General functions
Web-Server
Fault input 1 and fault
input 2
Siemens
Building Technologies
Text for: Logic 1*
Default val:
1
Setting val:
Max. 20 char.
* Notes:
· Note Section 2.4, "Update device web pages".
· Delete the entry to reset to default text.
2.5.4.9
Faults
Path: Home > 0.5 OZW672... > Settings > Faults
The following settings specify behavior in case of faults.
Select "Settings > Inputs > Fault input 1...2" to configure the actual fault inputs.
(see Section 2.5.4.8 "Inputs").
Data point
Delete history
Default value: No
Setting values:No,
Yes
Data point
Message triggering
Default val.:
Coming
Setting val:
Coming,
Coming and going
These data points can be set for fault input 1 and 2.
Data point
Fault input 1..2*
Default val.:
(Blank)
Setting val:
Max. 20 char.
Fault status message
delay mm:ss
Default val.: 00:05.
Setting val: 00:00...59:55
(Resolution 00:05)
Fault priority
Default val.: Urgent
Setting val: Urgent
Not urgent
Text for: No fault*
Default val: [Fault input x] Fault.
Setting val: Max. 20 char.
Web Server OZW672... V6.0
Commissioning
Logic 1: Fault.
Customizable text for fault input status, e.g.
Water pressure too low.
Explanation, example
Deletes the history of all events and messages.
: Setting value Yes is a temporary state,
Note
after approximately 2 seconds, the setting value
returns automatically to No.
Explanation, example
Coming: A message is triggered when a fault
is received (start of fault).
Coming and going: A corresponding
message is triggered at start and end of fault.
A Web Server fault displays the LED
Explanation, example
Customizable text for fault input. The
designation is displayed in the menu and
transmitted as part of the message.
Identical to data point in "Settings > Inputs >
Fault input 1...2".
The Fault status message delay acts as a
filter for short-term fault events. The time the
Web Server must wait until a fault becomes
active is set here.
Filter when sending a fault.
The setting Urgent sends the fault to all active
message recipients. The setting Not urgent
exempts all message recipients subscribing to
"Only urgent ones".
Customizable text for the message for an
outgoing fault at the fault input; e.g. Water
pressure ok.
The designation is transmitted in messages.
.