Motor Protection and Control
REM615
Product version: 5.0 FP1
Table 4. Input/output overview
Std. conf.
Order code digit
5-6
AC / AD
A
AG / AH
CA / CB
B
CC / CD
C
AE / AF
D
DA

18. Station communication

The relay supports a range of communication protocols
including IEC 61850 Edition 2, IEC 61850-9-2 LE, IEC
®
60870-5-103, Modbus
communication protocol is supported with using the protocol
converter SPA-ZC 302. Operational information and controls
are available through these protocols. However, some
communication functionality, for example, horizontal
communication between the relays, is only enabled by the IEC
61850 communication protocol.
The IEC 61850 protocol is a core part of the relay as the
protection and control application is fully based on standard
modelling. The relay supports Edition 2 and Edition 1 versions
of the standard. With Edition 2 support, the relay has the latest
functionality modelling for substation applications and the best
interoperability for modern substations. It incorporates also the
full support of standard device mode functionality supporting
different test applications. Control applications can utilize the
new safe and advanced station control authority feature.
The IEC 61850 communication implementation supports
monitoring and control functions. Additionally, parameter
ABB
Analog channels
7-8
CT
AB
4
AD
4
4
FE
AB
4
AH
4
AJ
4
4
FD
4
FF
AH
4
4
FD
AG
4
4
FC
AH
1
1
FD
and DNP3. Profibus DPV1
Binary channels
VT
Combi
BI
sensor
-
-
4
-
-
12
-
-
12
-
-
4
3
-
8
3
-
14
3
-
8
3
-
14
3
-
8
3
-
8
5
-
16
5
-
16
-
3
8
-
3
8
settings, disturbance recordings and fault records can be
accessed using the IEC 61850 protocol. Disturbance
recordings are available to any Ethernet-based application in
the standard COMTRADE file format. The relay supports
simultaneous event reporting to five different clients on the
station bus. The relay can exchange data with other devices
using the IEC 61850 protocol.
The relay can send binary and analog signals to other devices
using the IEC 61850-8-1 GOOSE (Generic Object Oriented
Substation Event) profile. Binary GOOSE messaging can, for
example, be employed for protection and interlocking-based
protection schemes. The relay meets the GOOSE performance
requirements for tripping applications in distribution
substations, as defined by the IEC 61850 standard (<10 ms
data exchange between the devices). The relay also supports
the sending and receiving of analog values using GOOSE
messaging. Analog GOOSE messaging enables easy transfer of
analog measurement values over the station bus, thus
facilitating for example the sending of measurement values
between the relays when controlling parallel running
transformers.
1MRS756890 N
BO
RTD
mA
4 PO + 2 SO
-
-
4 PO + 6 SO
-
-
4 PO + 2 SO
-
-
+ 3 HSO
4 PO + 2 SO
6
2
4 PO + 6 SO
-
-
4 PO + 9 SO
-
-
4 PO + 2 SO
-
-
+ 3 HSO
4 PO + 5 SO
-
-
+ 3 HSO
4 PO + 6 SO
6
2
4 PO + 2 SO
6
2
+ 3 HSO
4 PO + 6 SO
-
-
4 PO + 2 SO
-
-
+ 3 HSO
4 PO + 6 SO
-
-
4 PO + 2 SO
-
-
+ 3 HSO
17