Self-Diagnostics Function

Numbers in the following table indicate the number used in Nomenclature on pages 15 and 17.
(6) Main display
---
Noise detected in voltage or
current
h\t
Overheated
e01
Undervoltage alarm set value
memory error
Memory error of alarm set value
e02
of maintenance forecast monitor
or total run time monitor
e03
Other memory error
e04,
Hardware error
e05
(S8VS-48024A/B only)
Note: 1. External noise is probable as a cause of "
2. Operation out of the derating curve area, ventilation error, and incorrect mounting direction are probable as a cause of "
h\t
3. If the "
" error state continues for more than three hours, the maintenance forecast monitor function becomes invalid. The Yrs output
(Maintenance forecast output terminal (Yrs)) will remain OFF (no continuity).
Replace the power supply if this condition occurs even if the output is correct, as internal parts may be deteriorated.
h\t
4. The "
" error detection function is only for the S8VS-@@@24A@@.
28
Description
Output status
No change
Maintenance
forecast output
terminal (Yrs) turns
OFF.
Undervoltage
output terminal (DC
LOW) turns OFF.
Maintenance
forecast output
terminal (Yrs) turns
OFF or total run
time output terminal
(kh) turns OFF.
Undervoltage
output terminal (DC
LOW) turns OFF.
Maintenance
forecast output
terminal (Yrs) turns
OFF or total run
time output terminal
(kh) turns OFF.
Undervoltage
output terminal (DC
LOW) turns OFF.
Maintenance
forecast output
terminal (Yrs) turns
OFF or total run
time output terminal
(kh) turns OFF.
---
e01
", "
", "
Restoration method
Automatic reset.
Automatic reset.
Press and hold the Up Key U (9) or Down
Key D (10) for three seconds and check
the set value of the corresponding point.
The set value must return to the shipment
setting
Turn the AC input OFF then ON again.
If the Product is not reset, contact the
dealer.
Turns the AC input OFF then ON again.
If the Product is not reset, contact the
dealer.
e02
e03
e04
e05
", "
", "
", and "
" errors.
Setting after
restoration
No change
No change
Shipment setting or
value set in the
setting mode again
No change
No change
h\t