Summary of Contents for Rockwell Automation Allen-Bradley PanelView Plus Series

  • Page 1 PanelView Plus Terminals 2711P (400, 600, 700, 1000, 1250, 1500) User Manual...
  • Page 2 In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
  • Page 3: Table Of Contents

    Table of Contents Preface Objectives....... . . Preface-i Parts List ........Preface-i Intended Audience .
  • Page 4 Table of Contents Terminal Settings ....... 4-5 Networks and Communications ..... 4-6 Diagnostic Setup .
  • Page 5 Table of Contents Chapter 7 Transfer files and Upgrade Chapter Objectives ......7-1 Transfer Files Using a Compact Flash Card .
  • Page 6 Table of Contents Publication 2711P-UM001D-EN-P - September 2005...
  • Page 7: Objectives

    Preface Objectives This preface provides information on the contents of this manual including: • Intended audience • Parts List • Contents of manual • Additional resources • Software and firmware upgrades • European Communities (EC) Directive Compliance Parts List The PanelView Plus terminals ship with: •...
  • Page 8: Manual Contents

    Preface Manual Contents Chapter Title Description Overview Provides an overview of the terminals including features and product components. Installation Gives instructions on how to install the terminals in a panel or enclosure. Connect Power Describes how to connect power and reset the terminals.
  • Page 9: Additional Resources

    To receive software updates (software serial number required) and firmware upgrades for your terminal: Upgrades • Call your local Rockwell Automation sales office or distributor • Call Rockwell Software at 1-440-646-7800 or fax 1-440-646-7801 • Access www.software.rockwell.com Publication 2711P-UM001D-EN-P - September 2005...
  • Page 10: European Communities (Ec) Directive Compliance . Preface-Iv

    Allen-Bradley, ControlLogix, DH+, PLC-2, PLC-3, PLC-5, RSView, SLC and VersaView are registered trademarks of Rockwell Automation. CompactLogix, FlexLogix, InView, Logix, MicroLogix, PanelView, PanelView Plus, RSLogix, RSView32 and SoftLogix are trademarks of Rockwell Automation. All other trademarks are properties of their respective holders, and are hereby acknowledged. Publication 2711P-UM001D-EN-P - September 2005...
  • Page 11: Chapter 1 Chapter Objectives

    Chapter Overview Chapter Objectives This chapter gives an overview of the PanelView Plus terminals including: • Software support • PanelView Plus 400 and 600 features • PanelView Plus 700 - 1500 features • Catalog number configuration • Product components Software Support RSView Machine Edition runtime is included with all PanelView Plus terminals.
  • Page 12 Overview PanelView Plus 400 and 600 This section gives an overview of the PanelView Plus 400 and 600 terminals including: Features • Hardware features • Base configured units • Communication modules • AC or DC power supply • Displays Hardware Features The PanelView Plus 400 and 600 terminals are operator interface devices that feature: •...
  • Page 13 Overview Base Configured Units The base configured unit of the 400 and 600 terminals is available in two versions: • Base unit with RS-232 only and (1) USB port • Base unit with RS-232, 10/100BaseT Ethernet, (1) USB port and a network interface for a communication module RS-232 Only AC or DC Power Input...
  • Page 14 Overview Communication Modules You can attach a communication module with a network interface to the base configured unit of the PanelView Plus to increase your communications capability. • DH-485 • DH+ • Remote I/O (single rack) • Isolated RS-232 • DeviceNet •...
  • Page 15 Overview Displays and Input Options PanelView Plus 400 and 600 terminals are available with these display and operator input options: • 400 terminals: 3.8 inch grayscale (320 x 240) graphics display with keypad • 600 terminals: 5.5 inch color or grayscale (320 x 240) graphics display with keypad, touch screen, or keypad &...
  • Page 16 Overview Keypad or Keypad & Touch The keypad versions of the PanelView Plus 400 and 600 terminals are available with these options: • 400 terminals: grayscale display with keypad input only • 600 terminals: color or grayscale displays with either keypad or keypad &...
  • Page 17: Panelview Plus 700 - 1500 Features

    Overview PanelView Plus 700 - 1500 This section gives an overview of the PanelView Plus 700, 1000, 1250, 1500 terminals including: Features • Hardware features • Modular components • Base configured unit • Communication modules • Remote AC power supply •...
  • Page 18 Overview Modular Components The terminals use modular components allowing for flexible configuration, installation, and upgrades. Items can be ordered as separate components or factory assembled per your configuration. Communication Module Logic Module Display Module Base Configured Unit The base configured unit of the terminal consists of: •...
  • Page 19 Overview Communication Modules You can attach a communication module with a network interface to the base configured unit of the terminal to increase your communications capability. • DH+/DH-485/Remote I/O • DeviceNet • ControlNet The communication module installs easily on top of the logic module on the back of the unit.
  • Page 20 1-10 Overview Display Modules The terminals offer a range of TFT color graphic displays with either keypad, touch screen, or keypad & touch support. • 700 (6.5 inch) • 1000 (10.4 inch) • 1250 (12.1 inch) • 1250 High-Bright Touch (12.1) •...
  • Page 21 Overview 1-11 Keypad or Keypad & Touch The illustration shows the features of the 1000 keypad or keypad & touch display. All displays are similar except for size and the number of function keys available. Allen-Bradley Label IrDA Port (if present) Numeric Keypad Backspace and Enter Key...
  • Page 22: Catalog Number Configuration

    1-12 Overview Catalog Number The table lists the catalog number configuration for the terminals. Configuration Input Display Display Type Communications Power Memory Type Size Flash/RAM 2711P- K = Keypad 4 = 3.8 inch C = Color PanelView Plus 400 and 600 Terminals A = AC 1= 64 MB/64 MB T = Touch...
  • Page 23 Overview 1-13 Logic Modules (700 - 1500 only) Cat. No. Description 2711P-RP Logic Module without Flash/RAM memory 2711P-RP1 Logic Module with 64 MB Flash/64 MB RAM 2711P-RP2 Logic Module with 128 MB Flash/128 MB RAM 2711P-RP2K Conformally Coated Logic Module with 128 MB Flash/128 MB RAM 2711P-RP3 Logic Module with 256 MB Flash/256 MB RAM Communication Modules...
  • Page 24 1-14 Overview Compact Flash Cards (Blank) Cat. No. Description 2711P-RC2 128 MB Blank Compact Flash Card 2711P-RC3 256 MB Blank Compact Flash Card 2711P-RC4 512 MB Blank Compact Flash Card 2711P-RCH Compact Flash to PCMCIA Adapter Legend Kits Cat. No. Description 2711P-RFK6 Replacement Legend Strips for 600 Keypad Terminal...
  • Page 25 Overview 1-15 Replacement Bezels Cat. No. Description 2711P-RBK7 Replacement Bezel for 700 Keypad Terminal 2711P-RTK7 Replacement Bezel for 700 Touch Terminal 2711P-RBB7 Replacement Bezel for 700 Keypad or Keypad/Touch Terminal 2711P-RBK10 Replacement Bezel for 1000 Keypad Terminal 2711P-RTK10 Replacement Bezel for 1000 Touch Terminal 2711P-RBB10 Replacement Bezel for 1000 Keypad or Keypad/Touch Terminal 2711P-RBK12...
  • Page 26 1-16 Overview Protective Antiglare Overlays Description Cat. No. 2711P-RGK4 Antiglare Overlay for PanelView Plus 400 Keypad Terminal 2711P-RGK6 Antiglare Overlay for PanelView Plus 600 Keypad or Keypad/Touch Terminal 2711P-RGT6 Antiglare Overlay for PanelView Plus 600 Touch Terminal 2711P-RGK7 Antiglare Overlay for PanelView Plus 700 Keypad or Keypad/Touch Terminal 2711P-RGT7 Antiglare Overlay for PanelView Plus 700 Touch Terminal 2711P-RGK10...
  • Page 27 Overview 1-17 Cat. No. Description 2711P-RAT12S Adapts a PanelView Plus 1250 (or PV1000/1000E) Touch Terminal to a PanelView Standard 1400 Touch Cutout 2711P-RAK15 Adapts a PanelView Plus 1500 Keypad or Keypad & Touch Terminal to a PanelView 1200E/1400E Keypad Terminal 2711P-RAT15 Adapts a PanelView Plus 1500 Touch Terminal to a PanelView 1400E Touch Cutout...
  • Page 28 1-18 Overview Miscellaneous Cat. No. Description 2711P-RVT12 Solar Visor for Outdoor High-Bright 1250 Touch Screen Display Modules 2711P-RY2032 Replacement Battery for 700 - 1500 terminals 2711P-RTMC Replacement Mounting Clips for 700 - 1500 terminals 2711P-RTFC Replacement Mounting Levers for 400 and 600 terminals 2711P-RVAC Replacement AC Power Terminal Block for 400 and 600 terminals 2711-TBDC...
  • Page 29: Chapter 2 Chapter Objectives

    Chapter Installation Chapter Objectives This chapter provides instructions on how to install the terminals. It provides information on: • Hazardous locations • Environment • Enclosures • Outdoor installation (1250 High-Bright display only, cat. no. 2711P-RDT12H) • Required tools • Clearances •...
  • Page 30 Installation USB Ports The terminals contain Universal Serial Bus (USB) ports which comply with hazardous location environments. The 400 and 600 terminals have one USB port; the 700-1500 terminals have two USB ports. This section details the field wiring compliance requirements and is provided in accordance with the National Electrical Code, article 500.
  • Page 31: Environmental Considerations

    Installation Application Information Per the National Electrical Code, the circuit parameters of associated field wired apparatus for use in hazardous locations shall be coordinated with the host product such that their combination remains nonincendive. The PanelView Plus terminal and the USB peripheral device shall be treated in this manner.
  • Page 32: Outdoor Installation (Cat. No. 2711P-Rdt12H Only)

    The paint color, size, and power dissipated by the internal components of an enclosure affect the temperature rise inside the cabinet. Hoffman, a Rockwell Automation Encompass Partner, has information to assist you with enclosure selection and heating/cooling accessories to meet the temperature requirements of the installed equipment.
  • Page 33: Required Tools

    Installation Mount the terminal vertically to minimize solar loading on the display. Do not mount the terminal in a sloped enclosure if it will be exposed to direct sunlight. • Panel cutout tools Required Tools • Small, slotted screw driver for securing power and RS-232 connections •...
  • Page 34 Installation Mount the 400 or 600 Mounting levers secure the terminal to the panel. The number of levers you use (4 or 6) varies by terminal type. Terminal in a Panel • Disconnect all electrical power from the panel ATTENTION before making the panel cutout.
  • Page 35 Installation Slide each lever until flat side of lever touches the surface of the panel. Mounting Levers Mounting Slots Flat Side of Lever 7. When all levers are in place, slide each lever an additional notch or two until you hear a click. 8.
  • Page 36: Mount The 700-1500 Terminal In A Panel

    Installation Mount the 700-1500 Mounting clips secure the terminal to the panel. The number of clips you use (4, 6 or 8) varies by terminal type. Terminal in a Panel • Disconnect all electrical power from the panel ATTENTION before making the panel cutout. •...
  • Page 37 Installation 5. Slide the ends of the mounting clips into the slots on the terminal. Mounting Clip Mounting Clip Slot 6. Tighten the mounting clip screws by hand until the gasket seal contacts the mounting surface uniformly. 7. Tighten the mounting clips screws to a torque of 0.90 to 1.1 Nm (8 to 10 in-lb) using the specified sequence.
  • Page 38: Product Dimensions

    2-10 Installation Product Dimensions Product dimensions for each terminal are in mm (in). PanelView Plus 400 (6.0) 185 (7.28) (2.35) 3.54) 71 (2.81) 154 (6.08) Publication 2711P-UM001D-EN-P - September 2005...
  • Page 39 Installation 2-11 PanelView Plus 600 600 Keypad or Keypad & Touch Terminal (2.68) (6.58) (3.86) 71 (2.81) 268 (10.47) 154 (6.08) 600 Touch Terminal (2.68) (6.0) (3.86) 71 (2.81) 154 (6.08) 185 (7.28) Publication 2711P-UM001D-EN-P - September 2005...
  • Page 40 2-12 Installation PanelView Plus 700 The depth dimensions are shown for: • Base configured unit (display module and logic module) • Base configured unit with communication module 700 Keypad or Keypad & Terminal a 55 (2.18) Display to Logic Module b 83 (3.27) Display to Communication Module (7.58) (11.40)
  • Page 41 Installation 2-13 PanelView Plus 1000 The depth dimensions are shown for: • Base configured unit (display module and logic module) • Base configured unit with communication module 1000 Keypad or Keypad & Touch Terminal a 55 (2.18) Display to Logic Module b 83 (3.27) Display to Communication Module (9.77) (15.72)
  • Page 42 2-14 Installation PanelView Plus 1250 The depth dimensions are shown for: • Base configured unit (display module and logic module) • Base configured unit with communication module 1250 Keypad or Keypad & Touch Terminal a 55 (2.18) Display to Logic Module b 83 (3.27) Display to Communication Module (11.12) (16.36)
  • Page 43 Installation 2-15 PanelView Plus 1500 The depth dimensions are shown for: • Base configured unit (display module and logic module) • Base configured unit with communication module 1500 Keypad or Keypad & Touch Terminal a 65 (2.55) Display to Logic Module (12.97) b 93 (3.65) Display to Communication Module (18.46)
  • Page 44 2-16 Installation Publication 2711P-UM001D-EN-P - September 2005...
  • Page 45: Chapter 3 Chapter Objectives

    Chapter Connect Power Chapter Objectives This chapter covers wiring and safety guidelines, and provides information on how to: • Remove and install the power terminal block • Connect DC power • Connect AC power • Reset the terminal • Startup sequence Wiring and Safety Use publication NFPA 70E, ‘Electrical Safety Requirements for Employee Workplaces’, IEC 60364 ‘Electrical Installations in Buildings’...
  • Page 46: Remove And Install The Power Terminal Block

    Connect Power Remove and Install the You can remove and reinstall the power terminal block for ease of installation, wiring, and maintenance. The terminals ship with the Power Terminal Block power block installed. Explosion Hazard WARNING • Substitution of components may impair suitability for hazardous locations.
  • Page 47 Connect Power Remove and Install the Terminal Block for 400 and 600 Terminals AC and DC terminal blocks are keyed and marked ATTENTION differently so be sure to follow markings. Do not force terminal blocks into connectors to prevent potential damage to terminal. To remove terminal block: 1.
  • Page 48: Dc Power Connections

    Connect Power DC Power Connections Terminals that operate on 24V dc power are EN 61131-2 Equipment Class II devices. These terminals have an integrated, non-isolated, 24V dc power supply. The table lists the electrical input ratings. Power Type Terminal Input Range 400 and 600 24V dc nom (18…30 V dc) 25 W max (1.0 A at 24V dc)
  • Page 49 Connect Power Functional Earth Connection DC powered terminals have a Functional Earth (FE) terminal which you must connect to a low impedance earth ground. This connection is required for Electromagnetic Compliance (EMC) with the European Union (EU) EMC directive for CE-mark conformance. •...
  • Page 50 Connect Power Connect DC Power Explosion Hazard - Do not connect or disconnect WARNING equipment while circuit is live unless area is known to be non-hazardous. Disconnect all power before installing or replacing components. Failure to disconnect power may result in electrical shock and/or damage to the terminal.
  • Page 51: Ac Power Connections

    Connect Power AC Power Connections The 400 and 600 terminals that operate on AC power are EN 61131-2 Equipment Class I devices. These terminals have an integrated AC power supply with these ratings: • 85 to 264V ac (47 to 63 Hz) •...
  • Page 52 Connect Power Connect AC power Explosion Hazard - Do not connect or disconnect WARNING equipment while circuit is live unless area is known to be non-hazardous. Disconnect all power before installing or replacing components. Failure to disconnect power may result in electrical shock and/or damage to the terminal.
  • Page 53: Reset The Terminal

    Connect Power Reset the Terminal Reset the 400 and 600 Terminals The 400 and 600 terminals have a Reset switch on the side of the terminal. Use the Reset switch to restart the terminal without having to disconnect and reapply power. When reset, the terminal performs a series of startup tests and runs RSView ME.
  • Page 54 3-10 Connect Power Reset the 700-1500 Terminals The 700-1500 terminals have a Reset switch and a Default switch on the side of the logic module. Default Reset Reset Use the Reset switch to restart the terminal without having to disconnect and reapply power. Insert a thin, nonconductive probe into the hole marked Reset and press the switch.
  • Page 55: Startup Sequence

    Connect Power 3-11 Startup Sequence After a reset, the terminal performs a series of startup tests and then either: • runs the .MER application currently loaded in the terminal • enters configuration mode The action that occurs depends on what startup options are configured for your terminal.
  • Page 56 3-12 Connect Power Publication 2711P-UM001D-EN-P - September 2005...
  • Page 57: Chapter 4 Chapter Objectives

    Chapter Configuration Mode Chapter Objectives This chapter shows how to use the configuration screens of your PanelView Plus terminal to: • Perform data entry and navigation • Load an ME application • Run an ME application • Modify application settings •...
  • Page 58 Configuration Mode Main Screen Button Description Load Application (F1) Opens another screen where you can select an application to load. Once loaded, the application name will appear under Current Application. Run Application (F2) Runs the .MER application displayed under Current Application. An application must be loaded before you can run it.
  • Page 59 Configuration Mode Input Panel Many screens have buttons that access fields where you must enter/edit data. When you press the button or function key, the Input Panel opens ready for you to input data. If the field is restricted to a numeric value, only the 0-9 keys will be enabled.
  • Page 60: Load An Me Application

    Configuration Mode Load an ME Application To load an RSView ME .MER application, select the Load Application button on the main screen. List of .mer applications stored in the compact Moves flash of the terminal. highlight up Moves highlight down 1.
  • Page 61: Run An Application

    Configuration Mode Run an Application To run the currently loaded application, select the Run Application button on the main Configuration Mode screen. An application must be loaded, before you can run it. Log files generated by the application may be deleted if this option was selected on the main screen or enabled as a Startup Option under Terminal Settings.
  • Page 62: Networks And Communications

    Configuration Mode Terminal Setting Description Startup Options Specifies whether the terminal starts up in configure or run mode. Also lets you enable/disable tests to run on the terminal at startup. System Event Log Displays a list of system events currently logged by the terminal.
  • Page 63 Configuration Mode RSLinx Enterprise Communications Terminal Settings Networks and Communications The RSLinx Enterprise Communications screen shows a treeview of installed communication cards and network configurations. You can: RSLinx Enterprise Communications • edit or view the driver settings for the communication protocol used by your .MER application.
  • Page 64 Configuration Mode To edit communication settings: 1. From the RSLinx Configuration Screen, select the communication card installed on your terminal. 2. Select the Driver Settings button. A properties screen opens showing the current communication settings for the driver. 3. To modify a setting, select the setting and then the Edit button. The Input Panel opens showing the current setting.
  • Page 65 Configuration Mode DHPlus Properties The DHPlus Properties screen lets you view or modify settings for a terminal connected to a DHPlus network. Field Description Valid Values Identifies the communication card if multiple 0 - 3 Jumper ID cards are installed on terminal. Station Number The unique address of the terminal on the 0 - 77 (octal)
  • Page 66 4-10 Configuration Mode ControlNet Properties The ControlNet Properties screen configures communication settings for the terminal on a ControlNet network. Field Description Valid Values Device ID Unique address of the terminal on the 1 - 99 ControlNet network. DeviceNet Properties The DeviceNet Properties screen configures communication settings for the terminal on a ControlNet network.
  • Page 67 Configuration Mode 4-11 Field Description Valid Values Baud Rate Data rate at which serial driver 110, 300, 600, 1200, 4800 communicates. The baud rate is 9600, 19200, 38400, 115200 automatically configured if Use Auto Config is set to Yes. Use Auto Config Automatically or manually configures the Yes (auto configure) baud rate, parity and error checking...
  • Page 68 4-12 Configuration Mode Network Connections Terminal Settings Networks and Communications The Network Connections screen lets you configure these items for the terminal: Network Connections • Device Name • Network Adapters • Network Identification Device Name Terminal Settings Networks and Communications The Device Name screen identifies the terminal to other computers on the network.
  • Page 69 Configuration Mode 4-13 Network Adapters Terminal Settings Networks and Communications The Network Adapters screen configures driver settings for all network adapters installed on the terminal. The only network adapter Network Connections on the terminal is the (IntelR) Fast Ethernet Controller. Network Adapters Press the Name Servers button and/or IP Address button to access driver settings.
  • Page 70 4-14 Configuration Mode IP Address The IP Address screen identifies the IP address of the selected network adapter. If the network the terminal is connected to does not automatically assign an IP address, you can assign the address in this screen.
  • Page 71 Configuration Mode 4-15 Network Identification Terminal Settings Networks and Communications The Network Identification screen configures settings that enable the terminal to gain access to network resources. You can enter a user Network Connections name, password and domain (provided by your network administrator).
  • Page 72: Diagnostic Setup

    4-16 Configuration Mode Diagnostic Setup The Diagnostic Setup screen configures diagnostics for the current computer. The screen shows a treeview of possible diagnostic nodes. Terminal Settings To access the Remote Log Setup or Message Diagnostic Setup Routing, select the node and then the Edit button.
  • Page 73: File Management

    Configuration Mode 4-17 File Management The File Management screen lets you access screens to: • Delete Files • Copy Files Delete Files Terminal Settings From the Delete Files screen you can select options to: File Management • Delete Applications - deletes an .MER application file from a Delete Files storage location.
  • Page 74 4-18 Configuration Mode Delete Log Files Select this option to delete any data log files, alarm history files and alarm status files in the System Default location on the terminal. You will be asked to confirm the operation. Do you want to delete all of the RSView ME Station Log Files? Select Yes or No.
  • Page 75 Configuration Mode 4-19 2. Select the Destination button on the same screen to open the this screen. 3. Select the Destination button to select the storage location where you want to copy the application or font file to. • Internal Storage - the Internal Compact Flash in the terminal •...
  • Page 76: Display

    4-20 Configuration Mode Display The Display screen lets you open screens to access: • Display Contrast • Display Intensity • Display Temperature • Screen Saver • Cursor Display Contrast Terminal Settings The Display Contrast screen lets you view and modify the current Display contrast setting of the PanelView Plus 400 and 600 grayscale displays.
  • Page 77 Configuration Mode 4-21 Display Temperature Terminal Settings Display The Display Temperature screen shows the current temperature of the display. Display Temperature The 600 -1500 terminals have a CCFL (Cold-Cathode Fluorescent Lamp) backlight. This backlight requires temperature control when the internal temperature of the product is below 10 °C or above 60 °C. For proper backlight operation, the terminal monitors low and high temperature conditions.
  • Page 78 4-22 Configuration Mode Screen Saver Terminal Settings The Screen Saver screen lets you: Display • disable the screen saver. Screen Saver • enable the screen saver after the selected idle time. • adjust the brightness intensity of the screen saver. •...
  • Page 79: Font Linking

    Configuration Mode 4-23 Cursor Terminal Settings Display The Cursor screen enables/disables the on-screen cursor. Cursor Font Linking Font linking allows you to run a translated application on the terminal by linking a font file to the base font (for example, linking a Chinese Terminal Settings font file to the base font Arial).
  • Page 80: Input Devices

    4-24 Configuration Mode Input Devices The Input Devices screen lets you access screens to view and modify settings for the: • Keyboard • Keypad • Mouse • Touch Screen Keyboard and Keypad Setup The Keyboard and Keypad screen opens these screens: •...
  • Page 81 Configuration Mode 4-25 Key Settings for Terminal Keypad The Keypad Settings screen enables/disables Single Key Mode option which is used to restrict multiple or simultaneous key presses. Field Description Valid Values Single Key Mode Enables or disables Single Key Mode. Enabled Enabled with Abort If enabled, any programmable key that is...
  • Page 82 4-26 Configuration Mode Touch Screen Terminal Settings Input Devices The Touch Screen lets you access these screens: • Calibration Touch Screen • Cursor • Double-Tap Sensitivity Touch Screen Calibration Use a plastic stylus device with a minimum tip radius IMPORTANT of 1 mm (0.040 in) to prevent damage to the touch screen.
  • Page 83 Configuration Mode 4-27 Double-Tap Sensitivity This screen lets you set and test the sensitivity for both speed and physical distance between touch screen presses. • The Set button sets the sensitivity of touch screen presses. • The Test button tests the sensitivity of touch screen presses. If you double-tap the test button with the time set using the Set button, the Test button will reverse it’s foreground and background colors.
  • Page 84: Print Setup

    4-28 Configuration Mode Print Setup The Print Setup screen lets you access screens to configure print options for: • Displays • Alarms • Diagnostic messages Display, Alarm, and Diagnostic Print Setup Terminal Settings Print Setup The general setup for printing displays, alarm messages and diagnostics messages from an RSView .MER application is the same.
  • Page 85 Configuration Mode 4-29 Advanced Settings for Diagnostic Messages and Alarm Messages This screen configures when to print diagnostic or alarm messages that are sent to the Network or USB port. To configure how messages are queued for printing, select the Print Messages After button and set one of these options.
  • Page 86: Startup Options

    4-30 Configuration Mode Startup Options The Startup Options screen accesses these screens to modify: • RSView ME Station Startup • Startup Tests Terminal Settings RSView ME Station Startup Startup Options The RSView Machine Station Startup screen specifies what action the terminal takes on startup.
  • Page 87 Configuration Mode 4-31 Configuration Mode The Configuration Mode Options screen specifies whether the terminal will boot up in Configure Mode: • with the current application loaded. • with the communication configuration of the current application or the terminal’s RSLinx communication configuration. If you select Yes to replace the terminal’s communication configuration with that of the application, any changes made to the device addresses or driver properties in the RSLinx...
  • Page 88 4-32 Configuration Mode Startup Tests Terminal Settings Startup Options The terminal can run extended tests on startup. The Startup Tests screen provides access to these screens: Startup Tests • Startup Tests Settings • Repeat Count Startup Tests apply only to PanelView Plus 700 - IMPORTANT 1500 terminals.
  • Page 89 Configuration Mode 4-33 Startup Tests Settings From the Startup Tests Settings screen, you can: • enable extended diagnostics to run on the terminal at startup. • disable extended diagnostics at startup. • specify how many times to repeat the selected tests that are run on the terminal during startup.
  • Page 90: System Event Log

    4-34 Configuration Mode System Event Log The System Event Log screen displays a list of system events currently logged by the terminal. Terminal Settings System Event Log • To display System Event Log Details for a specific event, select an event and then select the More Details button. •...
  • Page 91: System Information

    Configuration Mode 4-35 System Information The System Information screen lets you access: • RSView ME Station information • Terminal Information Terminal Information Terminal Settings The Terminal Information screen displays these details for the System Information terminal: • Total power on time Terminal Information •...
  • Page 92 4-36 Configuration Mode Memory Allocation The Memory Allocation screen displays the: • amount of allocated storage or program memory. • amount of storage or program memory currently in use. You can modify the allocation of storage or program memory. Press the Up or Down button to increase/decrease the memory allocation.
  • Page 93 Configuration Mode 4-37 RSView ME Station Information Terminal Settings System Information The About RSView ME Station screen provides access to: • RSView ME Station firmware number About RSView ME Station • Rockwell Technical Support information x.xx.xx.xx Publication 2711P-UM001D-EN-P - September 2005...
  • Page 94: Time/Date/Regional Settings

    4-38 Configuration Mode Time/Date/Regional The Time/Date/Regional Settings screen lets you access these screens to set: Settings • Date • Regional settings • Time • Time zone Date Terminal Settings Time/Date/Regional Settings The Date screen shows and configures the current date in separate Year, Month and Day fields.
  • Page 95 Configuration Mode 4-39 Time Terminal Settings Time/Date/Regional Settings The Time screen shows and configures the current time in 24-hour format in separate Hour, Minute and Second fields. Time Field Description Valid Values Hour The current hour in 24-hour format. 0 - 23 Minute The current minute in 24-hour format.
  • Page 96 4-40 Configuration Mode Time Zone Terminal Settings Time/Date/Regional Settings The Time Zone screen shows the current time zone that is installed on the terminal. Time zones are installed as a part of the operating Time Zone system. Changing the time zone adjusts the current time and date to match the new time zone.
  • Page 97 Configuration Mode 4-41 Regional Settings Terminal Settings The Regional Settings screen allows you to access these screens: Time/Date/Regional Settings • Language Regional Settings • Numeric Format • Long Date Format • Short Date Format • Time Format The current language is shown at the bottom of the Regional Settings screen.
  • Page 98 4-42 Configuration Mode Time Format Terminal Settings The Time Format screen configures the time format for the current Time/Date/Regional Settings language. A sample of the current time is shown using the currently selected format. Regional Settings Time Format Field Description Example h:mm:ss tt (default) 7:23:02 AM or 1:13:31 PM...
  • Page 99 Configuration Mode 4-43 Short Date Format Terminal Settings The Short Date Format screen configures the short date format used Time/Date/Regional Settings by the current language. A sample of the current date is shown using Regional Settings the currently selected short date format. Short Date Format Field Short Date Formats...
  • Page 100 4-44 Configuration Mode Long Date Format Terminal Settings The Long Date Format screen configures the long date format used by Time/Date/Regional Settings the current language. A sample of the current date is shown using the Regional Settings currently selected long date format. Long Date Format Field Short Date Formats...
  • Page 101: Install And Replace Components

    Chapter Install and Replace Components Chapter Objectives This chapter shows how to install, replace or upgrade various components of the PanelView Plus terminals. • Logic module • RAM and internal compact flash • Communication module • Display module • Battery •...
  • Page 102: Compatibility Of Terminal Components

    Install and Replace Components Compatibility of Terminal When assembling components of a terminal or replacing the internal compact flash in a logic module, the components must be compatible. Components To verify compatibility of the internal compact flash with the logic 700 - 1500 Terminals Only module, you must know what version of RSView ME is running on the terminal.
  • Page 103: Install Ram Or Internal Compact Flash

    Install and Replace Components Install RAM or The logic module is available with or without RAM/internal compact flash installed. If RAM and internal compact flash are ordered as Internal Compact Flash separate components, you must install the memory before attaching the logic module to the display module.
  • Page 104: Install Or Replace The Logic Module

    Install and Replace Components Install or Replace This section shows how to install and replace the logic module. If the display module and logic module are ordered as separate the Logic Module components, attach the logic module to the display module before panel installation.
  • Page 105 Install and Replace Components To replace the logic module: Before replacing the logic module, you must remove the communication module, if attached. You will also need to remove the Internal RAM and compact flash from the logic module to reuse in the new logic module.
  • Page 106: Install Or Replace A Communication Module

    Install and Replace Components Install or Replace a This section shows how to install and replace a communication module. The communication module installs over the logic module. Communication Module The communication modules are available as separate catalog numbers for specific communication protocols. The installation is the same for all modules regardless of the communication type.
  • Page 107 Install and Replace Components To prevent ESD between the modules, allow the communication module to touch the logic module before making connection. Communication Module Connector Logic Module 5. Push down on the communication module until the connectors are firmly seated. 6.
  • Page 108 Install and Replace Components Install or Replace Communication Module on 400/600 Terminals To install a communication module: 1. Disconnect power from the terminal. 2. Set the terminal, display side down, on a clean, flat, stable surface. 3. Remove the label covering the connectors on the base unit of the terminal.
  • Page 109 Install and Replace Components To replace a Communication module: 1. Disconnect power from the terminal. 2. Disconnect the communication cables from the module. 3. Loosen the three screws that secure the communication module to the terminal. 4. Carefully lift the communication module away from the terminal and set aside.
  • Page 110: Replace The Display Module

    5-10 Install and Replace Components Replace the Display This section shows how to replace the display module. It is necessary to remove the communication module from the logic module to Module perform this operation. 700 - 1500 Terminals Only Communication Module Logic Module Display Module...
  • Page 111 Install and Replace Components 5-11 7. Position the new logic module over the new display module so that the connectors align. 8. Push down on the logic module until firmly seated. 9. Tighten the six captive screws that secure the logic module to the display module to a torque of 0.68 Nm 6 to 8 in-lb).
  • Page 112: Replace The Battery

    5-12 Install and Replace Components Replace the Battery A lithium battery is used by the real-time clock and static RAM; it is not used for application backup or retention. The clock module has a 700 - 1500 Terminals Only life expectancy of two years without power. When you connect or disconnect the battery an WARNING electrical arc can occur.
  • Page 113 Install and Replace Components 5-13 5. Carefully lift the logic module away from the terminal and flip over to expose the circuit board. Wear a properly grounded ESD wristband ATTENTION before touching any of the electronic components in the logic module. 6.
  • Page 114: Replace The Bezel

    5-14 Install and Replace Components Replace the Bezel Remove the Display Module Bezel It is not necessary to remove the logic module or communication 700 - 1500 Terminals Only module before removing the bezel, except for the PanelView Plus 700. 1.
  • Page 115 Install and Replace Components 5-15 7. Lift the back of the display module away from the bezel. Work on a clean, flat, stable surface to protect the display from debris, scratches and damage. Display Module Bezel 8. Detach all connectors (maximum of three). The number of connectors varies by model.
  • Page 116: Replace The Backlight

    5-16 Install and Replace Components Replace the Backlight This section shows how to replace the backlight for the 700, 1000, 1250, and 1500 terminals. The 1250 High-Bright terminals do not have a replaceable backlight. 700 - 1500 Terminals Only 1. Disconnect power from the terminal. 2.
  • Page 117 Install and Replace Components 5-17 For PanelView Plus 700 and 1000 Work on a clean, flat, stable surface to protect the display from debris, scratches and damage. 6. Press the retaining tab that secures the backlight and then pull out the backlight. Backlight Retaining Tab 7.
  • Page 118 5-18 Install and Replace Components For PanelView Plus 1250 and 1500 • The 1250 Series A and B displays have two backlights and use cat. no. 2711P-RL12C backlight replacement. • The 1250 Series C displays have only one backlight and use cat.
  • Page 119: Install The Remote Ac Power Supply

    Install and Replace Components 5-19 10. Reattach the LCD display connector to the circuit board. 11. Reattach the backlight connector to the circuit board. 12. Secure the LCD display by attaching the four screws and tighten to the specified torque. Screw Size Torque 0.68 Nm (6 to 8 in-lb) 13.
  • Page 120: Replace The Keypad Legend Inserts

    5-20 Install and Replace Components Replace the Keypad Legend This section shows how to replace the legend inserts in the keypad terminals. The legend strips are available as separate catalog numbers Inserts for each keypad terminal, except for the PanelView Plus 400 terminals which does not support replaceable legend strips.
  • Page 121: Use An External Compact Flash Card

    Install and Replace Components 5-21 Replace the Keypad Legend Inserts on the 700-1500 Terminals The F1-Fxx and K1-Kxx legend inserts on the PanelView Plus 700 - 1500 terminals are accessible when the display module bezel is removed. To replace the F1-Fxx or K1-Kxx function key legends: 1.
  • Page 122 5-22 Install and Replace Components Insert a Compact Flash Card 1. Insert the card in the compact flash card slot of the terminal until firmly seated. 400 and 600 Terminals 700 - 1500 Terminals Remove a Compact Flash Card 1. Press the Eject button on the logic module. When the button pops out, press it again to release the card.
  • Page 123: Terminal Connections

    Chapter Terminal Connections Chapter Objectives This chapter provides network and device connections for the terminals, including: • Wiring and safety guidelines • Logic controller cable charts • Communication port isolation • USB ports • Serial connections on base unit • Ethernet (onboard communications) •...
  • Page 124: Logic Controller Cable Charts

    Terminal Connections Logic Controller Cable The charts provide a summary of terminal connections to controllers and network interface modules. Charts Runtime Communication Cables - To Controllers Cables: PanelView Plus to SLC Controllers SLC-500, 5/01, 5/02 SLC-5/03, 5/04, 5/05 SLC 5/03 SLC 5/04 SLC 5/05 Protocol...
  • Page 125 Terminal Connections Cables: PanelView Plus to PLC-5 and MicroLogix Controllers MicroLogix 1000, 1200, PLC-5, PLC-5C, PLC-5E MicroLogix 1500LRP 1500LSP Protocol PanelView Plus Comm Port CH0 (25-pin RS-232) CH1 (9-pin RS-232) CH0 (8-pin Mini DIN) (DF1) (DF1 or DH-485) (DF1 or DH-485) RS-232 (DF1) Comm Port (9-pin) 2711-NC13 (16ft/5m) 2711-NC21 (16ft/5m)
  • Page 126 Terminal Connections Cables: PanelView Plus to Communication Adapters 1761-NET-AIC 1747-AIC Port 2 Port 3 1761-NETDNI Protocol PanelView Plus Comm Port Port 1 (9-pin) 8-pin Mini DIN() (DH485) or 1771-NET-ENI DF1 (any) RS-232 Comm Port (9-pin) 2711-NC13 (16ft/5m) 2711-NC21 (16ft/5m) 1761-CBL-AP00 (5m) PanelView Plus 400 -1500 2711-NC14 (32ft/10m) 2711-NC22 (49ft/15m)
  • Page 127: Communication Port Isolation

    Terminal Connections Communication Port The terminals contain integral and modular (externally attached) communication ports. These ports may contain electrical isolation Isolation depending on the catalog number of the terminal or communication module. Integral Communication Port Isolation Communication Port 400 and 600 Terminal 700-1500 Terminal RS-232 Non-isolated...
  • Page 128: Usb Ports

    Terminal Connections USB Ports The 700 - 1500 terminals have two USB ports. The 400 and 600 terminals have one USB port. The terminals support standard USB keyboard and mouse devices (HID devices) with native device drivers. They also support some USB printers that have Printer Control Language (PCL) capabilities.
  • Page 129: Serial Connections

    Terminal Connections Serial Connections The base configured unit of all terminals has a multi-purpose serial RS-232 port that supports: • DH-485 communications through a serial connection • DF1 full duplex communications with controllers using direct connections or modem connections • Third party point-to-point communications •...
  • Page 130 Terminal Connections Modem Connection Wire or radio modem communications is possible between the terminal and controller. Each modem must support full duplex communications. Refer to your modem user manual for details on settings and configuration. PanelView Plus Optical Isolator Controller DF1 Port Modem Modem...
  • Page 131 Terminal Connections Computer Connections The RS-232 serial port on the base configured unit of the terminals supports: • Application uploads/downloads using a direct connection or • Printing Base Configured Unit of PanelView Plus Computer Available Cables Cat. No. 2711-NC13, 5 m (16.4 ft) Cat.
  • Page 132: Ethernet Connections

    6-10 Terminal Connections Ethernet Connections The base configured unit of the 700 - 1500 terminals and the network based unit of the 400 and 600 terminals have an Ethernet port that supports: • EtherNet/IP communications • Third party Ethernet communications •...
  • Page 133 Terminal Connections 6-11 Cables Category 5 shielded and unshielded twisted-pair cables with RJ45 connectors are supported. If 100 Mbit/second data rates are used, we recommend that you use a shielded cable. The shielded cable will help insure that industrial noise immunity levels are maintained. The maximum cable length between the terminal’s Ethernet port and a 10/100Base-T port on an Ethernet hub (without repeaters or fiber) is 100 meters (328 feet).
  • Page 134: Dh-485/Dh+/Remote I/O Module

    6-12 Terminal Connections DH-485/DH+/Remote I/O Terminals with a DH-485/DH+/Remote I/O communication module support communication with these networks: Module • DH+ networks • DH-485 networks • Remote I/O networks You can communicate with only one network at one time. The 700-1500 terminals support all protocols on one module. The 400 and 600 terminals require a separate module for each protocol.
  • Page 135 Terminal Connections 6-13 DH+ Status Indicator Condition Indication Channel is not online blinking green Device is only node on the network. solid green Device is online and receiving token. blinking red Duplicate node solid red Failed selftest DH-485 Status Indicator Condition Indication Channel is not online...
  • Page 136 6-14 Terminal Connections DH-485 Network Port Wiring (700 - 1500 only) Use these instructions for wiring Belden cable. If you are using standard Allen-Bradley cables, see the Logic Controller Cable Charts. Attaching RS-485 Connector to the Communication Cable A daisy-chained network is recommended. We do IMPORTANT not recommend hybrid star/daisy chain networks as shown.
  • Page 137 Terminal Connections 6-15 DH-485 Connections (400 and 600 only) This section shows connections between a 400 and 600 terminal with a DH-485 communication module and an SLC or ControlLogix controller through the AIC+ module. PanelView Plus 400 or 600 AIC + with DH-485 Module 1784-CP14 Cable 1761-CBL-PM002 Cable...
  • Page 138 6-16 Terminal Connections DH+ Network Connections Use the Belden 9463 twin axial or equivalent cable (cat. no. 1770-CD), to connect a terminal to a DH+ link. You can connect a DH+ link in two ways: • trunk line/drop line - from the drop line to the connector screw terminals on the DH+ connectors of the processor •...
  • Page 139 Terminal Connections 6-17 Remote I/O Connections Use the Belden 9463 twin axial or equivalent cable (cat. no. 1770-CD), to connect a terminal to a Remote I/O scanner. The maximum cable length (link distance) is determined by the baud rate. • 2,800 m (10,000 ft) for 57.6K baud •...
  • Page 140: Controlnet Module

    • ControlNet System Planning and Installation Manual (1786-6.2.1) • ControlNet Cable System Component List (AG-2.2) • ControlNet Communications for PanelView Plus and VersaView CE Terminals (2711P-UM003) The Rockwell Automation website www.rockwellautomation.com provides information and product descriptions of ControlNet products. Under the Products and Services heading, select Communications.
  • Page 141 Terminal Connections 6-19 Minimum Requirements The following software and firmware must be installed on the development computer and the PanelView Plus terminal to configure and communicate with an Allen-Bradley controller on a ControlNet network. ControlNet Unscheduled Communications Software/Firmware PanelView Plus 700-1500 PanelView Plus 400 or 600 RSView Studio v3.10 or later...
  • Page 142 6-20 Terminal Connections ControlNet Connections 2711P-RN15C ControlNet Module for 400 and 600 Terminals Pin NAP Signal Signal Common No Connection Channel B TX_H TX_L Redundant BNC RX_L Cable Connectors RX_H Channel A No Connection Signal Common LED B Shell Earth Ground Network Access Port (NAP) LED A RJ-45 connector for temporarily connecting programming...
  • Page 143 Terminal Connections 6-21 NAP and Redundant Cables Refer to the ControlNet Cable System Planning and Installation manual (Publication 1786-6.2.1) for descriptions of ControlNet components. For information on purchasing these items, refer to the Allen-Bradley ControlNet Cable System Component List (Publication AG-2.2). Item Catalog Number RG-6 quad-shield...
  • Page 144: Devicenet Module

    • DeviceNet Selection Guide (Publication DNET-SG001) • DeviceNet Media Design Installation Guide (DNET-UM072) • DeviceNet Tips & Tricks (DNET-BR003) The Rockwell Automation website www.rockwellautomation.com provides information and product descriptions of DeviceNet products. Under the Products and Services heading, select Communications.
  • Page 145 Terminal Connections 6-23 Minimum Requirements Software/Firmware PanelView Plus 700-1500 PanelView Plus 400 and 600 RSView Studio v4.0 or later v4.0 or later RSView Machine Edition Runtime v4.0 or later v4.0 or later DeviceNet Module 2711P-RN10H 2711P-RN10C DeviceNet Connections 2711P-RN10C DeviceNet Module for 400 and 600 Terminals I/O Status Indicator MOD Status Indicator NET Status...
  • Page 146 6-24 Terminal Connections Do not connect or disconnect any communication WARNING cable with power applied to this device or any device on the network. An electrical arc could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
  • Page 147 Terminal Connections 6-25 DeviceNet Module (MOD) Status Indicator This bi-color (green/red) LED provides device status. It indicates whether or not the device has power and is operating properly. Condition Status Indication no power No power applied to device. green device operational Device is operating in a normal condition.
  • Page 148 6-26 Terminal Connections DeviceNet Network (NET) Status Indicator This bi-color (green/red) LED indicates the status of the communication link. Condition Status Indication not powered Device is not online. not online The device has not completed the Dup_MAC_ID test yet. The device may not be powered; look at the Module Status LED.
  • Page 149 Chapter Transfer files and Upgrade Firmware Chapter Objectives This chapter covers information on how to: • transfer applications using a compact flash card or from a computer. • upgrade terminal firmware Transfer Files Using a The PanelView Plus terminal allows you to copy or load files using a compact flash card from RSView ME.
  • Page 150 Transfer files and Upgrade Firmware Upgrade Firmware using a Compact Flash Card This section shows how to upgrade the firmware in a terminal using a compact flash card. This is a two step-process. First, you create a firmware upgrade card with the necessary firmware files. Second, you load this card in the target terminal to upgrade the firmware.
  • Page 151 Transfer files and Upgrade Firmware 3. From the Firmware source folder list, select the location of the firmware files. The default location is C:\Program Files\Rockwell Software\RSView Enterprise\FUPs. From the Upgrade firmware version list, select the version of the firmware you want to upgrade to, then press Next. 4.
  • Page 152 Transfer files and Upgrade Firmware 5. Select Finish to copy the firmware source files to the location specified in step 2. If the files were created in a separate folder on a local hard drive, copy the files to the root directory of the compact flash card.
  • Page 153 Transfer files and Upgrade Firmware 3. If other terminals exist on the same Ethernet network, the following error may display: "Error registering name on network (may be duplicate). Change in system Control Panel and try again." Ignore this error. It will be corrected during the upgrade. Press OK to acknowledge error and wait for terminal to reset.
  • Page 154 Transfer files and Upgrade Firmware Upgrade Firmware using a Network (Ethernet) Connection You can upgrade the firmware in a terminal that is connected to a desktop computer using a Serial, Ethernet or Network (using RSLinx Enterprise) connection. • Serial connection requires a RAS connection to be set up on computer.
  • Page 155 Transfer files and Upgrade Firmware 2. Select Upgrade firmware on terminal and press OK. 3. Select Network connection and press Next. Use the Ethernet and Serial connections only if the firmware upgrade is unsuccessful. 4. Locate the terminal on your Ethernet network via its IP address. Skip to Step 6 if you found the terminal.
  • Page 156 Transfer files and Upgrade Firmware 5. Double-click on EthernetIP Devices. Select the appropriate terminal and press OK. 6. Enter the IP address for the terminal and press OK. 7. Select the terminal to be upgraded and press OK. Publication 2711P-UM001D-EN-P - September 2005...
  • Page 157 Transfer files and Upgrade Firmware 8. From the Firmware source folder text box, select the location of the firmware files. The default location is C:\Program Files\Rockwell Software\RSView Enterprise\FUPs. From the Upgrade firmware version list, select the version of the firmware you want to upgrade to, then select Next. PanelView Plus 700 9.
  • Page 158 7-10 Transfer files and Upgrade Firmware 10. Press Finish to start the upgrade. 11. Press Yes to continue the upgrade process. If the terminal was properly prepared for the upgrade, no applications should be running. 12. Firmware files are downloaded to the terminal. This may take several minutes to 15 minutes.
  • Page 159 Transfer files and Upgrade Firmware 7-11 13. On touch or touch/screen terminals, you must calibrate the touch screen by selecting pointers in all four corners of the screen and pressing the middle of the screen when prompted. 14. Ignore the following message if it appears. It means RSView ME is being installed.
  • Page 160 7-12 Transfer files and Upgrade Firmware Publication 2711P-UM001D-EN-P - September 2005...
  • Page 161 Chapter Troubleshooting Chapter Objectives This chapter provides information on how to isolate and correct common operating problems with system components. • LED indicators • General troubleshooting • Troubleshooting components (display, touch screen, keypad, attached keyboard or mouse) • Ethernet • Advanced troubleshooting •...
  • Page 162 Troubleshooting General Troubleshooting This section provides a list of general troubleshooting steps to follow when trying to isolate problems. • Check for adequate power. An under-powered unit could result in unpredictable behavior. – The 400/600 DC powered terminals require 24V dc at 1.0 A. –...
  • Page 163 Troubleshooting • Check the messages at startup for errors. Record any error message and refer to the Startup Error Message table. • Check the voltages and temperatures (700-1500 only). From Configuration Mode, open Terminal Settings>System Information>Terminal Information. – Battery Voltage for 700-1500 terminals should be at least 2.75 V dc.
  • Page 164 Troubleshooting Troubleshooting This section provides tips on how to isolate problems with individual components of the terminal, including the display, touch screen, Components keypad, attached keyboard or mouse. Display Problems This section provides tips on how to isolate problems with the display.
  • Page 165 Troubleshooting Touch Screen Problems This section provides tips on how to isolate problems with the Touch Screen. • Check the catalog number of the unit. Verify that your terminal has a touch screen by looking at the label on the terminal.
  • Page 166 Troubleshooting Keypad Problems This section provides tips on how to isolate problems with the Keypad: • Check the Multi-Key/Hold-Off settings. From Configuration Mode, open Terminal Settings>Keypad>Keypad Settings. Is the Hold-Off Delay longer than expected, or are multiple key presses inhibited by Multi-Key Lockout? Check all configurable settings.
  • Page 167 Troubleshooting Problems with Attached Keyboard This section provides tips on how to isolate problems with the Keyboard. • Check for enabled Alt-Ctrl keys. From Configuration Mode, open Terminal Settings>Input Devices>Keyboard>Keyboard Settings. Are the keys enabled as expected? Check all configurable settings in Keyboard Properties.
  • Page 168 Troubleshooting • Check the LED indicators at the Ethernet connector. The Ethernet Problems green LED indicates a communications link and should be ON. The amber LED indicates data activity and should be flashing. Verify that there is a connection to the hub? •...
  • Page 169 Troubleshooting Advanced Troubleshooting 1. Take advantage of alternate connectivity - mouse versus touch screen, keyboard versus keypad, serial communications, and alternate Ethernet connections. 2. Know useful keyboard shortcuts so that you can navigate around the system without a mouse or touch screen. 3.
  • Page 170 8-10 Troubleshooting Startup Error Messages The table provides a list of system error messages that may display on startup and the recommended corrective action. The messages apply to all terminals except where indicated. When an error occurs, the terminal displays the error number with a text message. The word ERROR! appears under this line in different languages.
  • Page 171 Troubleshooting 8-11 Startup Information The table provides a list of system information messages that display at startup. The messages are in the order that they appear on the Messages terminal screen during startup and typically display for a few seconds. The messages apply to all terminals except where indicated.
  • Page 172 8-12 Troubleshooting Startup Sequence This flow chart provides a sequence of startup operations for the terminal and shows system information messages that display on the terminal. Power On Display copyright message, bootcode versions and "Testing..." message Initialize Video - Display "37 Video Initialized" (700-1500 only) Perform Power On Self Test Display "30 Watchdog Test"...
  • Page 173 Troubleshooting 8-13 System Identification Errors The error messages in this section appear on startup if incorrect or invalid components are used with the 700-1500 terminals. 700-1500 only • This dialog appears if a VersaView CE logic module is attached to a PanelView display module or a PanelView Plus logic module is attached to a VersaView CE display module.
  • Page 174 8-14 Troubleshooting • This dialog appears if the internal compact flash in the PanelView Plus logic module is corrupt. This is a fatal error. After pressing OK, you will be asked to power off the terminal and insert a valid 2711P-RWx internal compact flash card. Startup Problems If the terminal is configured to enter Configuration Mode at startup and does not, then reload the firmware.
  • Page 175 Troubleshooting 8-15 Clean the Display Window Use of abrasive cleaners or solvents may damage the ATTENTION display. Do not scrub or use brushes. To clean the display window: 1. Disconnect power from the terminal at the power source. 2. Use a clean sponge or soft cloth with a mild soap or detergent to clean the display.
  • Page 176 8-16 Troubleshooting Publication 2711P-UM001D-EN-P - September 2005...
  • Page 177 Appendix Specifications Electrical DC Power 400 and 600 Input Voltage DC 24V dc nom (18…30V dc) Power Consumption DC 25 W max (1.0 A at 24V dc) DC Power 700 - 1500 Input Voltage DC 24V dc nom (18…32V dc) Power Consumption DC 70 W max (2.9 A at 24V dc) AC Power 400 and 600...
  • Page 178 Specifications Display Display Type 400 and 600 Monochrome Monochrome Passive Matrix, Film Compensated Super-Twist Nematic (FSTN) 600 - 1500 Color Color Active Matrix TFT Thin-Film Transistor with LCD Liquid Crystal Display Display Size, Diagonal 3.8 in 5.5 in 6.5 in 1000 10.4 in 1250 and 1250 High-Bright...
  • Page 179 Specifications Mechanical Weight (for base unit without modules) 562 g (1.24 lb) 400 Keypad 930 g (2.05 lb) 600 Keypad or Keypad & Touch 789 g (1.74 lb) 600 Touch 1.9 kg (4.2 lb) 700 Keypad or Keypad & Touch 1.7 kg (3.8 lb) 700 Touch 2.9 kg (6.3 lb)
  • Page 180 Specifications Agency Certifications UL Listed Industrial Control Equipment UL Listed Industrial Control Equipment for use in Canada UL Listed Industrial Control Equipment for use in: • Class I, Div 2, Group A, B, C, D • Class I, Zone 2, Group IIC •...
  • Page 181 USB ports of the terminals. PanelView Plus PanelView Plus Device Vendor Model 700-1500 400 and 600 USB Keyboard Rockwell Automation Cat. No. 6189-KBDEPU1U Ortek MCK-600USB Dell RT7D10 Rockwell Automation Cat. No. 6189-KBDEPC1U Keyboard/Mouse USB Mouse...
  • Page 182 Compatible USB Devices Publication 2711P-UM001D-EN-P - September 2005...
  • Page 183 Appendix Available Fonts for Terminal Applications The following fonts are pre-installed on PanelViewPlus/VersaView CE terminals: • True Type fonts (scalable) – Tahoma.ttf (proportional) – Courier.ttf (fixed width) – Arial.ttf (proportional) • (23) fonts of various sizes migrated from PanelView Standard and PanelView "e"...
  • Page 184 Fonts CD (www.theautomationbookstore.com) at no charge. To download fonts that can be used on the PanelView Plus/VersaView CE terminals via the network, see the Rockwell Automation Knowledgebase (http://support.rockwellautomation.com). Select Knowledgebase under Self-Service Support (or Online Tools) and then enter Tech Note ID A66647102.
  • Page 185 Available Fonts for Terminal Applications Fonts File Name Size (Bytes) Trebuchet MS Trebuchet MS trebuc.ttf 69,688 Trebuchet MS Bold trebucbd.ttf 66,444 Trebuchet MS Bold Italic trebucbi.ttf 66,348 Trebuchet MS Italic trebucit.ttf 72,560 Verdana Verdana verdana.ttf 149,752 Verdana Bold verdanab.ttf 137,616 Verdana Bold Italic verdanaz.ttf 154,800...
  • Page 186 Available Fonts for Terminal Applications Fonts File Name Size (Bytes) Korean Locale Specific Support GL_CE gl_ce.ttf 4,130,084 Gulim & GulimChe (Choose 1) Gulim & GulimChe (Subset 1_30) gulim_1_30.ttc 3,010,268 Gulim & GulimChe (Subset 1_40) gulim_1_40.ttc 4,683,896 Gulim & GulimChe (Subset 1_50) gulim_1_50.ttc 7,128,756 Gulim &...
  • Page 187 Index USB ports compatibility of components AC power configuration mode 400-600 loading application 1-9, 3-7 700-1500 running application connect terminal settings Protective Earth connection ControlNet 1-17 AC power supply 700-1500 6-2, 6-21 cables 5-19 installation 6-18, 6-22 compatible controllers 1-12 accessories 4-10 configuration...
  • Page 188 Index DHPlus pre-installed function keys cables 1-6, 1-11 configuration keypad terminals 6-16 network connections Functional Earth connection 6-12 port connectors settings in configuration mode 6-13 status indicators 4-35 hardware monitor diagnostics hazardous locations 4-16 in Configuration Mode display USB port 1-10, 2-4 high-bright display 400-600...
  • Page 189 Index keyboard outdoor installation troubleshooting high-bright displays 4-24 keyboard settings keyboard/mouse compatible Preface-i packing list keyboards, compatible power terminal block 1-14, 5-20 keypad legend inserts install 4-24 keypad settings remove troubleshooting print setup 4-28 for alarms 4-28 for diagnostic messages 4-28 for displays 4-41...
  • Page 190 Index 4-10 Simple Network Management Protocol serial 4-43 6-11 short date format (SNMP) 4-30 startup options 6-11 SNMP Protocol 4-32 startup tests software 4-34 system event log specifications 4-35 system information agency certifications 4-35 terminal info electrical 4-39 time environmental 4-42 time format mechanical...
  • Page 191 Index Publication 2711P-UM001D-EN-P - September 2005...
  • Page 193 Outside United Please contact your local Rockwell Automation representative for States return procedure. ö Publication 2711P-UM001D-EN-P - September 2005 Supersedes Publication 2711P-UM001C-EN-P - October 2004 Copyright © 2005 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.