Installation
Shunt Trip and Auxiliary Contact Interface Connection
Note:
When installing shunt trip and auxiliary contact wiring to the RPP interface terminals, conduit must be
installed between the device and the RPP. Install the control wiring in separate conduit from the
power wiring.
To wire the terminals:
1.
Verify that the RPP is turned off and all power sources are removed.
2.
Route the RPP interface wiring through either the top or bottom of the cabinet to the RPP interface
terminals. See Figure 14 for wiring access and terminal locations.
3.
Connect the wiring. See Figure 15 for terminal assignments and Table 7 for termination requirements.
Optional Aux and Shunt Trip Terminal Block
for Main Breaker. See Figure 15 for details.

Figure 14. Shunt Trip and Auxiliary Contact Terminal Location (each side)

24
Eaton Remote Power Panel (RPP) User's Guide 164202125—Rev 5