Foundation Fieldbus CP Option Card Technical Manual
8.6
Default settings
Transducer Block
Param. No.
Description
50
Limited Range
Position Minimum
51
Limited Range
Position Maximum
52
Deadband
53
Hysteresis
54
Slow Mode Range
55
Motion Inhibit Time
56
Action on Loss of
Comms
57
Comms Lost
Position
58
Comms Fault Timer
59
Aux Input Mask
60
ESD HW_DI-4/Net
Disable
61
Part stroke % travel
position
62
Part stroke limit
63
Part stroke timeout
64
Partial stroke status
65
Control Mode [DO
4 function]
66
Discrete Block
control
86 of 116
Range
0-100%
0-100%
0.0-25.5%
0.0-25.5%
0-100%
0-255s
Value:
0 – No Action
1 – Open
3 – Close
5 – Stop
7 – Position
Any other value = off
0-100%
0-255s
0x00-0xFF
0- ESD function
1- Network disable
0-100%
0 – Close limit
1 – Open limit
0-7200 seconds
2 Date fields:
Partial Stroke Success
Partial stroke Failure
(MM/DD/YY HH:MM:SS)
Value:
0 – Positioning mode
1 – ESD
2 – S5 relay operate
3 – Partial stroke (DO)
4 – AO only
5 – Two-wire control
6 – Positioning mode
Bit:
0 – Multiple support
1 – Single support
Publication PUB089-005-00_0618
Default Setting
0%
100%
5.0%
2.0%
5%
5 sec
0 (No action)
0%
10 sec
0F
0
90%
1
300 sec
01/01/72 00:00:00
0
Note:
1. Not all actuator types
support partial stroking.
2. Mode 6 offers both
position control and
partial stroking in multibit
support..
0