13) Room temperature control for wired remote controller sensor
NOTE: Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to "Both" (01).
Ensure that the thermo sensor icon is displayed on the remote controller screen.
Function number
92
(For cooling)
14) Heat insulation condition (building insulation)
Heat insulation conditions differ according to the installed environment.
"Standard insulation" (00) allows system to rapidly respond to the cooling or heating load changes.
"High insulation" (01) is when the heat insulation structure of the building is high and does not re-
quire system to rapidly respond to cooling or heating load changes.
When "High insulation" (01) is selected:
• Overheating (overcooling) is prevented at the start-up.
• All room-temperature control settings (Function 30, 31, 92, and 93) will reset to "No correction
0.0 °F (0.0 °C)".
Function number
95
NOTE: When changing Function 95, perform this setting before other room-temperature control
settings (Function 30, 31, 92, and 93). If Function 95 is not set first, room-temperature con-
trol settings (Function 30, 31, 92, and 93) will be reset and you must re-do them again.
14-5. Function details
Setting value
00
01
02
03
04
05
06
07
08
93
(For heating)
09
10
11
12
13
14
15
16
17
Setting value
00
01
Setting description
No correction 0.0 °F (0.0 °C)
No correction 0.0 °F (0.0 °C)
-1 °F (-0.5 °C)
-2 °F (-1.0 °C)
-3 °F (-1.5 °C)
-4 °F (-2.0 °C)
-5 °F (-2.5 °C)
-6 °F (-3.0 °C)
-7 °F (-3.5 °C)
-8 °F (-4.0 °C)
+1 °F (+0.5 °C)
+2 °F (+1.0 °C)
+3 °F (+1.5 °C)
+4 °F (+2.0 °C)
+5 °F (+2.5 °C)
+6 °F (+3.0 °C)
+7 °F (+3.5 °C)
+8 °F (+4.0 °C)
Setting description
Standard insulation
High insulation
- 138 -
Factory
setting
More cooling
Less heating
Less cooling
More heating
Factory setting