Actuator Analogue Input feedback

The FF CP card includes two Analogue Input blocks, AI 1 and AI 2, which are used to report
information about the valve and actuator. These blocks are connected to the Transducer block in the
default configuration.
Function Block
No
AI 1
Valve Position
AI 2
Actuator Instantaneous
Torque/Thrust
Valve Position
Torque
Analogue Feedback
The current valve position is reported as an Integer Value in the range
0.0 to 100.0% in block AI 1.
The actuators automatically scale the valve position value reported
from the setting of the limit switches. This scaling is retained in
EEPROM when the actuator power is removed.
If Limited Range Positioning is invoked by setting the appropriate
parameters, then the reported valve position 0.0 to 100.0% follows the
limited range of valve travel.
The currently developed torque value is reported in block AI 2 in the
range 0 to 120% representing the percentage of actuator rated torque
generated.