Temperature 1/2/3 
 
- Name: NDE / DE / R / S / T 
 
- Limit: Temperature alarm value, please fill in the motor specifications. 
- Early Warning: Temperature warning value, please fill in according to the motor
specifications. 
 
- Low: Minimum temperature, please fill in the motor specifications. 
 
- High: Maximum temperature, please fill in the motor specifications. 
 
Sudden Change 
 
- Amplitude: Please fill in the degree according to the demand. 
 
- Time: Please fill in the required values. 
 
 

VB200 Settings

5. 
 
VB-200 Series Vibration gauge's pre-set RS485 ID value is 15. If the same group of RS485
online to be connected to multiple VB-200 Series Vibration gauge, the installation method
must be a VB-200 installation wiring and in accordance with the following steps to modify
the RS485 ID on none-15 value (0 ~ 14), then can only be connected to the second set of VB-
200 series vibration and set. 
 
The purpose of setting only one VB-200 vibration gauge at a time is to avoid that if multiple
VB-200s are connected to the AG-300 Plus at the same time, the preset RS485 ID value of
whole VB-200 vibration gauges are the same (15), and hard to distinguish them. Not to avoid
setting may be troublesome, please do according to a set to complete and then connect to another
VB-200 series of vibration rules installation and setting. 
 
                  