Download Print this page

Siemens Synco-Gamma Application Manual page 11

Hotel buildings

Advertisement

Application Manual
Hotel rooms – room automation
Fan coil unit with radiator in the bathroom, sun protection, presence-
dependent switching off of lighting and power supply
Features
·
·
·
·
·
·
·
·
·
·
·
·
Room setup
Individual room temperature control, heating and cooling
One control loop for the room and the bathroom
Automatic or manual fan control, 1- or 3-speed
Automatic or manual changeover of heating/cooling mode
Window contact – central detection of open windows
Detection of presence via hotel card switch
Presence- and time-dependent control of HVAC, lighting, sun protection, and power
supply to the room
Dimming and switching of lighting
Operation and display of HVAC
Simple and flexible installation thanks to wireless technology
Pushbuttons for "SOS", "Make up room", and "Do not disturb"
Demand-compensated production of heat and cooling energy thanks to automatic data
exchange with primary plant
1.
Room thermostat RDF600KN: The RDF600KN acquires the room temperature and controls the fan coil
unit and the radiator in the bathroom accordingly. The room operating mode can be selected and the
temperature setpoints can be adjusted on the room thermostat.
2.
STA23 electrothermal actuator: The STA23 adjusts the valve according to the positioning signal it
receives from the controller.
3.
AP 641 room control box: The AP 641 features 8 sockets for room automation modules type RS or RL.
4.
RS 525/23 universal dimmer: The RS 525/23 features a relay contact to dim a lighting group up to 250
VA.
5.
RL 521/23 blind actuator: The RL 521/23 features 2 relay contacts to control blinds.
6.
RS 510/23 binary output, 2-fold: The RS 510/23 features 2 relay contacts to switch electric circuits.
7.
RXZ97.1 gateway EnOcean/KNX: The RXZ97.1 converts EnOcean wireless signals from the wall trans-
mitter to KNX telegrams.
Nr. 01
Synco™
& Gamma
11

Advertisement

loading