System Operation; Operation Modes; Recipe (Color) Change; Solvent Push - Graco ProControl 1KS Operation

Automatic system for fluid management of single component coatings. includes flow control, flushing, and color change, for professional use only, approved for use in explosive atmospheres except the easykey
Hide thumbs Also See for ProControl 1KS:
Table of Contents

Advertisement

System Operation

Operation Modes

Mix
System mixes and dispenses material (apply Mix input).
Standby
Stops the system (remove Mix input).
Purge
Purges the system, using air and solvent (apply Purge

Mix Manifold Valve Settings

To open dose or purge valves, turn hex nut (E) counter-
clockwise. To close, turn clockwise. See Table 14 and
F
. 101.
IG
Valve
Dose (see
F
. 101)
IG
Purge (see
F
. 101)
IG
3A1080H
Table 14: Mix Manifold Valve Settings
Setting
Hex nut (E) 1-1/4 turns out
from fully closed
Hex nut (E) 1-1/4 turns out
from fully closed
input).

Recipe (Color) Change

The process when the system automatically flushes out
the old color and loads a new color. See pages 104-116.

Solvent Push

The Solvent Push feature enables the user to save
some mixed material by pushing it out to the gun with
solvent. The feature requires an accessory solvent
meter. See page 101 for complete information.
F
. 101. Valve Adjustment
IG
Function
Limits maximum fluid flow rate into integrator
and minimizes valve response time.
Limits maximum fluid flow rate into integrator
and minimizes valve response time.
System Operation
E
TI11581a
91