Table 9. Energizing inputs (sensors)
Description
Current sensor input
Voltage sensor input
1)
Equals the current range of 40...4000 A with a 80 A, 3 mV/Hz Rogowski
2)
Depending on the used nominal current (hardware gain)
3)
This range is covered (up to 2*rated) with sensor division ratio of 10 000:1
Table 10. Binary inputs
Description
Operating range
Rated voltage
Current drain
Power consumption
Threshold voltage
Reaction time
Table 11. RTD/mA measurement (XRGGIO130)
Description
RTD inputs
mA inputs
ABB
Rated current voltage (in secondary
side)
Continuous voltage withstand
Input impedance at 50/60 Hz
Rated voltage
Continuous voltage withstand
Input impedance at 50/60 Hz
Supported RTD sensors
Supported resistance range
Maximum lead resistance (three-
wire measurement)
Isolation
Response time
RTD/resistance sensing current
Operation accuracy
Supported current range
Current input impedance
Operation accuracy
Value
75 mV...9000 mV
1)
125 V
2)
2...3 MΩ
3)
6 kV...30 kV
50 V
3 MΩ
Value
±20% of the rated voltage
24...250 V DC
1.6...1.9 mA
31.0...570.0 mW
16...176 V DC
<3 ms
Value
100 Ω platinum
250 Ω platinum
100 Ω nickel
120 Ω nickel
250 Ω nickel
10 Ω copper
0...2 kΩ
25 Ω per lead
2 kV (inputs to protective earth)
<4 s
Maximum 0.33 mA rms
Resistance
± 2.0% or ±1 Ω
0...20 mA
44 Ω ± 0.1%
±0.5% or ±0.01 mA
1MRS756890 N
TCR 0.00385 (DIN 43760)
TCR 0.00385
TCR 0.00618 (DIN 43760)
TCR 0.00618
TCR 0.00618
TCR 0.00427
Temperature
±1°C
10 Ω copper: ±2°C
23