Fujitsu AUU7RLF Design & Technical Manual page 113

Multi: 5 rooms type
Hide thumbs Also See for AUU7RLF:
Table of Contents

Advertisement

¢ Installation
 Connection pattern
NOTE: Connection pattern is different according to type of Indoor unit.
Wall mounted type
 Pattern A
Connect the end of remote controller cable directly to the exclusive terminal block.
M4 screw
Terminal block
NOTE: It may be failed if it is connected to the outdoor unit or the terminal block for power sup-
ply.
 Pattern B
1. Modify the remote controller cable as follows:
• Use a tool to cut off the terminal on the end of the remote controller cable and then re-
move the insulation from the cut end of the cable as shown in following figure.
• Connect the remote controller cable and connecting cable as shown in following figure.
• Be sure to insulate the connection between the cables.
13-4. Simple remote controller (UTY-RSNUM: Optional part)
Indoor unit types
Compact cassette type
Slim duct type
ASU7RLF1, ASU9RLF1, ASU12RLF1, and
ASU15RLF1
ASU18RLF and ASU24RLF
Floor type
Remote controller
terminal block
Remote controller cable
Remote controller cable
Outdoor unit or Power supply terminal
block or Remote controller terminal block
PCB
Connecting
cable
White
Red
White
Insulated
Red
connection
Black
- 107 -
Connection pattern
Pattern A
Pattern B
Pattern C
Black
13. Remote controller