34
en | ULC Installation Guide
Control Panels
It is important to configure the parameters in order.
Point Profile 20
Set Point Profile Text (First Language) to: CF: Silence.
Set Point Type / Response / Circuit Style > Point Type to:
Custom Function.
Leave Point Type / Response / Circuit Style > Circuit Style at the
default: Single EOL (1KΩ).
Leave Point Type / Response / Circuit Style > Response at the
default: 7.
Figure 1.28: Point Profile 20
POINTS > Point Assignments
Set the POINTS > Point Assignments, Source, Text, and Profile
parameters, for points 9, 10, and 19 as follows.
Point 9
Set Point Assignments > Source to: Ouput.
Set Point Assignments > Text to: Fire Alarm Active.
Set Point Assignments > Profile to: 20 - CF: Silence
Point 10
Set Point Assignments > Source to: Ouput.
Set Point Assignments > Text to: Fire Trouble Active.
Set Point Assignments > Profile to: 20 - CF: Silence
Point 19
Set Point Assignments > Source to: Ouput.
Set Point Assignments > Text to: Fire Supervisory Active.
Set Point Assignments > Profile to: 20 - CF: Silence
2019.06 | 02 | F.01U.321.698