Satel Integra 24 Programming Manual
Satel Integra 24 Programming Manual

Satel Integra 24 Programming Manual

Alarm control panel
Hide thumbs Also See for Integra 24:
Table of Contents

Advertisement

PROGRAMMING
SATEL sp. z o.o.
ul. Budowlanych 66
80-298 Gdańsk
POLAND
tel. + 48 58 320 94 00
www.satel.eu
integra_p_en 04/16

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Integra 24 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Satel Integra 24

  • Page 1 PROGRAMMING SATEL sp. z o.o. ul. Budowlanych 66 80-298 Gdańsk POLAND tel. + 48 58 320 94 00 www.satel.eu integra_p_en 04/16...
  • Page 2 Before you start programming, please read carefully this manual in order to avoid mistakes that can lead to malfunction or even damage to the equipment. SATEL's goal is to continually upgrade the quality of its products, which may result in some changes of their technical specifications and firmware. The current information on the introduced modifications is available on our website.
  • Page 3 Changes made to the firmware version 1.15 Support for new wireless devices: Wireless devices AOD-200 – wireless outdoor dual technology motion detector (INTEGRA 128-WRL control panel or a control panel to which ACU-120 / ACU-270 controller is connected), ASP-100 – wireless outdoor siren (control panel to which ACU-120 / ACU-270 controller is connected).
  • Page 4: Table Of Contents

    Programming SATEL CONTENTS General ..........................5 Configuring the control panel with keypad ................5 Starting the service mode ..................5 Starting the service mode “from pins” ................6 Hiding the service mode ....................6 Exiting the service mode....................6 Service mode menu....................7 Entering data by means of the keypad ..............23 2.6.1...
  • Page 5 SATEL INTEGRA Options ........................61 Output triggering...................... 61 Clearing alarm in partitions ..................62 Output disabling....................... 62 Output groups......................62 Output state indicating..................... 63 Logical functions of outputs ..................63 5.10 Output testing ......................63 System options ....................... 64 Telephone options ....................64 Printer options ......................
  • Page 6 Programming SATEL 12.1.6 Event codes ......................... 90 12.1.7 Test transmissions ....................... 90 12.1.8 SMS reporting only INTEGRA 128-WRL ..............91 12.2 Starting the reporting ....................91 12.2.1 Telephone reporting ..................... 91 12.2.2 Reporting via Ethernet network..................92 12.2.3 GPRS reporting......................92 12.2.4...
  • Page 7: General

    GPRS communication is possible in case of INTEGRA 128-WRL control panel or after connecting the SATEL GSM module to the control panel. Communication over Ethernet is possible after connecting the ETHM-1 Plus / ETHM-1 Ethernet module to the control panel.
  • Page 8: Starting The Service Mode "From Pins

    In INTEGRA 24, INTEGRA 32, INTEGRA 64 and INTEGRA 128 control panels, the DIALER LED will start blinking. 4. Wait about 10 seconds (in INTEGRA 24, INTEGRA 32, INTEGRA 64 and INTEGRA 128 control panels, the DIALER LED will go off) and remove the jumper from the pins. The control panel will enter the service mode.
  • Page 9: Service Mode Menu

    SATEL INTEGRA Service mode menu Functions relating to INTEGRA 128-WRL control panel only are highlighted by white font on black background. Service end SM settings Service code INTEGRA ident. DLOADX ident. GUARDX ident. Ident. ACCO-NET DLOADX tel. No GUARDX tel. No...
  • Page 10 Programming SATEL [select partition by number] Hardware LCD keypads Settings [select device by name – see: p. 17] Names [select device by type and address] DTM short Tmp.alw.ld.DTM Expanders Settings ABAX - INTEGRA Tamper in part. Response period High jam sens.
  • Page 11 SATEL INTEGRA User Passwd Addr. D Addr. G Port D Port G GSM band Audio Options Tel. options. Mon. TELEPHONE Mon.GPRS Mon.SMS Mon. ETHM-1 Messaging SMS messaging Modem answer. Ext.mod.answ. Voice answer. Remote control Tone dialing Groud start No dialton.tst No answer test Dbl.
  • Page 12 Programming SATEL Confirm with 1 Autoabort msg. SM -> menu Tests -> menu No AC-no blght Fast exp. bus No rest. mon. Inf. aft. tamper Arm, view viol Arm, warn.trb. Blk aft.w.code Troubl. memory Hide alarms Events limit. View clear.al.
  • Page 13 SATEL INTEGRA Type Entry delay / Alarm delay / Surveillan. time / Signal. delay / Bypass time / Expander number / Arming mode / Group / Exit time / Outputs group Max.viol.time / Max.opening t. Max.n-viol.time No viol [min] Partition Power up delay Priority / Disrm.on viol.
  • Page 14 Programming SATEL Details [select output by name] Function Cut-off time Polarization + Pulsating Latch Timers control Timers 9..16 / Timers 17..28 / Timers 33..64 Arm - no ctrl. Off-delay tmr. Zones / Timers / Expanders / Outputs / Users / Doors / Voice mess. / Tel.
  • Page 15 SATEL INTEGRA Advanced Long hsk.s1t1 Long hsk.s1t2 Long hsk.s2t1 Long hsk.s2t2 Long hsk. wait. Need ack.id.s1 Id. 6-chars s1 Source name s1 Partit.name s1 SIA evr.bl.s1A / TELIM 0ton s1A SIA evr.bl.s1B / TELIM 0ton s1B Need ack.id.s2 Id. 6-chars s2 Source name s2 Partit.name s2...
  • Page 16 Programming SATEL Key (MS) Key (GPRS) Key (ETHM) SIA-IP SIA-IP acct Coded Key (SIA-IP) KeyHEX (SIA-IP) Timestamp SIA-IP test Tel.num.for SMS SMS format Repetition cnt. Suspension time TELIM/SIA prefix Identifier n [n – identifier number] Identifier sys. Event assign. Id. assignment...
  • Page 17 SATEL INTEGRA [select telephone by number] Tel. settings [select telephone by name] Tel. number Type Rounds count Fwd.unknwn.SMS Any code Code Assignment Zone alarms Synthesizer Pager message Telephones Zone tampers Synthesizer Pager message Telephones Panic alarms Synthesizer Pager message Telephones...
  • Page 18 Programming SATEL Telephones Messages [select message] Pager types [select pager] Msg.abort in P. [select telephone by name] Msg.abort on T. [select telephone by name] Tel.answ./ctrl. Voice answer. Double call Rings count On armed part. Remote control Users (all) [select user from the list of all users] Users (t.code)
  • Page 19 SATEL INTEGRA IP/MAC ETHM-1 Modules version Restarts Clear all Clear settings Clear codes Settings<-FLASH STARTER Devices connected to the keypad bus [service code] 9 Structure Hardware LCD keypads Settings INT-KLCD / INT-KLCDR / INT-KLCDK / INT-KLCDL / INT-KLCDS / INT-KLFR / INT-KSG...
  • Page 20 Programming SATEL Show arm Control (8#) (does not apply to INT-KSG) RS communicat. Sound volume (only INT-KLCD, INT-KLCDR, INT-KLFR and INT-KSG) Reviews Zones Partitions Alarms log Troubles log Troubles Chime changing State part. Zone characters Part.characters Code+arrows Sensitivity (only INT-KLCDR with firmware version 1.06 or newer or INT-KLFR)
  • Page 21 SATEL INTEGRA Tamper in part. INT-RS / INT-RS Plus DSR control RX control Tamper in part. Devices connected to the expander bus [service code] 9 Structure Hardware Expanders Settings INT-CR / INT-IT / INT-IT-2 Partit. LED R Partit. LED G Partit.
  • Page 22 Programming SATEL BI outs ctrl. MONO outs ctr. Part.blocking Guard control Changing code Code* not dis. Code* in arm Code#->Code * (only INT-SCR) Signalling Alarm (latch) Alarm (time) Entry time Exit time Auto-arm delay Code entered Chime zones Confirmation Backlight Auto backlight No autorst.3t.
  • Page 23 SATEL INTEGRA Partition INT-ENT Master users Users 3 wrong codes BI outs ctrl. MONO outs ctr. Guard control Signalling Delay act. time Code entered Confirmation Backlight Delay act. time No autorst.3t. Partition INT-R / CA-64 SR / CA-64 DR Lock feature...
  • Page 24 Programming SATEL Auto-arm delay Chime zones No autorst.3t. Partition INT-RX / INT-RX-S / INT-VG No autorst.3t. Partition ACU-120 / ACU-270 / ACU-100 / ACU-250 No autorst.3t. Tamper in part. Response period High jam sens. New device Use ARU-100 Active mode...
  • Page 25: Entering Data By Means Of The Keypad

    Microphone n [n = microphone number (1...4)] Speaker n [n = speaker number (1...4)] Only listen AVT buttons Sound signal. Silent alarm Satel commands Wait aft.event Wait aft.disc. Runtime No autorst.3t. Tamper in part. Entering data by means of the keypad...
  • Page 26: Selection From The Single-Choice List

    Programming SATEL 2.6.1 Selection from the single-choice list The upper line of display shows the function name, and the lower one – the currently selected item. To scroll through the item list, use the  keys (down) and the  keys (up).
  • Page 27: Entering Names

    SATEL INTEGRA Characters available after next keystroke mode [ABC] mode [abc] Table 1. Characters available in the keypad when entering telephone numbers (to change the letter case, press ). Special character Function description switch-over to pulse dialing switch-over to tone dialing (DTMF)
  • Page 28: Configuring The Control Panel With Dloadx Program

    Programming SATEL Characters available after next keystroke  " & < > Table 3. Characters available when entering names. The lower case letters are available under the same keys (to change the letter case, press  key). 3. Configuring the control panel with DLOADX program Required program version: 1.15.000 (or newer).
  • Page 29 SATEL INTEGRA opens the “Options” window. opens the “Zones” window. opens the “Outputs” window. opens the “Timers” window. opens the “Reporting” window. opens the “Messaging” window. opens the “Answering and remote control” window. opens the “Service note” window. opens the “Users” window.
  • Page 30: Parameters Related To Communication Between The Control Panel And Dloadx Program

    Programming SATEL  enables/disables the COM port,  opens the connection information window (remote programming). Color of the button icon has the following meanings: green – ready to send data, alternating green and yellow – data transmission in progress, red – no communication with the control panel, gray –...
  • Page 31 SATEL INTEGRA DLOADX program settings You can configure the modem communication settings in the “Configuration” window, “Modem” tab. Description of parameters Telephone numbers Panel’s tel. no – telephone number of the control panel. PC phone number – telephone number of the modem connected to computer with DLOADX program installed.
  • Page 32: Ethernet Communication Parameters

    Programming SATEL Initializing – lines containing the modem initialization commands: for communication with built-in control panel 300 bps modem: in the first line E0V1Q0 – a command required for proper operation of the modem. You should also add the operating mode selection: B0 or B1 (selection of transmission format: V.21 or Bell103), and the commands limiting transmission rate over telephone line to 300 bps.
  • Page 33: Gprs Communication Parameters

    DLOADX program via Ethernet. ETHM-1 ID – individual identification number of the control panel for the purpose of communication via the SATEL server. ETHM-1 MAC – hardware address of Ethernet module. 3.2.4 GPRS communication parameters...
  • Page 34: Starting Local Programming "From Pins

    Programming SATEL To start the local programming function you can use the [service code] 01 key shortcut. 6. Establishing communication will be signaled on the monitor screen by a corresponding message. 3.3.2 Starting local programming “from pins” If the control panel does not support LCD keypads, does not accept the service code, etc., you can use the emergency procedure of, so-called, starting “from pins”.
  • Page 35 (built-in 300 bps modem or external analog modem). The control panel may only be remotely programmed from a specified locality. 3. Connection initialized by means of SMS (INTEGRA 128-WRL control panel or SATEL GSM module operating as an external modem).
  • Page 36  configure the GSM telephone. DLOADX program settings:  configure the modem communication parameters. If communication is to take place through the SATEL GSM module connected to the control panel, configure settings of the module (see: GSM module manual). 1. Click on the button in the DLOADX program.
  • Page 37 SATEL INTEGRA to which the control panel is to connect) – the control panel will call the telephone number sent in the SMS message (the computer telephone number programmed in control panel will be ignored), the data will be sent using CSD technology.
  • Page 38: Starting Remote Programming Via Ethernet Network

    3. Establishing connection via the SATEL server. The control panel can be programmed from any location. No public IP address is required for the control panel or the computer...
  • Page 39 4. The DLOADX program will inform you about establishing connection by means of a suitable message. Communication via the SATEL server For communication via the SATEL server, the ports of 1024-65535 range are used as outgoing ports. These ports must not be blocked.
  • Page 40: Starting Remote Gprs Programming

    Configuring the control panel If GPRS communication is to take place through the SATEL GSM module connected to the control panel RS-232 port, enable the E ISDN/GSM/ETHM and...
  • Page 41 SATEL INTEGRA – IP address of the DNS server which is to be used by the control panel (you do not need to program the DNS server address, if the address of computer with DLOADX program is entered as the IP address, not name), ...
  • Page 42: Control Panel Data File

    Programming SATEL 5. Send an SMS message to the telephone number of INTEGRA 128-WRL control panel / GSM module connected to the control panel. In the case of INTEGRA 128-WRL, the SMS message should have the following form: xxxx=gprs= (“xxxx” – the control command programmed in the control panel, initializing communication with the DLOADX program) –...
  • Page 43: Objects

    SATEL INTEGRA Objects The objects are treated as separate alarm systems. By default, one object is created in the control panel. New object can be created:  using the keypad, in the service mode, by means of the N function EW OBJECT (S...
  • Page 44: Partition Parameters

    Programming SATEL 4.2.3 Partition parameters Shown in square brackets is the parameter name as presented in the LCD keypad. The user authentication can be based on a code, proximity card (125 kHz passive transponder) or DALLAS iButton. In the description of the partition parameters only the codes are taken into account, but the information also applies to the proximity cards and DALLAS iButtons.
  • Page 45 SATEL INTEGRA dependent “AND” type of partition will be armed when all indicated partitions are armed (start of the procedure of arming the last of the indicated partitions will initiate the procedure of arming the dependent partition). The dependent “AND” type of partition will be disarmed when any of the indicated partitions is disarmed.
  • Page 46 Programming SATEL Time to re-arm – the parameter applies to the B partition type. After disarming, the ANK VAULT control panel will be analyzing for a defined period of time whether a door in the partition will be opened by means of an access control module (partition keypad, code lock, etc.). If the door is not opened, the partition will be automatically re-armed (the partition exit delay countdown will not be running).
  • Page 47: Zones

    SATEL INTEGRA  in the DLOADX program connected to the control panel, in the “Structure” window, “System” tab, after clicking on the partition name and then on the “Partition timer” button. Zones The zone is a separated portion of the protected area which can be supervised by a detector or detectors.
  • Page 48: Programming The Zones

    Programming SATEL  using the DLOADX program, in the “Structure” window, “Hardware” tab, after clicking on the given expander. For the zones in INT-KSG keypad, the value of EOL resistors is programmed in the DLOADX program, “Structure” window, “Hardware” tab. After clicking on the given keypad, select the corresponding tab.
  • Page 49 SATEL INTEGRA by partition keypad, code lock, proximity card reader expander or DALLAS chip reader expander). Arming mode – refers to the 80. A and 82. A type zones. It defines which RMING ISARM type of armed mode will be activated by the zone: 0 –...
  • Page 50: Zone Types

    Programming SATEL 8. Follow output – the zone does not support any detectors – its status depends solely on the status of selected output (physical violations and tampers of the zone are ignored). Zone sensitivity – depending on wiring type: NO, NC, EOL, 2EOL/NC, 2EOL/NO –...
  • Page 51 SATEL INTEGRA – instant zone, which is already armed during exit delay countdown. 4. P ERIMETER – instant zone. 5. I NSTANT – violation of the zone during exit delay countdown is equivalent to the partition exit. 6. E – if disarmed, the zone will signal violation acoustically in keypads and on 7.
  • Page 52 Programming SATEL 46. 24 UMP FAILURE – may be used to control the outputs. Additional options (S 47. N TORE TO O ALARM ACTION and S ) enable the zone to be used for EVENT LOG O REPORTING TORE EVENT ONLY IF ARMED other applications e.g.
  • Page 53: Zone Options

    SATEL INTEGRA – similarly as the 0. E type with an extra feature: the 85. E – NTRY NTRY CONDITIONAL zone becomes an instant one upon arming, if no partition exit is registered upon starting the arming procedure. – similarly as the 0. E , but the zone restore during exit delay 86.
  • Page 54 Programming SATEL also be bypassed when the “full + bypasses” arming mode is on (registering a partition exit is irrelevant then). The zone will be unbypassed after the partition is disarmed. Alarm in arm state – an option for the zone types 64-79. It is available, if the N O BYPASS IF option is enabled.
  • Page 55 SATEL INTEGRA Alarm on exit delay end – with this option enabled, the zone will trigger alarm if it is violated at the moment of ending the exit delay countdown. If the option is disabled, the alarm will only be triggered in case of changing the zone status from normal to violated when armed.
  • Page 56: Counters

    Programming SATEL 4.3.7 Counters The control panel makes it possible to program 16 different counters which determine the operating mode of the counter zones (zone types 16-31). The counter parameters can be programmed:  using the keypad, in the service mode, by means of the C function (Z...
  • Page 57: Outputs

    SATEL INTEGRA or  key. The output allocated Select a zone for testing from the list and press the for signaling will stop doing its present duty (if it was active, it will be disabled) until the zone test is completed (the key pressed).
  • Page 58 Programming SATEL ) – signals the loud panic alarms triggered from keypad. 6. P ANIC FROM KEYPAD ) – signals the medical assistance call alarm triggered from 7. M EDICAL ALARM FROM KEYPAD keypad. – signals the tamper alarms. 8. T AMPER ALARM Fig.
  • Page 59 SATEL INTEGRA – alarm from 5. I and 6. E type zones, if the B option has been NSTANT ELL DELAY enabled and the S has been programmed for them, IGNALING DELAY – alarms from zones, for which the R...
  • Page 60 Programming SATEL ) – indicates the loss of AC power to the modules with power 30. AC LOSS EXPANSION MODULE supply. ) – indicates the low battery of the control panel mainboard. 31. B ATTERY TROUBLE MAINBOARD ) – indicates the violations of 60. T 32.
  • Page 61 SATEL INTEGRA If a cut-off time has been programmed for a R type output, the output will EMOTE SWITCH operate similarly to the 24. MONO S type output. WITCH – indicates lack of guard tour. 80. N O GUARD TOUR –...
  • Page 62 Programming SATEL  in the keypad settings, assign the door opening function to presenting / holding the card and indicate the 101. C – type zone as the door to be ARD READ EXPANDER opened. – signals lack of communication with wireless devices 102.
  • Page 63: Options

    SATEL INTEGRA Options Pol.+ – defines the output operating mode (see Table 5). high-current output option enabled option disabled (normal polarity) (reversed polarity) +12V voltage supply +12V voltage cut-off active status +12V voltage cut-off +12V voltage supply inactive status low-current output...
  • Page 64: Clearing Alarm In Partitions

    Programming SATEL Burglary zones in partition – indicate the partition in which the output will be activated by starting the test of burglary zones. Fire/technical zones in partition – indicate the partition in which the output will be activated by starting the test of fire or technical zones.
  • Page 65: Output State Indicating

    SATEL INTEGRA The outputs of MONO , BI and S SWITCH SWITCH EMOTE SWITCH HUTTER UP HUTTER DOWN type can be grouped by the function performed by them. Each group may be given a name. The output groups can be defined: ...
  • Page 66: System Options

    Reporting - GPRS [Mon.GPRS] – with this option enabled, the control panel can send event codes using GPRS technology (the INTEGRA 128-WRL control panel or another control panel to which the SATEL GSM module is connected). This does not apply to the TELIM format.
  • Page 67: Printer Options

    SATEL INTEGRA Modem ISDN/GSM/ETHM [ISDN/GSM modem] – enable this option if the GSM, ISDN or ETHM-1 / ETHM-1 Plus module is connected as the external modem. The option is available if the E option has been enabled. XTERNAL MODEM Answering - ETHM/GSM [Ext.mod.answ.] – if this option is enabled, it is possible to initiate communication with the control panel from the outside, by means of the ETHM-1 / ETHM-1 Plus module, GSM or ISDN modem.
  • Page 68: Printout Contents

    Programming SATEL 2400 bps (off:1200 bps) – data will be sent to RS-232 port at a rate of 2400 bps (if the option is disabled - at a rate of 1200 bps). CR+LF (off: CR) – parameter determining the control mode of paper feed in the printer.
  • Page 69 SATEL INTEGRA Block keypad after 3 wrong codes [Blk aft.w.code] – with this option enabled, entering an invalid code (reading in an invalid card / DALLAS iButton) three times will block the keypad (reader) for 90 seconds. After expiry of that time, each next entry of an invalid code (read- in of an invalid card / DALLAS iButton) will block the device immediately.
  • Page 70: Arming Options

    Programming SATEL 94. E and 95. E zone types (the option cannot be NTRY XIT INTERIOR NTRY INTERIOR disabled), – the P option is enabled for the 9. 24 zone type (the option cannot be RIORITY AMPER disabled), – the A 3 and A 1 options are disabled for the 12.
  • Page 71: Times

    SATEL INTEGRA Do not arm if battery trouble [If batt. trbl.] – if this option is enabled, arming will be impossible in case of a battery failure. Do not arm if outputs trouble [If outs. trbl.] – if this option is enabled, arming will be impossible when the control panel detects that the mainboard outputs are overloaded or devices connected to these outputs are cut off.
  • Page 72: Service Options And Parameters

    Programming SATEL Do not report time server trouble [No t.serv.trbl] – with this option enabled, no trouble will be reported if there is no communication with the time server. Service options and parameters In the keypad, most of the options and parameters, as described below, are available in SM submenu.
  • Page 73: Default User's Authority Level

    SATEL INTEGRA Tries no. before trouble [PING tries] – the number of unsuccessful communication tests (the module has received no answer to the PING command sent) after which trouble will be reported. If value 0 is programmed, the communication test will be disabled.
  • Page 74: Programming The Keypads

    Programming SATEL GPRS GPRS APN – access point name for Internet GPRS connection. Username [User] – user name for Internet GPRS connection. Password [Passwd] – password for Internet GPRS connection. DNS server – IP address of DNS server to be used by the control panel. It is necessary for...
  • Page 75: Keypad

    SATEL INTEGRA Fig. 8. Example of LCD keypad settings. 8.1.1 Keypad Name – individual name of the LCD keypad (up to 16 characters). Partitions managed by keypad [Partitions] – partitions which can be armed/disarmed or alarm in which may be cancelled from the keypad. These functions are available to the users having appropriate rights and access to these partitions.
  • Page 76 Programming SATEL Show fire alarms of partitions [Fire alarms] – the keypad can signal fire alarms from selected partitions. CHIME signal of zones [Chime zones] – the keypad can audibly signal violation of selected zones. If the zone is armed, violation will not trigger the CHIME signal.
  • Page 77 SATEL INTEGRA Sign. exit delay [Exit time sig.] – with this option enabled, the keypad will audibly signal the exit delay countdown. The signaling refers to:  partitions selected when configuring the S parameter in HOW EXIT DELAY OF PARTITIONS the following keypads: INT-KLCD (v2.14 or newer) / INT-KLCDR (v2.14 or newer) /...
  • Page 78: Volume/Filter

    Programming SATEL Viol. of zone – backlight will be additionally turned on when the selected zone is violated. Entry delay in part. – backlight will be additionally turned on when starting the entry delay countdown in the selected partition. Tamper signaled in part. [Tamper in part.] – partition where alarm will be triggered in the event of keypad tamper, triggering the alarm from keypad etc.
  • Page 79: User Functions Definition

    SATEL INTEGRA 1 – zone state [Zones] – if this option is enabled, the user can inspect the zone state after pressing and holding for 3 seconds the key with number 1. 4 – partitions armed [Partitions] – if this option is enabled, the user can inspect the partition state after pressing and holding for 3 seconds the key with number 4.
  • Page 80: Proximity Cards

    Programming SATEL 8.1.5 Proximity cards Proximity card handling parameters are available for the keypads provided with proximity card readers (INT-KLCDR and INT-KLFR). Card function Card read [Card close] – you can select the function executed after presenting the card. Card holddown [Card close long] – you can select the function executed after holding the card.
  • Page 81: Parameters And Options Of Abax System

    SATEL INTEGRA 100 keyfobs. In the keypad, in the service mode, the C ABAX function is KFOBS H E C available (S ABAX ), which TRUCTURE ARDWARE XPANDERS KFOBS enables copying the keyfob related data. In the DLOADX program, to write to a new controller the data about APT-100 keyfobs already assigned to the users, click on the “Write to all”...
  • Page 82 Programming SATEL In the case of the AMD-103 magnetic contact, the presence check is performed in a different way than for the other ABAX system devices. If the value programmed for the F parameter differs from 0, the lack of presence will be reported if no ILTER transmission from the AMD-103 magnetic contact is received within one hour.
  • Page 83: Configuring The Wireless Devices - Dloadx Program

    SATEL INTEGRA AVD-100 – wireless vibration detector and magnetic contact. The following is to be programmed:  active reed switch [first zone],  sensitivity of vibration detector (registering a single vibration meeting the sensitivity criterion will cause alarm) [second zone], ...
  • Page 84: Specific Character Of The Operation Of Wireless Devices

    Programming SATEL digit – pet immunity option: 0 (disabled) or 1 (enabled). ARD-100 – enter a number from the 1 to 16 range to determine sensitivity (1 – minimum; 16 – maximum). ATD-100 – for each position taken by the detector, enter in turn: ...
  • Page 85: Wireless Sirens

    SATEL INTEGRA The mode of operation of wireless detectors depends on the status of partition to which the zone with wireless detector belongs: partition disarmed – the detector operates in passive mode. It is a battery saving mode, in which communication with the control panel takes place mainly during time intervals determined by the R parameter.
  • Page 86: Wireless Expanders Of Hardwired Zones And Outputs

    Programming SATEL The type of zones to which the wireless siren is assigned should be matched to the information sent: ASP-105 – first zone: low battery and tamper; second zone: external 12 V DC power loss and tamper. ASP-205 – both zones: low battery and tamper.
  • Page 87: Timers

    SATEL INTEGRA 9.3.4 230 V AC wireless controllers Activation of the output to which the controller is assigned will result in energizing the 230 V AC electrical circuit (if reverse polarity of the output has been programmed, the circuit will be deenergized).
  • Page 88: User Schedules

    The control panel can send event codes to the monitoring station:  over the telephone network: – via analog telephone line – INTEGRA 24, INTEGRA 32, INTEGRA 64 and INTEGRA 128 control panels, – by means of GSM voice channel – INTEGRA 128-WRL control panel (this form of transmission is not recommended), ...
  • Page 89: Reporting Parameters And Options

    SATEL INTEGRA – server address, port number, S and K (ETHM) (reporting through Ethernet TATION KEY network), – server address, port number, S and K (GPRS) (GPRS reporting), TATION KEY – telephone number of the monitoring station and SMS message format (SMS reporting), ...
  • Page 90: Selection Of The Monitoring Station

    Programming SATEL No module restart reports [No rest. mon.] – when this option is enabled and the Contact ID or SIA format is used for reporting, no event codes referring to module restarts will be sent to the monitoring station.
  • Page 91 Port – the number of port through which communication with the monitoring station will be effected. IP format – events can be sent using the SATEL or SIA-IP format (SIA DC-09 standard). The SIA-IP format can be used for transmission over Ethernet, if an ETHM-1 (firmware version 1.06 or newer) / ETHM-1 Plus module is connected to the control panel.
  • Page 92: Sia-Ip

    Programming SATEL SIA / TELIM prefix 2 characters which will precede each of the identifiers in case of the SIA and TELIM formats. Thus an identifier consisting of 6 characters can be obtained. 2 hexadecimal characters (digits or letters from A to F) can be programmed. Entering 00 means that the prefix will not be added.
  • Page 93: Sms Reporting

    SATEL INTEGRA  in specified time intervals. For each monitoring station, the number of days, hours and minutes between transmission can be individually programmed. The test transmission code will be sent: – after a predefined period of time has elapsed since the last transmission, irrespective of...
  • Page 94: Reporting Via Ethernet Network

    – reporting format in which the codes will be sent, – server address, – port number, – IP format in which the codes will be sent (SATEL or SIA-IP), – encryption key (S ) and control panel identifier for the purposes of reporting...
  • Page 95: Sms Reporting

    – reporting format in which the codes will be sent, – server address, – port number, – IP format in which the codes will be sent (SATEL or SIA-IP), – encryption key (S ) and control panel identifier for the purposes of GPRS...
  • Page 96: Messaging Parameters And Options

    Programming SATEL  PAGER type text messages defined by the installer (the SATEL GSM modules enable the PAGER messages to be converted into SMS),  SMS messages defined by the installer. only INTEGRA 128-WRL Messaging is performed independently from reporting but reporting has the priority. If in the course of messaging some events occur which must be reported to the monitoring station by the control panel, the messaging will be interrupted.
  • Page 97: Events Assignment

    For messaging using the PAGER type messages, you must define the parameters of pager identification. Default parameters of the pager type 1 are adjusted to the SATEL GSM module requirements for conversion of the PAGER type message into SMS message.
  • Page 98: Answering Phone Calls And Remote Control

    Programming SATEL – type of messaging (select 0 – voice), – number of attempts made by the control panel to notify the indicated telephone number about the event, if receipt of the message has not been acknowledged, – how the receipt of voice message is to be acknowledged (if the messaging is to be acknowledged, enable the A option or enter the 4-digit code).
  • Page 99: Users And Remote Switches

    SATEL INTEGRA Answer if all chosen partitions are armed [On armed part.] – you can indicate the partitions whose status will affect the telephone answering and control functions (they will only be executed, if all indicated partitions are armed). If the A...
  • Page 100 Programming SATEL Fig. 15. An example of SMS control settings. Accept only SMS from [Authorized tel.] – you can indicate the telephone numbers from the list programmed for telephone messaging which will be authorized to send SMS messages containing the control commands (the control commands sent from other telephone numbers will be ignored by the control panel).
  • Page 101: Control Panel Firmware Update

    16. Control panel firmware update Available on the www.satel.eu website is the current version of control panel firmware and the F X program enabling to write it to the control panel. In order to update the firmware: LASH 1.
  • Page 102: Manual Update History

    Programming SATEL 2. Start the F X program. LASH 3. Click on the button to select the file with control panel new firmware. 4. Click on the button to indicate the port to be used for communication with the control panel and start the firmware update.
  • Page 103  Section describing how to start remote programming via Ethernet has been modified (p. 36).  Information on communication via the SATEL server has been added (p. 36 and p. 37).  Section describing how to start remote programming via GPRS has been modified (p.