Hotel buildings

Advertisement

Application Manual
Reception area – room automation
Air conditioning plant with indoor air quality and lighting control
Features
·
·
·
·
·
·
·
Room setup
Room-supply air temperature control/CO
Automatic data exchange between room HVAC and primary plant
VAV controller to optimize the ventilation system
Remote control of individual rooms or groups of rooms
Demand-compensated production of heat and cooling energy thanks to automatic data
exchange with heating and refrigeration controller
Constant light control
Efficiency class A conforming to EN 15232
1.
AQR2532 room sensor with AQR2576 basic module: The AQR sends information about the room
temperature and the indoor air quality to the ventilation controller, which controls the temperature and the
proportion of fresh air in the supply air.
2.
N 141/02 KNX/DALI gateway: The N141 transmits the KNX signal to the DALI bus to switch and dim the
lighting. In the other direction, status information, such as error messages or operating times of lamps, is
sent to the KNX bus.
3.
UP258E21 presence detector with constant light control: The UP258E21 acquires room occupancy
and brightness. This information is then fed to the room thermostat and the KNX/DALI gateway.
4.
UP 588 color touch panel: The UP 588 is used to control and monitor HVAC, the lighting and the blinds.