Motor Protection and Control
REM615
Product version: 5.0 FP1
received from other devices over the station bus, thus
increasing the extent of relevant information.
The standard configuration D includes one conventional
residual current (Io) input and three combi-sensor inputs for
phase currents and phase voltages. The connection of the three
combi-sensors is made with RJ-45 type of connectors.
Sensors offer certain benefits compared to conventional
current and voltage instrument transformers, for example,
GUID-52860380-D410-4969-A44E-7C7311221D0F V5 EN
Figure 5.
Motor protection and control of contactor and circuit breaker controlled motors using standard configurations A and B
Figure 5
illustrates an example of motor protection and control
of contactor and circuit breaker controlled motors using
standard configurations A and B. To prevent possible power
system instability due to busbar voltage collapse, the
10
3I
Io
RTD
REU615
REM615
Std. conf.
B
Std. conf.
ANSI
ANSI
IEC
37
3I<
47O-/59
47U+/27
46R
I2>>
47O-/59
U2>/3U>
50L/50NL
59G
47U+/27
U1</3U<
49,66,48,51LR
Is2t n<
81
49M
3Ith>M
81LSH
50L/50NL
ARC
1)
Light detection only
51N-2/67N-1
Io>>/Io> ->
50P/51P
3I>>>
51LR
Ist>
51P/51N
3I/Io
current sensors do not saturate at high currents, they consume
less energy and they weigh less. In voltage sensors the risk of
ferro-resonance is eliminated. The sensor inputs also enable
the use of the relay in compact medium voltage switchgears,
such as ABB's UniGear Digital, SafeRing and SafePlus, with
limited space for conventional measuring transformers, thus
requiring the use of sensor technology. Further, the adapters
also enable the use of sensors with Twin-BNC connectors.
REF615
Std. conf.
C/D
ANSI
IEC
46
I2>
Io
50L/50NL
ARC
50P/51P
3I>>>
50N/51N-1/51N-2
Io>>>/Io>>/Io>
51BF/51NBF
3I>/Io>BF
3I
68
3I2f>
3I
3U
Uo
Io
RTD
REM615
A
Std. conf.
IEC
ANSI
IEC
U2>/3U>
37
3I<
U1</3U<
46R
I2>>
1)
ARC
1)
49,66,48,51LR
Is2t n<
Uo>
49M
3Ith>M
f</f>,df/dt
50L/50NL
ARC
UFLS/R
51N-1/51N-2
Io>>/Io>
50P/51P
3I>>>
51LR
Ist>
51P/51N
3I/Io
simultaneous starting of several motors can be inhibited with
the "restart inhibit" input of REM615. The optional RTD/mA
inputs are utilized for motor winding and bearing temperature
supervision.