Omron C200H Series Replacement Manual page 29

From c200h to cs1
Hide thumbs Also See for C200H Series:
Table of Contents

Advertisement

<Transistor Output Units>
C200H-series Unit
C200H-OD217
24 VDC, 0.3A, Sourcing,
Terminal block, 12 outputs
C200H-OD212
24 VDC, 0.3A, Sinking,
Terminal block, 16 outputs
C200H-OD21A
24 VDC, 1.0A, Sourcing,
Terminal block, load short
circuit protection, 16 outputs
C200H-OD218
4.5 to 26.3 VDC, 0.1A,
Sinking, Connector, 32
outputs (Group-2)
C200H-OD215
4.5 to 26.3 VDC, 0.1A,
Sinking, Connector, 32
outputs (Special I/O )
C200H-OD21B
24 VDC, 0.5A, Sourcing,
Connector, load short circuit
protection, 32 outputs
(Group2)
Corresponding CS-series Unit
CS1W-OD212
12-24 VDC, 0.5A, Sourcing,
Terminal block, load short circuit
protection, 16 outputs
CS1W-OD211
12-24 VDC, 0.5A, Sinking,
Terminal block, 16 outputs
CS1W-OD212
12-24 VDC, 0.5A, Sourcing,
Terminal block, load short circuit
protection, 16 outputs
CS1W-OD231
12-24 VDC, 0.5A, Sinking,
Connector, 32 outputs
CS1W-OD231
12-24 VDC, 0.5A, Sinking,
Connector, 32 outputs
CS1W-OD232
12 - 24 VDC, 0.5A, Sourcing,
Connector, load short circuit
protection, 32 outputs
Description
Transistor Output Units with
terminal block for 12 outputs.
Replace this unit with a
Transistor Output Unit with 16
outputs.
Transistor Output Units with
terminal block for 16 outputs.
Transistor Output Units with
terminal block for 16 outputs.
Transistor Output Units with
connector for 32 outputs.
Transistor Output Units with
connector for 32 outputs.
*The CS-series does not have
Unit which supports Dynamic
Output. Continue using this
C200H Unit or change the
wiring for static mode.
Transistor Output Units with
connector for 32 outputs.
Difference
1) Terminal block
2) Output points (12-> 16 points)
3) Number of circuit (12 points/common x1
circuit ->8 points/common x2 circuits)
4) Output circuit specification
Output voltage range (5 to 24 VDC ->
24VDC)
5) Internal current consumption
(5VDC:10mA->170mA, 26VDC:75mA->
0mA)
6) External power supply (Not required ->
24VDC:40mA)
1) Terminal block
2) Number of circuit (16 points/common x1
circuit ->8 points/common x2 circuits)
3) Output circuit specification
Residual voltage (1.4V->1.5V)
ON response time(0.2ms->0.5ms)
OFF response time(0.3ms->1.0ms)
1) Terminal block
2) Number of circuit (16 points/common x1
circuit ->8 points/common x2 circuits)
3) Output circuit specification
Output capacity (1A/point, 4A/Unit ->
0.5A/point, 5A/Unit)
Residual voltage (0.8V->1.5V)
ON response time (0.1ms->0.5ms)
OFF response time (0.3ms->1ms)
4) Internal current consumption
(5VDC:160mA-> 170mA)
5) External power supply (24 VDC: 35mA->
40mA)
6) Alarm output (Supported -> Not
supported)
1) Number of circuit (32 points/common x1
circuit ->16 points/common x2 circuits)
2) Output circuit specification
Output voltage range (5 to 24 VDC-> 12 to
24VDC)
Residual voltage (0.8V->1.5V)
ON response time (0.1ms->0.5ms)
OFF response time(0.4ms->1ms)
3) Internal current consumption(DC5V:
180mA->270mA)
4) External power supply (5 to 24
VDC:110mA -> 12 to 24VDC:50mA)
1) Connector
2) Output method (Dynamic or Static mode
-> Static only)
The specification of static is as follows.
3) Number of circuit (8 points/common x 4
circuits ->16 points/common x2 circuits)
4) Output circuit specification
Output voltage range(5 to 24 VDC -> 12 to
24VDC)
Residual voltage (0.7V->1.5V)
ON response time (0.2ms->0.5ms)
OFF response time (0.6ms->1ms)
5) Internal current consumption
(5VDC:220mA->270mA)
6) External power supply (5 to 24
VDC:90mA -> 12 to 24VDC:50mA)
1) Number of circuit (32 points/common x1
circuit ->16 points/common x2 circuits)
2) Output circuit specification
Output capacity (0.5A/point, 5A/Unit ->
0.5A/point, 2.5A/Common, 5A/Unit)
Residual voltage (0.8V->1.5V)
ON response time (0.1ms->0.5ms)
OFF response time (0.3ms->1ms)
3) Internal current consumption
(5VDC:180mA -> 270mA)