ABB RELION 615 Series Product Manual page 40

Motor protection and control
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Motor Protection and Control
REM615
Product version: 5.0 FP1
Table 57. Circuit breaker failure protection (CCBRBRF) main settings
Parameter
Current value
Current value Res
CB failure mode
CB fail trip mode
Retrip time
CB failure delay
CB fault delay
Table 58. Arc protection (ARCSARC)
Characteristic
Operation accuracy
Operate time
Reset time
Reset ratio
Phase start value = 1.0 × I
1)
, current before fault = 2.0 × set
n
2)
Includes the delay of the heavy-duty output contact
3)
Normal power output
4)
High-speed output
Table 59. Arc protection (ARCSARC) main settings
Parameter
Phase start value
Ground start value
Operation mode
Table 60. Multipurpose protection (MAPGAPC)
Characteristic
Operation accuracy
40
Function
CCBRBRF
CCBRBRF
CCBRBRF
CCBRBRF
CCBRBRF
CCBRBRF
CCBRBRF
Operation mode = "Light
1)2)
+current"
Operation mode = "Light only"
Phase start value , f
= 50 Hz, fault with nominal frequency, results based on statistical distribution of 200 measurements
n
Function
ARCSARC
ARCSARC
ARCSARC
Value (Range)
0.05...2.00 × I
n
0.05...2.00 × I
n
1 = Current
2 = Breaker status
3 = Both
1 = Off
2 = Without check
3 = Current check
0...60000 ms
0...60000 ms
0...60000 ms
Value
±3% of the set value or ±0.01 × I
Minimum
3)
9 ms
4 ms
4)
2)
3)
9 ms
4)
4 ms
Typically 40 ms
Typically 0.96
Value (Range)
0.50...40.00 × I
n
0.05...8.00 × I
n
1 = Light+current
2 = Light only
3 = BI controlled
Value
±1.0% of the set value or ±20 ms
1MRS756890 N
Step
0.05
0.05
-
-
10
10
10
n
Typical
Maximum
3)
12 ms
15 ms
6 ms
4)
9 ms
4)
3)
10 ms
12 ms
4)
4)
6 ms
7 ms
Step
0.01
0.01
-
3)
3)
ABB