Fujitsu AUU7RLF Design & Technical Manual page 184

Multi: 5 rooms type
Hide thumbs Also See for AUU7RLF:
Table of Contents

Advertisement

Indoor unit connect-
Outdoor temperature
ing capacity
kBtu/h
°CDB
-10.0
34
NOTE: Specifications are based on the following conditions.
• Power source of specifications: 230 V
• 2 or more indoor units should be connected.
• Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit]
• The total ability of connected a indoor unit is from 34,000 Btu up to 54,000 Btu.
• Input in the table are calculated based on the maximum indoor unit input combina-
tions.
6-2. Cooling capacity
17.8 °CDB
12.2 °CWB
TC
IP
TC
8.33
1.11
9.41
-5.0
8.33
1.10
9.41
0.0
8.33
1.10
9.41
5.0
8.33
1.22
9.41
10.0
8.33
1.35
9.41
15.0
8.33
1.86
9.41
20.0
8.33
2.37
9.41
25.0
8.33
2.61
9.41
30.0
8.33
2.85
9.41
35.0
8.33
3.04
9.41
40.0
7.24
2.82
8.19
46.1
6.16
2.61
6.96
Indoor temperature
21.1 °CDB
23.9 °CDB
15.6 °CWB
17.2 °CWB
IP
TC
IP
1.13
9.92
1.14
10.60
1.12
9.92
1.13
10.60
1.12
9.92
1.13
10.60
1.25
9.92
1.26
10.60
1.37
9.92
1.39
10.60
1.89
9.92
1.91
10.60
2.41
9.92
2.43
10.60
2.65
9.92
2.67
10.60
2.90
9.92
2.92
10.60
3.09
9.92
3.12
10.60
2.87
8.63
2.90
2.65
7.34
2.67
- 178 -
26.7 °CDB
29.4 °CDB
19.4 °CWB
21.7 °CWB
TC
IP
TC
IP
1.15
11.36
1.17
1.15
11.36
1.16
1.14
11.36
1.15
1.27
11.36
1.28
1.40
11.36
1.42
1.93
11.36
1.95
2.45
11.36
2.48
2.70
11.36
2.74
2.95
11.36
2.99
3.15
11.36
3.19
9.20
2.93
9.88
2.96
7.80
2.70
8.40
2.73
32.2 °CDB
22.8 °CWB
TC
IP
11.71
1.17
11.71
1.17
11.71
1.16
11.71
1.29
11.71
1.42
11.71
1.96
11.71
2.50
11.71
2.75
11.71
3.00
11.71
3.21
10.18
2.98
8.66
2.75
6. Capacity table

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents