Save Image As". 49 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser...
  • Page 50 Note Make sure there is at least 60 MB free memory on the web server when uploading. If not, check the contents via File transfer > Documents. 50 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser...
  • Page 51: Operation With Acs790

    ACS790 and import them to the web server. • Parameterization: Read and write parameter sets. • Commissioning protocol. • Offline trend. For more details, see data sheet N5649. 51 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser 28.08.2012...
  • Page 52 Empty page 52 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Operate using a web browser 28.08.2012...
  • Page 53: Visualize Plants

    Note The switch from an LPB to a BSB bus system and vice versa is not recommended since this renders the defined plant web pages unusable. 53 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Visualize plants...
  • Page 54: Example Of A Plant Web Page

    The extension consists of additional, explanatory text (3), a link to the Internet (4) and an integrated web cam image (5), that is updated periodically (e.g. every minute). 54 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Visualize plants...
  • Page 55: Plant Web

    (current available memory is available at "File transfer > Documents") • A maximum of 100 elements may be added on a plant webpage from one web page element type (e.g. a maximum of 100 data point elements). 55 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Visualize plants 28.08.2012...
  • Page 56: Toolbar

    (e.g. web cams). User levels Only an administrator may generate and change visualization. User levels have the same rights for operation and monitoring. 56 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Visualize plants...
  • Page 57: Import Web-Capable Plant Diagrams

    7. From the dropdown list box, select the bus address for the connected controller. 8. Click [ OK ] to start. The plant diagram is finished. 57 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Visualize plants 28.08.2012...
  • Page 58 • The data point text "Data point not found" is displayed. • Three question marks "???" are displayed as the data point value. See Section 4.6 for any post editing. 58 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Visualize plants 28.08.2012...
  • Page 59: Create Own Plant Web

    9. If satisfied, click OK to finish. 10. Click OK to change to view. The data point value was read and is displayed. 59 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Visualize plants...
  • Page 60 The following describes how to add two lines to the plant web page: • To another plant web page. • To an external web page. The link to a document is not displayed, but works accordingly. 60 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Visualize plants...
  • Page 61 12. If satisfied, click OK to finish. 13. Click OK to change to view. The link is enabled immediately in the view mode: Click to open the corresponding web page. 61 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Visualize plants...
  • Page 62 12. Edit Position and Scaling. 13. Click Apply to check the results of formatting in a preview. 14. If satisfied, click OK to finish. 15. Click OK to change to view. 62 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Visualize plants...
  • Page 63: "Energy Indicator" Function

    • The data point is not monitored via the "Energy indicator" function. No tree leaf The "Energy indicator" function is based on standard EN 15232 "Energy efficiency Standard EN 15232 in buildings". 63 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function 28.08.2012...
  • Page 64: Lpb/Bsb Bus Topology

    16 bus devices via the "Energy indicator" function. A maximum processing time of ca. 40 minutes results for the max. quantity of Note "Energy indicator" data points. 64 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function...
  • Page 65: Lpb/Bsb Devices

    "Energy indicator" function (see Section 2.4). The "Device web pages" (see screenshot) pane can be opened with "Service" and Note "Administrator" access rights. 65 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function...
  • Page 66: Energy Indicator" Function Levels

    Section 5.3.4. When a checkbox is cleared (deactivated), message "Monitoring off, green limits reset to default values! Really to be continued?" is displayed; see Section 5.3.4. 66 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function...
  • Page 67: Partial Plants" Level

    Indication of the number of actively monitored data points (x) for possible number Monitored data points of data points to be monitored (y) for each partial plant; see Section 5.2.4. 67 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator"...
  • Page 68: Data Points" Level

    ) shows all enumeration values. When level "Data points" is selected, they are sorted by "Device Description". Us- Note ers cannot change the sort order. 68 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function 28.08.2012...
  • Page 69: Number Of "Monitored Data Points

    "x of y" is displayed for each partial plant in the corresponding row and the sum "Partial plants" level of all partial plants is displayed in the bottom row. Level "Data points" does not have indication "x of y". Note 69 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function 28.08.2012...
  • Page 70: Energy Indicator" Visibility

    "Energy indicator" remains active even if "Energy indicator on the web = Not Notes visible" is selected. Configuration "Energy indicator on the web" (Visible/Not visible) also applies to user groups "Service" and "End user". 70 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function 28.08.2012...
  • Page 71: Summary Display "Energy Indicator" For A Plant

    The summary display "Orange leaf" with "2 Green limit(s) crossed" is displayed (in the previous example) because two "Green limits" were exceeded in "Heat circuit 2" (see next screenshot). 71 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator"...
  • Page 72: Energy Indicator" Commissioning Function

    Note LPB/BSB bus is interrupted. No comparison to "Green limits" then takes place and column "Value" contains "---" while column "Energy indicator" displays a "Grey leaf". 72 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function...
  • Page 73: Estimated Processing Time

    The checkbox in the "Energy indicator" column allows for deactivating monitoring of one or multiple data points e.g. for operational reasons. Data point monitoring active (default following commissioning) Data point monitoring deactivated 73 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function...
  • Page 74 Following "Monitoring off" and reactivation, "Energy indicator" data points may no longer be within the green limits, as the "Green limits" reset to default values have different dependencies. 74 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function...
  • Page 75: Activating "Data Point Monitoring

    "Data points" level are also activated. "Cooling circuit 1" is reactivated. All data points of "Cooling circuit 1" are reactivated. 75 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function 28.08.2012...
  • Page 76 Note that "Monitoring activated" at the "Partial plants" level does not mean that Note all subordinate data points are activated and monitored also. This also applies to "Monitoring activated" at the "Plant level". 76 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function...
  • Page 77: Dialog Boxes, Data Points, And "Green Limits

    The setting range for the data point value and its "Green limit" corresponds to the Bars green/orange bar limited by value indications to the right and left of the bar. 77 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator"...
  • Page 78: Dialog Boxes With Numeric Data Points

    1 Set the cooling setpoint by 1 K higher (or max. the same) as the "Green limit" Note to display the "Energy indicator" = "Green leaf". 78 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function...
  • Page 79: Dialog Boxes With Enumeration Data Points

    The entry fields of values that can not be set are grayed, i.e. they are unavailable for editing. Other than that, the dialog boxes are the same as for the "Administra- tor" user group. 79 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator"...
  • Page 80: E-Mail With "Energy Indicator" For The Plant

    • Reception is confirmed in data point "Energy indicator transmitted = Yes". • Data point "Reason" contains feedback on whether the e-mail was sent or which setting must be checked in the event of an error. 80 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator"...
  • Page 81: Mail Inbox

    • The next transmitted e-mail is transmitted as per Transmit time 1 and/or 2. • Manually triggered "Test receiver" is successful. The diagnostic options are identical to those of other e-mail recipients. Note 5.5.2 Mail inbox 81 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function 28.08.2012...
  • Page 82: E-Mail Contents

    10 lines follow this text where each line may contain a free text regardless of the language selected in the web server. (Signature line 1...10, with max. 49 char- acters per line). E-mail "Energy indicator" 82 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function 28.08.2012...
  • Page 83: Exceptions

    Changed data of the "Energy indicator" function are lost. The "Energy indicator" function starts with the data point values and "Green limits" similar to creating a device list in the web server. 83 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator"...
  • Page 84 Empty page 84 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies "Energy indicator" function 28.08.2012...
  • Page 85: Communications

    IP address of the web server in the router according to its MAC address. If the router with DHCP server is not available, the web server uses the default IP address 192.168.2.10. 85 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Communications 28.08.2012...
  • Page 86 The web server's IP address can be set manually as an option. • We recommend using IP addresses from the private range in the home network (see Section 7.3.1). 86 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Communications 28.08.2012...
  • Page 87 Select Start > Control Panel > Network Connections > Local Area Connection Select the "General" tab. Click [ Properties ] Select "Internet Protocol (TCP/IP)". Click [ Properties ] Select "Use the following IP address". Continued on next page. 87 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Communications 28.08.2012...
  • Page 88 • The default gateway and DNS server settings have no meaning for LANs without router, provided no e-mail is sent within the home network. • We recommend using IP addresses from the private range in the home network (see Section 7.3.1). 88 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Communications...
  • Page 89: Remote Operation Via The Internet

    The appropriate connection is required (e.g. DSL router) for remote operation via Internet. Setting up Internet access is not described here. • The example here were created using the Siemens Gigaset SX763 router (see Notes Section 7.3.5). Workflow, terms and functionality may differ when using other products.
  • Page 90 We recommend enabling the firewall to protect the local area network: • Firewall: On. Address Translation Activate NAT to ensure that the web server can be reached via the Internet. (NAT) • NAT: On. 90 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Communications 28.08.2012...
  • Page 91 In the example, queries from the Internet to the public IP address (Internet con- nection)/Port 80 is forwarded to the local IP address 192.168.2.10 (web server) / Port 80. 91 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Communications 28.08.2012...
  • Page 92 HTTPS encryption via port 443 is also supported. The required certificate is not Encrypted connection (HTTPS) accredited. The self-signed certificate from Siemens is valid for 20 years and is installed on the web server. The certificate must be installed on the web browser for encrypted communications.
  • Page 93: Messages Via E-Mail

    • Internet access is set up for the web server (see Section 6.1.2). • The settings for "E-mail", "Message receiver 1…4", "System report" (see Section 2.5.2). Example mail 93 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Communications...
  • Page 94 Web server fault Example of an e-mail Data point, information From: myhome@bluewin.ch …> Communication > E-mail: E-mail address sender service@siemens.com …> Message receiver > Message receiver 1…4: E-mail address Subj: Message central unit: Message type: Demo HCS, …> Texts: Name,...
  • Page 95 Fault inputs 1...2 Example of an e-mail Data point, information From: myhome@bluewin.ch …> Communication > E-mail: E-mail address sender service@siemens.com …> Message receiver > Message receiver 1…4: E-mail address Subj: Message central unit: Message type: Demo HCS, …> Texts: Name, …>...
  • Page 96 System report with fault Example of an e-mail Data point, information From: myhome@bluewin.ch …> Communication > E-mail: E-mail address sender service@siemens.com …> Message receiver > Message receiver 1…4: E-mail address Subj: Message central unit: Message type: Demo HCS, N. OK …>...
  • Page 97 "User name" and "Password" from the mail server for each e-mail transmission. • The mail server can also be installed on the local area network. 97 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Communications 28.08.2012...
  • Page 98 Empty page 98 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Communications 28.08.2012...
  • Page 99: Appendix

    Device failure (Bus) as a result, device failure (bus) is assigned to "System faults", whereas all other faults generated by the web server are assigned as "Local faults". 3) Possible causes of recipient type e-mail: Erroneous Ethernet or e-mail settings. 99 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Appendix 28.08.2012...
  • Page 100: Windows Commander

    Check whether DNS and mail servers can be reached. nslookup <IP address> Translates an IP address to the domain name and vice or <domain> versa: Look up domain names. 100 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Appendix 28.08.2012...
  • Page 101: Communications

    Arcor mail.arcor.de CompuServe smtp.compuserve.de Freenet mx.freenet.de T-Online smtpmail.t-online.de Additional information on free e-mail providers: • http://www.patshaping.de/hilfen_ta/pop3_smtp.htm • http://www.iopus.com/guides/bestpopsmtp.htm Note Siemens is not responsible for third-party page contents. 101 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Appendix 28.08.2012...
  • Page 102: Install Rndis Driver

    4. Wait until installation is complete and click [ Finish ] Result The RNDIS driver is now installed. The PC can communicate with the web server via USB. 102 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Appendix...
  • Page 103: Alternative Network Configuration

    The RNDIS driver is now installed. The PC can communicate with the web server via USB. Note The RNDIS driver is installed as part of the ACS790 Siemens software installation. 7.3.4 Alternative network configuration We recommend setting up IP settings for commissioning as an alternative configu-...
  • Page 104 Enter IP address, subnet mark and operational standard gateway as well as DNS server. Result The PC assumes the configuration with these settings as soon as it is no longer integrated in the standard network. 104 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Appendix 28.08.2012...
  • Page 105: Siemens Routers

    7.3.5 Siemens routers We recommend the following router from Siemens to connect to an internal network with DSL connection: We recommend the Gigaset SX763 WLAN dsl by Siemens. This router supports all requirements for trouble-free operation of web server. Performance features •...
  • Page 106: Glossary Of Ethernet And Internet Terms

    Internet. The DoS attack aims at disabling com- puters and networks to prevent network resources from being provided and ser- vices from being executed. 106 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Appendix 28.08.2012...
  • Page 107 The web server supports HTTPS (Hyper Text Transfer Protocol Secure). HTTPS A hub in a star-topology network connects various network devices by receiving all data from one device and forwarding it to other devices. 107 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Appendix...
  • Page 108 48 bit, e.g. 00-55-96-5D-00-2C. The MAC address is assigned by the network adapter manufacturer and cannot be changed. Mbps Million bits per second indicates the transmission rate in a network. Media Access Control See MAC address 108 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Appendix 28.08.2012...
  • Page 109 IP address). Port Forwarding is achieved by the correct NAT / PAT definition in the router. Protocol for dial-up connection of a computer to the ISP. PPP over Ethernet See PPPoE 109 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Appendix 28.08.2012...
  • Page 110 A standard gateway (see also DSL router) is also referred to as a network address used by clients to send their packages if the target address is outside the immedi- ate network. 110 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Appendix 28.08.2012...
  • Page 111 (application). UDP, in contrast to TCP, is an unsecured protocol. UCP is a so- called connection-less protocol. Data packets are broadcast. The recipient is re- sponsible for receiving data. The sender does not receive notification if the data packages were received. 111 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Appendix...
  • Page 112 In addition, they automatically provide, depending on class, own services or use services of other devices on the network. A URL refers to an information source, e.g. http://www.siemens.com. The URL is a uniform web address that is used to determine the network protocol used (e.g.
  • Page 113: Index

    Message recipient Numeric data points .......... 78 Holidays/special days ........31, 44 Setting range ............. 77 Monday...Sunday, special day .....30, 43 Display and operating elements ......8 DynDNS..............92 113 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Index 28.08.2012...
  • Page 114 LPB / BSB, Clock time supplier......24 Web server diagnostics ........44 Message recipients 1 to 4 ......... 27 Web server faults..........47 Time/Date ............22 Web server operation ........... 41 114 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies Index 28.08.2012...
  • Page 115 115 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies 28.08.2012...
  • Page 116 Siemens Switzerland Ltd Infrastructure & Cities Sector Building Technologies Division Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 © 2010-2012 Siemens Switzerland Ltd www.siemens.com/sbt Subject to change 116 / 116 Siemens Web server OZW672... V4.0 CE1C5712en Building Technologies 28.08.2012...