Foundation Fieldbus CP Option Card Technical Manual
8.1
Setting up with the Setting Tool
The actuator includes a communication port for setting the actuator performance, limit switches etc.
via the Setting Tool. This communication link can be used to set some, but not all, of the actuator
specific Transducer Block parameters. The parameters will be supplied set to their factory default
values. These should still be checked with a configuration tool to ensure optimum actuator and
network compatibility. Refer to the relevant actuator's "Full Configuration Manual" to see the access
route through the actuator menu screens to reach the settings that affect the FF CP card.
The Transducer block parameters that may be set by using the Setting Tool are listed below. The
available range for the deadband setting when using the setting tool is less than the range found using
the configuration tools.
FF TB
Parameter
50
Limited Range Position Minimum
51
Limited Range Position Maximum
52
Deadband
53
Hysteresis
55
Motion Inhibit Time
59
Comms loss action
60
Comms lost position
61
Comms Fault timer
62
Auxiliary Mask (Function)
Note:
Parameters may only be altered by the setting tool if the actuator control knob is set to the
Local or Local Stop position.
78 of 116
Description
Publication PUB089-005-00_0618
Range
0 – 100%
0 – 100%
0.0 – 9.9%
0.0 – 9.9%
0 – 255 sec
0 – No Action
1 – Open
3 – Close
5 – Stop
7 – Position
Any other value = off
0-100%
0-255s
0x00-0xFF
Default
Value
0%
100%
5.0%
2.0%
5 sec
0
0
10
0x0F