Fujitsu AUU7RLF Design & Technical Manual page 180

Multi: 5 rooms type
Hide thumbs Also See for AUU7RLF:
Table of Contents

Advertisement

Indoor unit connect-
Outdoor temperature
ing capacity
kBtu/h
°FDB
34
NOTE: Specifications are based on the following conditions.
• Power source of specifications: 230 V
• 2 or more indoor units should be connected.
• Pipe length: 24.6 ft (7.5 m), Height difference: 0 ft (0 m) [Outdoor unit - Indoor unit]
• The total ability of connected a indoor unit is from 34,000 Btu up to 54,000 Btu.
• Input in the table are calculated based on the maximum indoor unit input combina-
tions.
6-2. Cooling capacity
64 °FDB
54 °FWB
TC
IP
TC
14
28.4
1.11
32.1
23
28.4
1.10
32.1
32
28.4
1.10
32.1
41
28.4
1.22
32.1
50
28.4
1.35
32.1
59
28.4
1.86
32.1
67
28.4
2.37
32.1
77
28.4
2.61
32.1
87
28.4
2.85
32.1
95
28.4
3.04
32.1
104
24.7
2.82
28.0
115
21.0
2.61
23.8
Indoor temperature
70 °FDB
75 °FDB
60 °FWB
63 °FWB
IP
TC
IP
TC
1.13
33.9
1.14
36.3
1.12
33.9
1.13
36.3
1.12
33.9
1.13
36.3
1.25
33.9
1.26
36.3
1.37
33.9
1.39
36.3
1.89
33.9
1.91
36.3
2.41
33.9
2.43
36.3
2.65
33.9
2.67
36.3
2.90
33.9
2.92
36.3
3.09
33.9
3.12
36.3
2.87
29.5
2.90
31.5
2.65
25.1
2.67
26.8
- 174 -
80 °FDB
85 °FDB
67 °FWB
71 °FWB
IP
TC
IP
TC
1.15
38.8
1.17
40.0
1.15
38.8
1.16
40.0
1.14
38.8
1.15
40.0
1.27
38.8
1.28
40.0
1.40
38.8
1.42
40.0
1.93
38.8
1.95
40.0
2.45
38.8
2.48
40.0
2.70
38.8
2.74
40.0
2.95
38.8
2.99
40.0
3.15
38.8
3.19
40.0
2.93
33.7
2.96
34.8
2.70
28.7
2.73
29.6
90 °FDB
73 °FWB
IP
1.17
1.17
1.16
1.29
1.42
1.96
2.50
2.75
3.00
3.21
2.98
2.75
6. Capacity table