Appendix F - Changing The Itk Revision - rotork Mk3 Technical Manual

Foundation fieldbus option card
Table of Contents

Advertisement

Foundation Fieldbus CP Option Card Technical Manual
APPENDIX F – CHANGING THE ITK REVISION
1
Using a setting tool with an IQ3/IQT3/SI
NB. - This procedure requires:
.
Actuator User Interface PCB firmware to be at least version V113
·
Foundation fieldbus software version to be at least V/M3.1B1.4H1.1.
·
The FF highway to be both connected and powered up.
The actuator's mains power to be applied.
.
·
At least a service engineer level password to change the ITK revision.
In order to see what the current ITK version is, it is necessary to have a correctly powered Foundation
Fieldbus network connected to the actuator. Without the network applied, the menu item will show, as
default, ITK4.6 although this may not be the ITK version of the card.
Fig F.1: Changing the ITK rev via the HMI on an IQ3 / IQT3 / SI
Once the correct password has been entered, a different ITK version can be selected and entered.
Once done, it is necessary to restart the Rotork Foundation Fieldbus card to enable the setting to take
effect. This can be done by cycling the power on the fieldbus network or disconnecting the fieldbus
connection to the Rotork Foundation Fieldbus card. Alternatively, if an NI Configurator Tool is
connected, restart the processor as shown in section 3.
Please note the EEPROM is cleared during this operation so the restart process could take a couple
of minutes to complete.
Restarting the processor does not delete the tag names nor any project schedule that the card may
have.
If you're unfamiliar with using a setting tool, go to section 2 of this appendix.
106 of 116
via the Foundation Field bus menu item.
3
Publication PUB089-005-00_0618
actuator
3

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Mk3 and is the answer not in the manual?

Questions and answers

Table of Contents

Save PDF