Advertisement

 
AG-300 Plus
Gateway
 
User Manual
 
 
Copyright © 2018, All Rights Reserved.
Ver: R02 D/C: 106-1123
 
 

Advertisement

Table of Contents
loading

Summary of Contents for TECOM AG-300 Plus

  • Page 1   AG-300 Plus Gateway     User Manual     Copyright © 2018, All Rights Reserved.   Ver: R02 D/C: 106-1123...
  • Page 2   AG-300 Plus Gateway User Manual   Federal Communication Commission Interference Statement   This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
  • Page 3   AG-300 Plus Gateway User Manual   The device must be installed at least 1 meter from radio frequency equipment, such as TVs,   radios, hi-fi or video equipment (which radiate electromagnetic fields). Do not attempt to upgrade device in an unstable power environment. This could cause  ...
  • Page 4: Table Of Contents

    7.1 The wireless AP mode configuration (WiFi mode setup) ......  ..33  7.2 WiFi mode setting ....................38  8. Hardware Settings ......................42  The setting instructions of Teco inverter and Tecom AG-300 Plus Gateway ......44  The App Software Operation ......................46     ...
  • Page 5: Introduction

    Introduction   The Gateway AG-300 Plus, Temperture Transducer TT-300, Accelerometer VB-200 and Multi- function Power Meter PM-300 and so on. It is suitable for measuring the temperature, vibration and many power data in the power panel, electromechanical, rotational mechanical market. Gateway can benifit you easy to manage your manufacture electromechanical devices, make sure your equipment is in a healthy state and prevent catastrophic downtime. ...
  • Page 6: Setting Up The Gateway

    After unpacking the product package box, please connect the devices by following the connection figure as shown in below figure.  A. The AG-300 Plus WAN port (blue) connects to the ADSL modem LAN port via the network cable.  B. The AG-300 Plus is connected to the TT-300 and VB-200 or three-phase meters (PM-300) via RS-485. ...
  • Page 7: Rs-485 Wiring Method

    2’nd RS485  (2) TT-300  A. Connect TT-300 to AG-300 Plus by using CAT5e (or CAT6) cable.  B. Total two twisted pairs of CAT5e cable are used; one twisted pair for RS485 signal,  and the other twist pair would be used for power and ground. ...
  • Page 8   AG-300 Plus Gateway User Manual   (3) VB-200ST/VB-200SC    (RS485-)  (RS485+)    Twisted Pair    Twisted Pair    (4) PM-300    (RS485-)   (RS485+)       Twisted Pair  Pin 22 (B)    Pin 21 (A)       ...
  • Page 9: Pm-300 Pt/Ct Wiring Method

                          AG-300 Plus Gateway User Manual     PM-300 PT/CT wiring method   3.    Attention and warnings  (1) It is prohibited to carry out wiring work during power is on line.  (2) After the input power cut OFF, do not touch the circuit or change the wiring before the status P LED of PM-300 went off. ...
  • Page 10: Dimensions Of Devices

      4.    (1) AG-300 Plus dimensions : 130mm (L) x 99mm (W) x 36 mm (H) (2) PM-300 dimension : 72mm (L) x 72mm(W) x 86mm (H)  (3) TT-300 dimension : 59mm (L) x 36mm(W) x 16mm (H)  (4) VB-200ST dimensions : 30.5mm (L) x 30.5mm (W) x 11.5mm (H) (5) VB-200SC dimensions : Ø23.5 * 38.0 mm ...
  • Page 11: Pm-300 Views

      AG-300 Plus Gateway User Manual     PM-300 Views   6.          Page...
  • Page 12: Tt-300 Views

      AG-300 Plus Gateway User Manual     TT-300 Views   7.          Page...
  • Page 13: Vb-200St/Vb-200Sc Views

      AG-300 Plus Gateway User Manual     VB-200ST/VB-200SC Views   8.    Vibration gauge installation position (recommended)     Vibration measurement must observe the following rules according to ISO-10816 standard.  1. Close to the bearing  2. In direction either vertical or horizontal rather than 45-degrees or tilted direction  ...
  • Page 14   . AG-300 Plus Gateway User Manual Vertical      Axial  Vertical  Vertical      Vertical    Horizontal  Horizontal    Axial      Axial  Horizontal  Axial  Horizontal      3 Axials X/Y/Z Installation Location 安 3 Axials X/Y/Z Position  ...
  • Page 15: Installation Precautions

      AG-300 Plus Gateway User Manual   Installation Precautions     (1) VB-200SC is only suitable for installation with screw holes. If you want to add magnet, please use VB-200ST instead.  (2) VB-200ST original magnet on the surface of the flatness requirements, can not be used in the cylindrical motor.
  • Page 16: Installation Reference

      AG-300 Plus Gateway User Manual   Installation Reference     11-1 Vertical  When the vibration gauge is installed in the vertical direction, it should be placed just above the rotating shaft. At this time, the Z-axis of the vibration gauge is the vertical direction.
  • Page 17   AG-300 Plus Gateway User Manual   11-2 Horizontal  When the vibration gauge is installed in the horizontal direction, it should be placed on the level of the rotation axis, does not put too high, so as not to increase the vibration value.
  • Page 18   AG-300 Plus Gateway User Manual   11-3 Axial  When the vibration gauge measurement value is the axial direction, it must be placed on the level of the rotation axis, do not put too high, so as not to increase the vibration value.
  • Page 19: Device Settings

    - Connect an Ethernet cable point-to-point between Notebook/PC and AG-300 Plus (LAN Port)  - Connect the power adapter to AG-300 Plus  - The computer opens the browser, and the address bar enters the AG-300 Plus setup page URL http://192.168.168.10  - Enter the user name: admin ...
  • Page 20: Account Settings

      AG-300 Plus Gateway User Manual   Step 2  (if the network is DHCP plug and play, you can omit this step)  - In the left main menu click to use the 【Settings 】 【WAN Settings 】.  - Please select【STATIC (fixed IP)】in the WAN Connection Type Pull-down menu. ...
  • Page 21   AG-300 Plus Gateway User Manual   Click on the left main menu to use the 【Settings 】 【Unit Pairing 】, and then click the 【Add】button.    Step 2    - Name: Please enter your name.    - Account: 100 (account number 100-119 total 20 groups). ...
  • Page 22: Electromechanical Equipment Configuration

      AG-300 Plus Gateway User Manual - Password: Please enter your personal password (recommended account number). - When the setting is completed, click the 【Save】button below.    - Please click the【Start Pairing】to complete the account settings.      Electromechanical equipment configuration  ...
  • Page 23   AG-300 Plus Gateway User Manual   Step 2    Motor configuration table    - Name: Please define it yourself.    - Work ID: Please enter the motor number.    - Voltage: Please fill in the motor specifications.    - Current: Please fill in the motor specifications. ...
  • Page 24: Tt-300 Settings

    4-digit switches hardware, representing RS485 ID 0 ~ 15 (please refer to Section 8 of the device settings). Please set the RS485 ID of Gateway AG-300 Plus with the corresponding TT-300 to the same RS485 ID.         ...
  • Page 25   AG-300 Plus Gateway User Manual   - To add TT-300, please click the 【+】button.     - Line: Select to use line 1 or line 2, (Please select line 2 for TT-300) - RS485 ID: Please fill in according to RS485 specification. ...
  • Page 26: Vb200 Settings

    The purpose of setting only one VB-200 vibration gauge at a time is to avoid that if multiple VB-200s are connected to the AG-300 Plus at the same time, the preset RS485 ID value of whole VB-200 vibration gauges are the same (15), and hard to distinguish them. Not to avoid setting may be troublesome, please do according to a set to complete and then connect to another VB-200 series of vibration rules installation and setting. ...
  • Page 27   AG-300 Plus Gateway User Manual   - To add VB200, please click the【+】button under VB200 Item.    - Line: Select to use line 1 for VB-200 (Recommended). - RS485 ID: Please fill in according to RS485 specification. - Name: VB- 200 or defined by user. ...
  • Page 28   AG-300 Plus Gateway User Manual   Vibration X / Y / Z    - Name: X / Y / Z    Vibration    - Limit: Vibration alarm value, please fill in the motor specifications.  - Early Warning: Vibration warning value, please fill in according to the motor specifications. ...
  • Page 29   AG-300 Plus Gateway User Manual   Modify VB-200 RS485 ID    Please follow the following steps to modify the RS-485 ID of VB-200.      1. Select the   modify button   2. Modify VB-200's RS485 ID   and press 【Save】 button  ...
  • Page 30: Elecmeter (Pm-300) Settings

      AG-300 Plus Gateway User Manual     ElecMeter (PM-300) Settings   6.  - To add ElecMeter, please click the【+ 】button under ElecMeter Item. - To Select【PM300 】in the Type field    - Line: Select to use line 1 or line 2, (Please select line 2 for PM-300). ...
  • Page 31   AG-300 Plus Gateway User Manual - Down Limit: Under Voltage alarm value, please fill in the motor specifications. - Down Early: Under Voltage warning value, please fill in the motor specifications. - Low: Minimum voltage value, please fill in the specifications. ...
  • Page 32   AG-300 Plus Gateway User Manual   - Time: Please fill in the required values.    Power    - Limit: Power alarm value, please fill in accordance with the motor specifications. - Early Warning: Power warning value; please fill in accordance with the motor ...
  • Page 33: Wireless Setup

    Wireless setup   7.    Designed for e-gateway AG-300 Plus hardware, the "wireless setup" page contains options of WiFi mode, "Basic", "Advanced", "Security", and "Station list".    You may set WiFi mode into "Wireless AP mode" and "Wireless client mode". The wireless AP mode is an AP with gateway serving as WiFi access point. ...
  • Page 34   AG-300 Plus Gateway User Manual   WiFi [Disable] page: see figure below:    7.1.2 Advanced wireless settings    This option is aimed at setting up country/region and support channel with page as shown in figure below:       ...
  • Page 35   AG-300 Plus Gateway User Manual   7.1.3 Wireless security/encryption settings    This option is aimed at setting up wireless security and encryption to prevent equipment access and monitoring without certification; available security modes are WPASKWPA2PSK and Disable with factory default set to the latter. See figure below for page of this option: ...
  • Page 36   AG-300 Plus Gateway User Manual   Set up WPA algorithm, pass phrase, and key renewal interval; once set up and saved successfully users are required to input pass phrase set up here to connect to WiFi.       ...
  • Page 37   AG-300 Plus Gateway User Manual   The client end is required to log in WiFi router of e-gateway AG-300 Plus2 with his/her smartphone:          Page...
  • Page 38: 7.2 Wifi Mode Setting

      AG-300 Plus Gateway User Manual   7.1.4 Station list  Users of this solution may monitor clients connected to AP.    7.2 WiFi mode setting   Select STA mode and click [Apply] in the WiFi mode setting.       ...
  • Page 39   AG-300 Plus Gateway User Manual   7.2.1 Station profile    Having a gateway as an ordinary client, this page displays information of APs saved in the gateway; you may add, delete, and edit information of desired AP; select an AP and click "Open", the gateway will then auto connect to the AP;...
  • Page 40   AG-300 Plus Gateway User Manual   7.2.2 Edit station profile    In most cases, users may change parameters of "Name", "SSID", "BSSID" and "Security policy" and leave default value of the others intact in the station profile edit page. ...
  • Page 41   AG-300 Plus Gateway User Manual   7.2.3 Station link status    Link information after gateway connected to AP is shown here. 7.2.4 Scan near AP          Page...
  • Page 42: Hardware Settings

                             AG-300 Plus Gateway User Manual   Scan gateway neighboring APs for information  Click "Connect" to connect the AP; data of the latter are not saved (data lost after gateway restarted).  Click "Rescan to scan" neighboring APs once again. Scanning may fail to identify all APs when there are many available nearby;...
  • Page 43   AG-300 Plus Gateway User Manual   B. AG-300 Plus Pin Assignment    (1) 1’st RS485 pin out : Pin 1 & 2 (2) 2’nd RS485 pin out : Pin 5 & 6 (3) DO pin out : Pin 7~9 ...
  • Page 44: The Setting Instructions Of Teco Inverter And Tecom Ag-300 Plus Gateway

      This setting document is for the Teco inverter (hereinafter referred to as the inverter) and the Tecom AG-300 Plus Gateway (hereinafter referred to as the AG-300 Plus), in the hardware wiring and parameter settings for a brief description.   ...
  • Page 45   AG-300 Plus Gateway User Manual   RS485 Pin Assignment of Inverter RJ-45 and Connect to AG-300 Plus                   1  2  3  4  5  6  7  8  Data+ Data –  Data+ RSV. ...
  • Page 46: The App Software Operation

    App in the mobile phone. The mobile phone must have the outbound network connection capability to use this App.    Step 1  Please start TECOM Smart Monitor System APP.    Step 2  Please click Sign In . ...
  • Page 47 Note :  - Host ID code can be retrieved in the setting page once AG-300 Plus is connected to network.  - In the left main menu, click Device information Status overview. Host ID code can be found in System information. ...
  • Page 48   AG-300 Plus Gateway User Manual   Step 4  After logged in, please click the name of the motor to enter, to retrieve the information of that motor.    TECOM Co., Ltd   No.23, R & D Rd. II,  ...

Table of Contents