INSTALLATION

GENERAL INFORMATION
The MCT 1302 is a compact panel mounting instrument made of aluminum.
The instrument is installed in a panel in a slot with a drilling template of 138 x 82 mm and is secured
by means of the 2 tensioning screws supplied.
Rmax 2
138±1
The MCT 1302 must not be immersed in water, subjected to jets of water and cleaned or washed with
solvents.
Do not expose to heat or direct sunlight.
Do not install the instrument near power equipment (motors, inverters, contactors, etc.) or near devices
that do not comply with CE regulations for electromagnetic compatibility.
The connection cable for the load cells must have a maximum length of 140 m/mm2.
The RS232 serial line must have a maximum length of 15 meters (EIA RS-232-C standards).
The warnings given on the connection of the individual peripheral devices must be observed.
OVERALL DIMENSIONS
MCT 1302
149
136
30
20
5.0
149
Page 6