The FE port resembles the RS485 port. Follow the silk screen when connecting
communications cables as, if the RS485 port is mistaken for the FE port during cable
connection, the WebUI cannot be connected. Conversely, if the FE port is mistaken for the
RS485 port during cable connection, RS485 communication fails.
Dry contact signals take effect after you set them. Disable unused dry contact signals on
the monitoring system.
In a parallel system, ensure that used dry contacts properly connect to each UPS.
The monitoring interface card provides external ports as well as monitoring and control
functions for the MDU. The ports include the ambient temperature and humidity sensor port,
iBattery port, FE port, battery temperature monitoring port, and network management port.
The MDU monitors the UPS, allows users to set parameters, delivers commands, reports
information, and displays the UPS key information and parameters on the LCD.
Figure 2-27 Monitoring interface card
Table 2-7 Ports on the monitoring interface card
Port
DO_1
DO_2
DO_3
Issue 05 (2019-02-27)
DO_1 to DO_4 meet the maximum voltage and current requirements of 30 V DC/1 A or 60 V DC/0.5 A.
Copyright © Huawei Technologies Co., Ltd.
Silk Screen
NO
COM
NO
COM
NO
2 Overview
Description
DO_1 is used to output
alarms and indicates critical
alarms by default. It can be
set to indicate minor alarms,
bypass mode, battery mode,
or low battery voltage.
DO_2 is used to output
alarms and indicates minor
alarms by default. It can be
set to indicate critical
alarms, bypass mode,
battery mode, or low battery
voltage.
DO_3 is used to output