Hotel buildings

Advertisement

Application Manual
Eenergy center – primary control
Ventilation control
ADCE06 U2B HQ
Heating control
HB0001 H6B HQ
H0F001 H6B HQ
Refrigeration control
CBA001 U2B HQ
Supply air temperature control for VAV systems
·
Control of speed-controlled fans with differential pres-
sure control
·
Control of air dampers depending on indoor air quality
·
Control of supply air temperature via the heat recovery
system, the valve of the air cooling coil and the valve of
the air cooling coil in sequence
Weather-compensated boiler temperature control with con-
trolled maintained boiler return temperature
·
Weather-compensated boiler temperature control
·
Maintained boiler return temperature with own mixing
valve
·
Control of boiler pump depending on boiler operating
mode
·
Control of a 1- or 2-stage burner
·
Control of boiler temperature by modulating burner with
modulating DC 0...10 V control
Demand-compensated precontrol for external consumers
·
Demand-compensated precontrol
Demand-dependent chilled water generation
·
On/off of plant depending on the request from consum-
ers (request via KNX)
·
Plant on via external contact (demand)
·
Control of chilled water pump, with pump kick and mon-
itoring of volumetric flow
·
Control of recooling pump, with pump kick and monitor-
ing of volumetric flow
·
Control of chilled water flow temperature through acti-
vation of recooling pump and switching on of refrigera-
tion machine
·
Control of recooling temperature via recooling valve
and activation of recooling fans
·
Control of refrigeration machine via on/off command
compressor, refrigeration valve and monitoring input for
fault status signal from the refrigeration machine. The
Nr. 11
Synco™
& Gamma
59