Part name
Stop switch
Load factor monitor
Speed monitor
Eco-mode lamp
(Speed change indication lamp)
Block heater relay
Droop switch
Rmax1 switch
Rmax2 switch
Speed1 switch
Speed2 switch
Reverse droop switch
Speed selection enable switch
TNV Application Manual
Table 2-7 Requirements of user-selected electrical parts
E-ECU pin No.
E15
E32
E22
E2
E24
E13
E14
E9
E17
E5
E6
Requirements
Contact
Normally closed (b-contact)
Max.
current 12 Vdc/20 mA or higher
Min.
current 12 Vdc/10 mA or lower
Resistive load
Pulled up to 12 Vdc
Max. current
12 Vdc/200 mA or lower
ON voltage
1.5 V Max.
OFF voltage
Power supply voltage
Lamp load
12 Vdc-3.4 W Max.
Rush current
12 Vdc/3 A-10ms Max.
Contact
Normally open (a-contact)
Rated voltage
12 Vdc
Rated load current 100V: 115 Vac/4 A Min., continuous
200V: 210 Vac/2 A Min., continuous
Coil current
12 Vdc/300 mA Max.
Coil inductance
200 mH Max.
Switching durability 10
Other features must be compliant with applicable specifications.
When the block heater is connected to the commercial
power supply, observe standards and regulations
concerning the dielectric withstand voltage and insulation
resistance of relay contacts.
Contact
Normally open (a-contact)
Max. current
12 Vdc/20 mA or higher
Min. current
12 Vdc/10 mA or lower
CONTROL SYSTEM
6
times or more
2-23