1.5.1

Required programming

COMPLIANCE SETTINGS > UL Canada Compliance
Set the COMPLIANCE SETTINGS > UL Canada Compliance
parameter to Yes.
PANEL WIDE PARAMETERS > Report Routing > Fire Reports >

Fire Cancel

Set the PANEL WIDE PARAMETERS > Report Routing > Fire
Reports > Fire Cancel parameter for each Route Group (1 to 4)
to No.
Figure 1.17: Fire Cancel
POINTS > Point Profiles (Point Indexes)
Configure Point Profiles 1, 4, and 6 as shown below.
It is important to configure the parameters in order.
Point Profile 1
Set Alarm Abort to: No.
Set Point Profile Text (First Language) to: Fire Panel Trouble.
Set Point Type / Response / Circuit Style > Point Type to:
Fire Point.
Set Point Type / Response / Circuit Style > Circuit Style to:
Single EOL (1KΩ) or Single EOL (2KΩ).
Set Response to: 3.
Point Profile 4
Set Point Profile Text (First Language) to: Fire Panel Alarm.
Set Point Type / Response / Circuit Style > Point Type to:
Fire Point.