D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 19.0
.
19.0 UL/NFPA Compliant
Installations

19.1 Required Components

To install a D9412GV4 or D7412GV4 that is UL
and NFPA compliant, the following items must
be included:
D8109 Red Fire Enclosure
D192G Bell Supervision Module
D928 Dual Phone Line Module
D8004 Transformer Enclosure
Ground Fault Detect enabled on the
control panel
Refer to Table 38 on page 149 for specific
application installation requirements.
19.2 Installing Combination Fire and
Intrusion Alarm Systems
When installing a combination fire and
intrusion alarm system, you must
adhere to the following requirements
in order to comply with Sections 56.1,
56.2, and 56.4 of the 9
864.
Keypads used in Fire applications
must have Idle Scroll Lock enabled.

19.2.1 SDI Bus Devices

Keypads (Command Centers)
Keypads used exclusively for intrusion system
operation must be kept separate from fire
keypads. The use of an ICP-SDI-9114 is
required to separate fire and intrusion devices
on the SDI bus. All fire points must be within
the scope of a fire keypad (unless otherwise
required by local Authority Having Jurisdiction
(AHJ).
Bosch Security Systems, Inc. | 7/16 | F01U265457-09
th
Edition of UL
Interface Modules
Connect the DX4020 Network Interface
Module and the D9210C Access Control
Interface Module to the SDI bus only if
the interface module is located within
the control panel enclosure or in a
separate enclosure in the same room
within 20 ft (6.1 m) of the main control
panel.
Route all SDI bus wiring in EMT
(electrical metallic tubing) conduit.
Fire and Intrusion devices must be on
separate circuits. Refer to ICP-SDI-
9114 Installation Instructions (P/N:
F01U030068).

19.2.2 Zonex Bus Devices

When installing a combination fire and
intrusion alarm system with built-in
POPITs such as the ZX PIR's (ZX776Z,
ZX938Z, ZX935Z, ZX970, ZX794Z, or
ZX835), these devices cannot be used
on the same Zonex as the Fire system
with input devices.
D8125 POPEX Modules
The expansion bus can be shared between fire
and non-fire devices where the POPIT module
provides data isolation between the input and
the bus connections.
D8125MUX Multiplex Interface Modules
When connecting a D8125MUX module
to Zonex Bus 1 or 2, all multiplex
modules should supervise only all fire
or all non-fire devices.
Do not connect fire and non-fire
devices to the same D8125MUX
module.
Using Zonex Bus 1 exclusively for fire
devices and Zonex Bus 2 exclusively for
non-fire devices is acceptable.
D8128D OctoPOPIT Modules
Do not connect fire and non-fire
devices to the same D8128D
OctoPOPIT Module.
UL/NFPA Compliant
Installations
147