17-2. Points to remember when installing
• The product shall be installed at a place which can withstand the weight and vibration of the in-
door.
• To allow maintenance after refrigerant piping, drain piping, and electric wiring connection and in-
stallation, provide an installation service space and an inspection port, as required.
*Installation service space is shown on
• Be careful when installing the unit at the following places.
Condition
When the
If the indoor unit is installed where the installation height
ceiling is high.
given in the installation manual is exceeded, the
temperature difference between the floor and ceiling of the
room will be large and the heating effect will be poor.
Moreover, even if the indoor unit is installed within the
installation height, a similar phenomena will occur when
installed in a room in which the doors are opened and
closed frequently and hot air circulation is obstructed by
furniture such as desks or chairs.
When lower
When the lower level of the room is a semi-open space
level directly
such as warehouse or parking lot the surface temperature
contacts the
of the flooring will become low and the radiation of cold
outside air.
from the floor will increase.
In this case, even if the room temperature is suitable, you
may feel the foot level is cold.
When the
When an indoor unit is installed in a position where the
airflow
outlet airflow will directly contact people, a draft may be
distribution is
felt.
poor.
In addition, when there are obstructions in the path of the
intake and outlet airflow, the air distribution may become
extremely bad.
When inside the
When the indoor unit is installed where the inside of the
ceiling is high
ceiling is 30 °C (86 °F) RH80% or greater, the dew point
temperature
temperature of the outer perimeter may become higher
and high
than the cabinet surface temperature and moisture will
humidity.
condense on the surface of the cabinet and water drops
may fall inside the room. →Refer to Fig. A.
In addition, the humidity may vary considerably the same
as when the inside of the ceiling is close to hermetically
sealed and used as the outside air intake path.
17-2. Points to remember when installing
"Dimensions"
Contents
Moist air curve
Relative humidity 80 %
Dry bulb temperature 30 °C (86 °F)
- 154 -
on page 12.
Countermeasures (Reference)
1. Switch the setting to the high
ceiling mode.
2. Install a circulator.
3. Arrange the furniture in the
room so that it does not obstruct
the hot air.
1. Adjust the louver fins or take
other measures matched to the
site.
2. Change the indoor unit outlet.
1. Add heat insulating material to
the outside of the indoor unit
cabinet.
*Regarding the cassette type,
use of optional High humidity
correspondence kit is
recommended.
2. Strengthen the heat insulating
material of the refrigerant piping
and drain piping too. →Refer to
Fig. B.
3. When the humidity inside the
ceiling changes considerably,
install a ventilation port.
Condition which
requires addition
of outside heat
insulation
Fig. A
17. Indoor unit installation precautions